Aircon diagnostic cases
Case notes from completed jobs: the fault pattern, what we tested, what we found, and why we called it that way. Details anonymised, diagnostics intact.
Find a similar case
Search by what you're noticing or what you're comparing: symptom, quote concern, brand, property type, location, or confirmed fault.
Orchard office stayed warm after partition works. The supply path was blocked by the new layout, not a weak aircon system.
Bishan HDB unit blowing cold air but airflow kept weakening each week. We opened the unit and traced it to heavy buildup on the fan barrel and coil.
Teck Ghee HDB unit worked in the morning but cut out every afternoon. Outdoor unit in an alcove with blocked airflow. Thermal protection was tripping.
Changi landed home breaker trips clustered around rainy evenings. Compressor tested normal. Rusty outdoor switch box with failed seals was the cause.
Daikin C4 in Clementi caused mid-cycle shutdowns. The temperature sensor was giving false readings. Sensor replacement cleared the fault.
All four units in a Tampines condo showed LG CH05 at once. Wiring tested fine. Outdoor control board had failed. Replaced the board.
All four rooms in a Sengkang HDB lost cooling simultaneously. The LG outdoor unit had a gas leak at the pipe connections, requiring full system replacement.
Jurong East HDB aircon auto mode kept shutting off every few minutes. The sensor read the room as colder than it was. One part swap restored stable cycling.
Bukit Batok HDB bedroom unit leaked after servicing. The drain joint was slightly loose, not a cracked tray or major repair.
Pasir Ris HDB bedroom was slow to cool near a green edge. Leaf litter blocked the outdoor condenser, so airflow was restored before gas work.
Changi Village HDB wall unit buzzing loudly when running. Mounting plate had loosened from the wall. Resecured bracket stopped the noise. Compressor was fine.
Tengah BTO unit was never cold from day one. System was undercharged by the installer for the pipe run length. Topped up to correct charge and cooling started.
Toa Payoh HDB breaker trips with a hot smell pointed to compressor failure. Heat-damaged isolator connection was the actual cause. No compressor work needed.
Sengkang BTO bedroom leaked at trunking. The drain pipe had sagged along a long route, so the repair was drain support and fall correction.
Rochor shophouse aircon tripped after rain. A rooftop isolator cover gap let moisture in, not compressor or indoor unit failure.
Cafe unit in Outram losing cooling despite quarterly servicing. Thick grease sludge on evaporator. Chemical overhaul restored cooling, no parts needed.
Sembawang Canberra flat had weak airflow after nearby renovation. Fine dust loaded the blower, not a gas leak or failing motor.
MHI unit in Jurong East still faulted after a capacitor swap. The outdoor control board output path had no output to the compressor. Board replacement fixed it.
Hougang HDB ceiling cassette with weak airflow. Corroded motor contacts were reducing fan speed, not a blocked filter. Motor contacts cleaned and restored.
Cassette unit in Choa Chu Kang leaking onto office equipment. Drain line was fully blocked with sludge. Drain pan was intact. Drain flush fixed it.
Marina Bay condo cassette leaking water during heavy tropical rain. Drain line froze briefly from extremely cold aircon output. Cleared and insulated the line.
Joo Koon factory office cassette blew warm air. A gas-flow valve was stuck partly closed, starving the indoor coil. Compressor was fine.
Marina South office cassette rattled after ceiling service. The panel was not seated flat, not a failed fan motor or compressor.
Dhoby Ghaut office cassette rattled at medium fan speed. Loose fan blade retaining clip was the actual cause, not compressor bearing fault.
Raffles Place office cassette started dripping after routine filter cleaning. Drain trap had lost its water seal. No cracked coil, no pump fault.
Intermittent ceiling drip in Marina South office persisted after a drain replacement. A concealed joint gap upstream was the actual source.
Daikin A3 on a ceiling-concealed unit in Bukit Timah. drain pump motor had failed. Water backed up. Replaced the drain pump.
