Aircon diagnostic cases
Diagnostic case notes: the fault pattern, what we tested, what we found, and why we called it that way. Details anonymised, diagnostics intact.
Find a similar case
Search by what you're noticing or what you're comparing: symptom, quote concern, brand, property type, location, or confirmed fault.
Orchard office stayed warm after partition works. The supply path was blocked by the new layout, not a weak aircon system.
Bishan HDB unit blowing cold air but airflow kept weakening each week. We opened the unit and traced it to heavy buildup on the fan barrel and coil.
Teck Ghee HDB unit worked in the morning but cut out every afternoon. Outdoor unit in an alcove with blocked airflow. Thermal protection was tripping.
Changi landed home breaker trips clustered around rainy evenings. Compressor tested normal. Rusty outdoor switch box with failed seals was the cause.
Daikin C4 in Clementi caused mid-cycle shutdowns. The temperature sensor was giving false readings. Sensor replacement cleared the fault.
All four units in a Tampines condo showed LG CH05 at once. Wiring tested fine. Outdoor control board had failed. Replaced the board.
All four rooms in a Sengkang HDB lost cooling simultaneously. The LG outdoor unit had a gas leak at the pipe connections, requiring full system replacement.
An Ang Mo Kio HDB flat leaked days after a routine service. The drain hose had been reseated at the wrong angle behind the trunking, not a new fault.
Jurong East HDB aircon auto mode kept shutting off every few minutes. The sensor read the room as colder than it was. One part swap restored stable cycling.
An older Bedok HDB outdoor unit rocked on startup. It was sitting on an unlevel ledge base, not a fault with the compressor.
Bukit Batok HDB bedroom unit leaked after servicing. The drain joint was slightly loose, not a cracked tray or major repair.
Pasir Ris HDB bedroom was slow to cool near a green edge. A privacy screen too close to the outdoor unit trapped its exhaust. Clearance fixed it.
Changi Village HDB wall unit buzzing loudly when running. Mounting plate had loosened from the wall. Resecured bracket stopped the noise. Compressor was fine.
A Bishan condo cassette blew weak air right after a chemical wash. A filter clip was never reseated, letting the filter sag into the airflow path.
Tengah BTO unit was never cold from day one. System was undercharged by the installer for the pipe run length. Topped up to correct charge and cooling started.
Toa Payoh HDB breaker trips with a hot smell pointed to compressor failure. Heat-damaged isolator connection was the actual cause. No compressor work needed.
Sengkang BTO bedroom leaked at trunking. A renovation-era shelf had crushed the drain pipe's bore, so the fix relieved the pinch, not another flush.
Rochor shophouse aircon tripped after rain. A sun-cracked cable sheath on an exposed rooftop run let moisture in, not a failed isolator or compressor.
A Bukit Batok HDB outdoor unit clicked on every rotation in the afternoon. The fan blade had warped from heat, not a motor fault.
A Bukit Panjang HDB outdoor unit rocked on a hillside ledge in wind gusts. Support brackets were never fully tightened at install.
Cafe unit in Outram losing cooling despite quarterly servicing. Thick grease sludge on evaporator. Chemical overhaul restored cooling, no parts needed.
Sembawang Canberra flat had weak airflow after nearby renovation. Fine dust loaded the blower, not a gas leak or failing motor.
MHI unit in Jurong East still faulted after a capacitor swap. The outdoor control board output path had no output to the compressor. Board replacement fixed it.
Hougang HDB ceiling cassette with weak airflow. Corroded motor contacts were reducing fan speed, not a blocked filter. Motor contacts cleaned and restored.
Cassette unit in Choa Chu Kang leaking onto office equipment. Drain line was fully blocked with sludge. Drain pan was intact. Drain flush fixed it.
Marina Bay condo cassette leaking during heavy tropical rain. The condensate pump float switch was slow to trigger at peak load. Recalibration fixed it.
Joo Koon factory office cassette blew warm air. A gas-flow valve was stuck partly closed, starving the indoor coil. Compressor was fine.
Marina South office cassette rattled after ceiling service. The panel was not seated flat, not a failed fan motor or compressor.
Dhoby Ghaut office cassette rattled at medium fan speed. Loose fan blade retaining clip was the actual cause, not compressor bearing fault.
Raffles Place office cassette started dripping after routine cleaning. Debris in the drain line caused a partial blockage. No cracked coil, no pump fault.
Intermittent ceiling drip in Marina South office persisted after a drain replacement. A concealed joint gap upstream was the actual source.
