CallWhatsApp
Skip to main content
Snowflake Aircon Services

Coastal Unit Losing Gas Again: Salt Ate Through The Pipe Fitting

Topping up refrigerant more than once in the same year signals a leak, not just normal consumption. In coastal locations, the outdoor pipe joints face an additional threat. Salt-air corrosion can thin metal fittings slowly enough that the leak only shows up as gradually declining cooling.

Case Details

UnitSamsungWall-mounted
Age5 years old
LocationCondoSouthern Islands, Singapore
ReportedThe aircon has been topped up twice this year and is losing cooling again. The unit faces the sea, a previous contractor keeps topping up and saying everything looks fine, but the gas never holds.

Diagnostic Turning Point

  • Concern: Risk appeared to be an internal compressor leak requiring full system replacement.
  • Key check: Inspected outdoor pipe joints for corrosion damage and tested with leak detector fluid before just topping up gas

What We Checked

Two top-ups in one year with the same problem returning confirms a leak. The seaside exposure made the outdoor pipe joints the first place to inspect.

  • Refrigerant pressure was low again, confirming ongoing loss.
  • Indoor coil and pipe joints showed no signs of leakage.
  • Outdoor unit flare nut had visible surface corrosion and pitting from salt exposure.
  • Leak detector fluid applied at the corroded flare nut confirmed active seepage.

The Diagnosis

Salt-laden coastal air had corroded the flare nut at the outdoor unit pipe connection over the years. The corrosion thinned the metal wall enough to allow slow refrigerant seepage. Each top-up restored cooling temporarily, but the leak continued because the corroded fitting was never replaced.

What Fixed It

The compressor is not leaking internally, the corroded flare nut at the outdoor pipe joint needs replacing. Once the new fitting is installed and the joint sealed, the system should hold gas normally. Applying protective coating to exposed outdoor fittings can slow future corrosion in this location.

After the corroded flare nut was replaced and the joint resealed, the system was charged and pressure-tested. Gas pressure held stable and the cycle of repeated top-ups stopped.

Why This Happens

Why coastal aircon units lose gas at the outdoor pipe joints.

  • Salt-laden air accelerates corrosion on exposed metal fittings at the outdoor unit. Flare nuts and service valve connections are especially vulnerable.
  • The corrosion thins the fitting wall gradually, creating a slow seepage point that is not detectable during a routine top-up visit.
  • Replacing the corroded fitting and sealing the joint stops the leak permanently. Repeated top-ups without inspecting the joint just delays the permanent fix.

Ready to Get Started?

Tell us what’s going on. Symptoms, setup, photos, anything we should know. We’ll assess and come back with the right next step.

WhatsApp us