Dhoby Ghaut office ceiling unit dripped after quarterly service. Drain fitting was loose from reassembly. Reconnected and tested. Leak stopped.
LG CH10 in Woodlands HDB. Diagnosed as control board fault. Actual cause was a cracked blower wheel catching on the housing. Wheel replaced, motor fine.
Novena clinic room aircon shut down after long sessions. Dust on the condenser trapped heat, so cleaning and airflow checks came before control-board work.
Outram clinic room cooled weakly after long runtime. A return grille packed with lint was restricting airflow, not a gas issue.
Changi coastal condo bedroom was not cooling well. Salt and fine grit packed the outdoor condenser fins, so airflow was restored before any gas work.
Katong condo aircon blowing but not cold. Previous company said gas leaked and coil needed replacing. Chemical servicing of caked evaporator restored cooling.
Sentosa unit kept losing gas after top-ups. Salt-air corrosion had damaged the outdoor pipe fitting. Resealing stopped the repeat loss.
Novena condo concealed unit dripping from two points. drain pump had seized from scale buildup. Pump replaced, dripping stopped.
River Valley condo bedroom had musty aircon smell. A wet coil and blocked drain pan held moisture inside the unit after rainy days.
Paya Lebar condo aircon started dripping after renovation. Fine dust had collected in the drain path, so the choke was cleared before bigger work.
Serangoon HDB cooling dropped and water dripped after a chemical servicing. Drain pan cover and blower wheel both left out of position during reassembly.
Upper Thomson landed home wall unit dripping intermittently on humid days. Drain pipe had sagged over the years. Resupported pipe to restore gradient.
Orchard office ducted system gradually lost airflow. Staff feared duct deterioration. Return air filter in the ceiling void had not been cleaned in years.
Hougang HDB aircon showed an error after renovation works nearby. The fault was a nicked communication wire in trunking, not a failed board.
Panasonic H11 appeared after a Bedok thunderstorm. A loose indoor connection caused the fault. Reseating it cleared the error.
Samsung error appeared after servicing in Marina East. The board was locked in fault state, not dead. Reset and checks restored cooling.
Tengah HDB error code appeared right after renovation. Signal wire had been nicked and rejoined with wires swapped. Correcting the sequence cleared the error.
LG CH05 in Ang Mo Kio kept returning. The outdoor wire connector was corroded, not the control board. Cleaned and refitted the connection.
Daikin A3 kept returning after drain clearing in Toa Payoh. A sag in the drain line inside the false ceiling trapped sludge. Rerouted the line.
Mitsubishi E6 in Yishun traced to a corroded wire splice in a ceiling void junction box. Weatherproof re-splice resolved it.
York E1 in Jurong East kept returning after resets. Corroded outdoor wire connections were cleaned and refitted. No board replacement needed.
Samsung E1 after renovation in Jurong West HDB. Cable insulation nicked during drilling. Exposed wire shorted against trunking. Fixed with no parts replaced.
Pioneer factory office cassette dripped again after cleaning. Dust sludge blocked the drain line, not a cracked pan or failed pump.
On-and-off aircon trips in a Sungei Kadut factory office traced to a corroded isolator switch. Wiring was intact. No cable replacement needed.
Cassette unit in Tuas factory losing cooling gradually. Condenser coil coated in industrial dust. Chemical servicing restored full capacity.
Pioneer factory office became warm again. Oil dust coated the condenser coil, blocking heat release, not pointing to compressor failure.
Sungei Kadut factory office cassette had weak airflow. Sawdust coated the blower wheel, not a motor or gas fault from workshop dust.
Telok Blangah HDB aircon not cold at five years old. Condenser coil was crusted with salt residue from sea breeze. Chemical servicing restored cooling.
An LG outdoor unit on a high-floor Punggol condo corroded in just 4 years due to direct wind and rain exposure, causing a gas leak far earlier than expected.
Museum area gallery office felt warm after a display partition was added. The return air path was blocked, not a gas or compressor fault.