Daikin A3 on a ceiling-concealed unit in Bukit Timah. drain pump motor had failed. Water backed up. Replaced the drain pump.
Dhoby Ghaut office ceiling unit dripped after quarterly service. Drain fitting was loose from reassembly. Reconnected and tested. Leak stopped.
Hitachi ceiling-concealed unit in a Serangoon condo leaked only after power outages. The pump's own safety cut-off needed a reset, not a replacement.
A Changi landed home aircon tripped once during a storm after a gas top-up visit. A loose isolator terminal screw, shaken by storm vibration, was the cause.
A Choa Chu Kang industrial unit rattled on startup. Nearby machinery vibration had crumbled its leveling blocks, not a fault in the unit itself.
A Clarke Quay restaurant unit dripped during dinner service. The drain line sagged around a heritage structural beam, not a cracked pan.
A new Clementi condo unit ran warm after installation. An energy-saving mode was left on from setup, capping the compressor, not a defective unit.
LG CH10 in Woodlands HDB. Diagnosed as control board fault. Actual cause was a cracked blower wheel catching on the housing. Wheel replaced, motor fine.
Novena clinic room aircon shut down after long sessions. Dust on the condenser trapped heat, so cleaning and airflow checks came before control-board work.
Outram clinic room cooled weakly after long runtime. A return grille packed with lint was restricting airflow, not a gas issue.
Changi coastal condo bedroom was not cooling well. Salt and fine grit packed the outdoor condenser fins, so airflow was restored before any gas work.
Katong condo aircon blowing but not cold. Previous company said gas leaked and coil needed replacing. Chemical servicing of caked evaporator restored cooling.
Sentosa unit kept losing gas after top-ups. Salt-air corrosion had damaged the outdoor pipe fitting. Resealing stopped the repeat loss.
Novena condo concealed unit dripping from two points. drain pump had seized from scale buildup. Pump replaced, dripping stopped.
River Valley condo bedroom had musty aircon smell. A wet coil and blocked drain pan held moisture inside the unit after rainy days.
Paya Lebar condo aircon started dripping after renovation. Fine dust had collected in the drain path, so the choke was cleared before bigger work.
Marine Parade condo cooling cut out under load after gas top-ups. The fault was a salt-corroded outdoor electrical terminal, not the refrigerant joint.
York multi-split in a landed Hougang home lost cooling evenly in every room over a year. A full check confirmed genuine compressor wear, not a cheaper fix.
A Downtown Core high-rise condo unit hummed through the wall. Its internal compressor mounts had perished from years of wind sway, not the external feet.
Upper Thomson landed home wall unit dripped intermittently on humid days. Mineral buildup at a downstream joint narrowed the drain, so it was cleared.
Orchard office ducted system gradually lost airflow. Staff feared duct deterioration. Return air filter in the ceiling void had not been cleaned in years.
A Mitsubishi Heavy ducted system at a Sembawang industrial site kept resetting itself. A loose terminal connection was the cause, not the control board.
Hougang HDB aircon showed an error after renovation works nearby. The fault was a nicked communication wire in trunking, not a failed board.
Panasonic H11 appeared after a Bedok thunderstorm. A loose indoor connection caused the fault. Reseating it cleared the error.
Samsung error appeared after servicing in Marina East. The board was locked in fault state, not dead. Reset and checks restored cooling.
Tengah HDB error code appeared right after renovation. Signal wire had been nicked and rejoined with wires swapped. Correcting the sequence cleared the error.
LG CH05 in Ang Mo Kio kept returning. The outdoor wire connector was corroded, not the control board. Cleaned and refitted the connection.
Daikin A3 kept returning after drain clearing in Toa Payoh. A sag in the drain line inside the false ceiling trapped sludge. Rerouted the line.
Mitsubishi E6 in Yishun traced to a corroded wire splice in a ceiling void junction box. Weatherproof re-splice resolved it.
York E6 in Jurong East kept returning after resets. Corroded outdoor wire connections were cleaned and refitted. No board replacement needed.
Samsung E1 after renovation in Jurong West HDB. Cable insulation nicked during drilling. Exposed wire shorted against trunking. Fixed with no parts replaced.
Choa Chu Kang ducted LG office system showed CH38 with every zone fading together. The leak traced to the branch distributor; the outdoor unit needed no work.
Pioneer factory office cassette dripped again after cleaning. Dust sludge blocked the drain line, not a cracked pan or failed pump.
On-and-off aircon trips in a Sungei Kadut factory office traced to a corroded isolator switch. Wiring was intact. No cable replacement needed.
Cassette unit in Tuas factory losing cooling gradually. Condenser coil coated in industrial dust. Chemical servicing restored full capacity.
Pioneer factory office became warm again. Years of oil-laden grit cracked the condenser fan blade, cutting airflow though the coil looked only lightly dusty.
Sungei Kadut factory office cassette had weak airflow. Sawdust coated the blower wheel, not a motor or gas fault from workshop dust.
Telok Blangah HDB aircon not cold at five years old. Condenser coil was crusted with salt residue from sea breeze. Chemical servicing restored cooling.
A Kallang HDB flat near Little India cooled poorly. Grease from food stalls had coated the condenser fins, not a refrigerant leak or failing compressor.
An LG outdoor unit on a high-floor Punggol condo corroded in just 4 years due to direct wind and rain exposure, causing a gas leak far earlier than expected.
Fujitsu ceiling-concealed case in Bukit Timah: coil fouling behind the filter, not the compressor, explained a year of fading cooling. A coil clean fixed it.
Museum area gallery office felt warm after a display partition was added. The return air path was blocked, not a gas or compressor fault.
Tanglin landed room became warm in the afternoon. Seed pods blocked the garden-facing condenser, so heat could not escape properly.
Newton condo unit topped up twice in one year but kept losing cooling. A pinhole leak in the concealed copper pipe behind the wall was the cause.
A welded gas leak on an LG outdoor unit in Woodlands failed again. Cooling returned briefly before a new leak appeared on the same corroded pipe section.
Yishun HDB with repeated cooling loss after multiple top-ups. Focused leak checks on the service port traced the hidden source to a faulty service valve core.
Macpherson HDB case: regular servicing missed deep evaporator coil fouling. Chemical servicing reopened the coil and restored cooling.
A Geylang shophouse leaked after a cleaning visit. The drain hose was never properly seated behind the access panel, not a new drainage fault.
Downtown Core office became warm by afternoon. The condenser was recycling hot air inside a service recess, so airflow planning mattered more than gas.
Sharp 6-0 in Woodlands HDB. Fan motor grinding on a 13-year-old unit. Bearings worn out. Owner chose replacement over repair given the age.
Tampines HDB bedroom aircon dripped after years of use. A drain choke behind the trunking caused backup, not a cracked tray or gas problem.
Ang Mo Kio condo with three ceiling cassettes struggling to cool and high monthly bills. Outdoor unit was too small for the indoor capacity.
A Hougang HDB flat leaked days after routine servicing. The pump's mounting bracket screws were left loose, not a new fault in the pump itself.
Ang Mo Kio Daikin with ice on pipe. Assumed low gas. Airflow pattern and coil condition pointed to buildup restricting the evaporator, not a refrigerant issue.
Punggol HDB indoor unit blew air but the outdoor side stayed silent. A starter relay fault in the start path was the cause. Not a compressor failure.
A Jurong East HDB outdoor unit rocked on startup. A corroded, seized mounting bolt let one corner shift, not a fault inside the compressor itself.
An older Jurong West HDB outdoor unit rattled at night. Anchor bolts had backed out of aged, crumbling wall concrete, not a loose compressor or fan fault.
A Kallang River condo bedroom stayed warm despite a working aircon. Site hoarding was blocking the outdoor unit's air path, not a sizing issue.
Dairy Farm landed home aircon gradually lost cooling. Told the compressor was failing, but the condenser mesh was actually caked with renovation dust.
Bukit Timah landed master bedroom became weak after pipe work. A loose flare joint was found before replacing the unit or topping up gas blindly.
Serangoon landed outdoor unit rattled after a storm. A bent fan guard mounting tab was touching the blade tip, not a compressor fault or motor failure.
Seletar landed aircon dripped and smelled musty after rain. Biofilm inside the drain tray caused both, not a cracked tray or failed indoor unit.
LG CH35 case in Bedok: leak tracing found corroded outdoor pipe connections. After sealing and recharge, cooling returned without parts replacement.
LG CH38 in Bukit Panjang: a pressure test found a loose flare-nut joint, not corrosion. Retightening and a recharge restored cooling without replacement.
LG CH38 hit one Yishun condo bedroom on a multi-split while other rooms stayed cold. The leak was a pinhole in that room's own indoor coil.
LG CH38 case in Toa Payoh: a chemical wash loosened a nearby joint. Resealing it stopped the leak, without blaming the wash or the unit's age.
LG system 3 in Serangoon had a gas leak along a long pipe run. pressure hold testing narrowed it to the outdoor unit connections, not the concealed piping.
Cooling kept dropping after gas top-ups in Bukit Batok. We traced the leak to corroded LG outdoor unit connections and presented three repair options.
Clementi HDB wall unit rattled loudly during startup then went quiet. Mounting was solid. Worn motor bearings let the rotor shift during spin-up.
Tanglin low-rise condo bedroom aircon rattled at night. A loose trunking cover vibrated, not compressor or indoor fan failure.
Jurong East mall shop cassette dripped late in the day. The discharge hose had worked loose from the pump outlet after hours of runtime, not a cracked tray.
A new Marina East condo leaked after installation. The drain line was pitched the wrong way on the new run, not a defective unit.
A Marina South office outdoor unit rattled against the wall in waterfront gusts. Refrigerant pipe clips were loose, not a fault.
A Marine Parade condo outdoor unit wobbled slightly out of balance. Salt residue had built up unevenly on the fan blade, not a motor fault.
A Museum-district office zone stayed warm after a ducted unit relocation. The return damper was left closed, not a new cooling fault.
Newton condo outdoor unit cut out on hot afternoons. Storage on a narrow ledge blocked condenser airflow, so the unit overheated.
A brand-new Tampines unit never reached set temperature. The installer blamed settling-in time, but a skipped vacuum step had left air in the line.
Cashew condo unit shut down every few hours with no error code. A replaced control board did not fix it. The room sensor was the cause.
Europace case in Serangoon: a new wall-mounted unit dripped only in humid weather. An out-of-level bracket was tilting the drain pan; no parts needed.
New multi-split system in Bukit Panjang cooled unevenly. Two control wire pairs swapped at the wire connection point during installation.
A brand-new LG unit in Hougang threw CH38 within weeks. Leak checks found nothing: the installer never finished charging it correctly at setup.
Marina South office stayed warm after fit-out works. A supply grille was boxed in by ceiling works, not a gas or compressor issue.
PRISM+ wall unit case in Serangoon: a nearly-new unit rattled at certain fan speeds. A front panel clip had not fully engaged. Reseating it stopped the rattle.
A new Punggol HDB outdoor unit hummed near the waterway. The fan guard was resonating in open wind, not a fault with the fan motor itself.
A new Tengah HDB outdoor unit rattled between blocks. A leftover shipping packing block was rattling against the fan guard, not a fan fault.
A new aircon unit in Tengah started leaking after its first service. The drain pan had not been reseated properly, not a defective unit.
A Newton condo's high-floor outdoor unit hummed through the wall. Anti-vibration pads had flattened over the years, not a compressor fault.
Serangoon HDB aircon ran noisier and weaker after a chemical servicing. The blower wheel had been reassembled off-centre on its shaft, not a drain issue.
A Novena clinic's outdoor unit buzzed between patient sessions. The compressor mount rubber had hardened from long runtimes, not a motor fault.
Straits View office cassette leaked after servicing. The drain pump cover was misaligned, so water escaped inside the cassette.
Paya Lebar office cassette had weak airflow. Road dust loaded the return filter, so the unit needed cleaning, not gas top-up.
Straits View office aircon showed an error after peak load. A drain overflow switch stopped the unit, not a failed board.
River Valley office aircon tripped after long runs. A stuck drain float switch stopped the unit, not a failed control board.
Bukit Merah HDB room had weak airflow despite a clean filter. The blower wheel behind the cover was packed with dust, not a motor fault.
An older Bukit Merah HDB block leaked after a chemical wash. The drain pump's discharge tube was crimped during reassembly, not a new pump failure.
Marine Parade condo trunking leaked after servicing. Drain insulation was left open in humid trunking, causing condensation drip.
Newton condo trunking dripped after long cooling. A small insulation gap caused pipe sweat, not a cracked drain or gas problem.
Sembawang HDB unit rattled at night. The issue was hardened wall-bracket rubber transferring vibration, not a failing compressor.
Choa Chu Kang HDB room had weak airflow even with a clean filter. A gapped replacement filter let dust bypass onto the coil, not the blower wheel.
Hougang HDB trunking drip came from a cracked drain elbow behind the casing. The indoor unit and gas circuit were not the problem.
Queenstown older HDB unit dripped along the trunking. The access panel's gasket seal had perished with age, not a cracked drain fitting, so a reseal fixed it.
An older Sengkang HDB outdoor unit rattled after storms. Wind-driven rain had loosened the fan guard, not a fault with the fan motor.
Gree ducted office case: one zone stayed warm while the rest cooled. The zone's damper actuator had slipped on its shaft, not failed outright.
Queenstown condo with only one room staying warm while others cooled normally. Fault was in the indoor airflow and coil condition, not a system-wide gas issue.
Straits View office had one warm zone while the rest cooled. The duct damper was stuck near closed, so cold air could not reach that side.
Daikin cassette in Geylang cooling one side poorly. Stuck louver vane and partial coil fouling on that section. Fixed without any parts.
Samsung E1 on one unit in a Sengkang condo system-3. Other two worked fine. control board swap test confirmed indoor board fault. Replaced it.
An Orchard retail outdoor unit buzzed above the street. Traffic and escalator vibration had loosened the mounting bracket.
An original Queenstown HDB block leaked after a chemical wash. Where the drain line meets the pump wasn't pushed fully home, not a new pump fault.
An original Toa Payoh HDB block's unit wouldn't restart after a chemical wash. The isolator switch was left off, not a new fault.
Sungei Kadut industrial office cooled weakly. A past pressure-wash had flattened the condenser fins, so fin combing came before any gas or compressor work.
Seletar outdoor unit buzzed after a windstorm. A prior repair left the fan blade off-center, grazing the guard under storm sway, not a loose screw.
Jurong West HDB outdoor unit buzzing but not starting. Sounded like compressor failure. Capacitor test pinpointed the cause, one swap restored cooling.
Choa Chu Kang Daikin outdoor unit went silent. We tested and cleared the capacitor, starter relay, and wiring before confirming compressor failure.
Outdoor unit rattling loudly at night in Woodlands HDB. Mounting rubber had hardened and bracket bolts loosened. No compressor fault.
Bukit Timah landed outdoor unit rattled after storms. Leaves were caught behind the fan guard, not a failing compressor.
Boon Lay HDB unit had no airflow despite clean filters and blower. Power reached the fan motor, but it would not run. Burnt motor, not blockage.
Sharp 7-0 in Bedok. Outdoor unit hard-starting and tripping on hot afternoons. A capacitor reading low, not a failed compressor, was the cause.
Pasir Ris HDB aircon tripped after rain. A loose terminal inside the isolator was condensing to earth in humid weather, not the compressor or a failed seal.
Bukit Batok HDB outdoor unit tripped on start. Rain and humidity had corroded the ledge isolator contact, corrected before quoting compressor work.
An Outram conservation shophouse outdoor unit rattled on the five-foot way. Street-level traffic had shaken the bracket loose, not a fan fault.
A Pasir Ris HDB outdoor unit rattled in the sea breeze. Salt-laden wind had loosened the fan guard, not a fault with the fan itself.
A Paya Lebar office ducted unit whistled above the workstations at high fan speed. A duct clamp was loose, not a fault with the unit.
Bedok HDB unit stopped cooling two days after routine service. Service valve left partially closed, restricting refrigerant flow. No parts needed.
Kampong Glam shophouse unit smelled musty even after servicing. Mould had colonised the evaporator coil fins behind the filter. Chemical servicing resolved it.
A Pioneer factory cassette leaked after a chemical wash. The drain pump hose was reassembled loose, not a new pump failure.
Tuas port-side office aircon tripped intermittently. Salt-air corrosion damaged the isolator, not the compressor or indoor board.
A pre-war Kallang shophouse aircon threw a random error code. An aged signal wire had chafed through inside old trunking, not a failing control board.
A PRISM+ cassette in a Kallang office answered the remote on and off. A service cover left ajar let dust settle on the sensor window. No parts were replaced.
Mitsubishi E6 in Bishan condo appeared only when the drain pump ran. Communication cable alongside pump cable caused interference.
Wall unit rattling on startup in Boon Keng. Quoted for fan motor replacement. Blower barrel setscrew was loose. Tightened and noise stopped.
Pasir Ris HDB remote stopped controlling the unit. Power light stayed on, but no buttons worked. The receiver failed; the main board was fine.
Yishun reservoir-side flat had a musty smell when the aircon started. A blocked fresh-air path was trapping humidity in the bedroom itself, not coil dirt.
Orchard retail aircon shut down at fixed early-morning and closing hours. A shared corridor exhaust fan being off, not a failing condenser, was the cause.
Geylang shophouse aircon tripped after rain. The isolator's cable entry had never been sealed, letting water track in during storms and trip the breaker.
A River Valley office cassette leaked after being relocated. The drain hose was kinked on the new run, not a new cassette fault.
A Singapore River riverside condo's new unit never cooled properly. The refrigerant line was not fully purged of air before charging in a cramped service void.
A Rochor conservation shophouse outdoor unit rattled in its narrow airwell. The bracket never sat flush against the uneven brickwork, not a fan fault.
Southern Islands outdoor unit rattled near the seafront. A rubber isolation mount had perished from exposure, not compressor or fan motor failure.
A Seletar landed home's drain pump never engaged after a chemical wash. The power lead was left unconnected, not a pump failure.
A Sembawang HDB flat's drain backed up and overflowed after routine servicing. The drain outlet cap was left on, not a new blockage.
Carrier ceiling-suspended unit in a Serangoon shop buzzed for months. Support rod bolts had loosened from years of foot traffic, not a failing fan motor.
Bukit Merah shop aircon dripped near closing time. Long runtime exposed a jammed drain pump float, not a cracked tray or major unit fault.
Rochor shophouse aircon was not cooling well. The condenser was trapped in a narrow airwell, so hot air recirculated around it.
A Robertson Quay office aircon tripped only under heavy load. Wiring had worn through at a tight bend in a cramped condenser recess, not a compressor fault.
Outram shophouse trunking kept dripping. A retrofit drain pipe had backfall, so water sat in the line and leaked back before more drain clearing.
A Southern Islands villa smelled of drains after its first heavy rain post-install. The new drain trap was left dry, letting stagnant air back through.
Paya Lebar unit started short cycling after servicing. The temperature sensor had been knocked out of its clip. Reseating it fixed the cycle.
A Straits View ceiling-concealed office unit hummed through the marina-facing wall. Suspension rods were sitting uneven, not a fault.
River Valley office with one room staying warm while others cooled normally. We confirmed a jammed damper linkage, not low refrigerant or compressor failure.
A Sungei Kadut factory outdoor unit vibrated against its frame. Mounting isolators had perished from heat exposure, not a compressor fault.
An older Tampines HDB outdoor unit tapped the wall on every cycle. The support frame was flexing with age, not a compressor fault.
A Tanglin landed home's drain tray filled with dust after a wash. The return-air grille was left unlatched, not a new drain fault.
All three Mitsubishi Electric units showed E7 in Punggol. Wiring was clean. Outdoor board stopped receiving signals. Replacing it fixed the fault.
A Toshiba multi-split in a Bukit Timah condo lost cooling in one bedroom only. Pressure checks ruled out a leak; that room's own valve had seized.
A Tuas factory unit's drain pump siphoned water back after servicing. The non-return valve was installed backwards, not a pump failure.
Canberra HDB cooling faded across two linked bedrooms after repeated top-ups. A pin-hole leak at a shared distributor joint fed both coils.
Seletar industrial cassette blowing unevenly across vanes. Compacted dust on one side of the blower wheel caused the imbalance. Chemical clean restored it.
Clementi HDB cooling faded after every top-up. We ran a pressure test overnight and traced the leak to the indoor pipe joint. No more repeated top-ups.
Southern Islands villa cassette dripped during humid weather. The drain pump chamber was dirty and could not keep up with the moisture load.
Balestier HDB wall unit dripping onto bedroom floor. Drain tray was choked with algae blocking the outlet. Cleaned tray and flushed drain. Drip stopped.
Ducted unit water overflow in a Tanglin landed home was caused by a stuck drain pump water-level switch, not a failed pump needing full replacement.
Marina East waterfront condo kept losing cooling after repeat gas top-ups. Salt corrosion had degraded the condenser coil, not a refrigerant leak.
Marina East condo aircon smelled musty after idle periods. Drain tray film and moisture were the cause, not gas or a failed indoor unit.
Europace cassette case in Geylang: fading airflow traced to a grease film on the blower wheel, not the compressor. A degreasing clean fixed it, no parts needed.
Buona Vista system-4 tripped when one bedroom unit switched on. One faulty indoor board triggered outdoor protection. Replacing it fixed the system.
An older Woodlands HDB block tripped its breaker after routine servicing. A capacitor cover was left open, not a new electrical fault.
Tuas workshop office had weak airflow. The return filter was loaded with industrial dust, not a gas leak or failed cassette fan.
A Yishun HDB flat leaked near a trunking joint after routine servicing. The drain pipe had been reconnected with too little fall, not a new pipe crack.
Ready to get started?
Tell us what’s going on. Symptoms, setup, photos, anything we should know. We’ll assess and come back with the right next step.