Tanglin landed room became warm in the afternoon. Seed pods blocked the garden-facing condenser, so heat could not escape properly.
Marine Parade condo kept losing cooling after gas top-ups. The leak was at a corroded outdoor connection exposed to coastal air.
Newton condo unit topped up twice in one year but kept losing cooling. A pinhole leak in the concealed copper pipe behind the wall was the cause.
A welded gas leak on an LG outdoor unit in Woodlands failed again. Cooling returned briefly before a new leak appeared on the same corroded pipe section.
Yishun HDB with repeated cooling loss after multiple top-ups. Focused leak checks on the service port traced the hidden source to a faulty service valve core.
Macpherson HDB case: regular servicing missed deep evaporator coil fouling. Chemical servicing reopened the coil and restored cooling.
Downtown Core office became warm by afternoon. The condenser was recycling hot air inside a service recess, so airflow planning mattered more than gas.
Sharp 6-0 in Woodlands HDB. Fan motor grinding on a 13-year-old unit. Bearings worn out. Owner chose replacement over repair given the age.
Tampines HDB bedroom aircon dripped after years of use. A drain choke behind the trunking caused backup, not a cracked tray or gas problem.
Ang Mo Kio condo with three ceiling cassettes struggling to cool and high monthly bills. Outdoor unit was too small for the indoor capacity.
Ang Mo Kio Daikin with ice on pipe. Assumed low gas. Airflow pattern and coil condition pointed to buildup restricting the evaporator, not a refrigerant issue.
Punggol HDB indoor unit blew air but the outdoor side stayed silent. A starter relay fault in the start path was the cause. Not a compressor failure.
Dairy Farm landed home aircon gradually lost cooling. Told the compressor was failing. Outdoor condenser was choked with leaf litter from nearby trees.
Bukit Timah landed master bedroom became weak after pipe work. A loose flare joint was found before replacing the unit or topping up gas blindly.
Serangoon landed outdoor unit rattled after windy weather. Dried leaves caught in the fan guard, not a compressor fault or motor failure.
Seletar landed aircon dripped after rain. Leaf sludge in the drain tray caused overflow, not a cracked tray or failed indoor unit.
LG CH35 case in Bedok: leak tracing found corroded outdoor pipe connections. After sealing and recharge, cooling returned without parts replacement.
LG system 3 in Serangoon had a gas leak along a long pipe run. pressure hold testing narrowed it to the outdoor unit connections, not the concealed piping.
Cooling kept dropping after gas top-ups in Bukit Batok. We traced the leak to corroded LG outdoor unit connections and presented three repair options.
Clementi HDB wall unit rattled loudly during startup then went quiet. Mounting was solid. Worn motor bearings let the rotor shift during spin-up.
Tanglin low-rise condo bedroom aircon rattled at night. A loose trunking cover vibrated, not compressor or indoor fan failure.
Newton condo outdoor unit cut out on hot afternoons. Storage on a narrow ledge blocked condenser airflow, so the unit overheated.
Brand-new unit in Tampines never reached set temperature. Installer said it needed time to settle in. The gas charge was low from day one.
Cashew condo unit shut down every few hours with no error code. A replaced control board did not fix it. The room sensor was the cause.
New multi-split system in Bukit Panjang cooled unevenly. Two control wire pairs swapped at the wire connection point during installation.
Marina South office stayed warm after fit-out works. A supply grille was boxed in by ceiling works, not a gas or compressor issue.
A new aircon unit in Tengah started leaking after its first service. The drain pan had not been reseated properly, not a defective unit.
Straits View office cassette leaked after servicing. The drain pump cover was misaligned, so water escaped inside the cassette.
Paya Lebar office cassette had weak airflow. Road dust loaded the return filter, so the unit needed cleaning, not gas top-up.
Straits View office aircon showed an error after peak load. A drain overflow switch stopped the unit, not a failed board.
River Valley office aircon tripped after long runs. A stuck drain float switch stopped the unit, not a failed control board.
Bukit Merah HDB room had weak airflow despite a clean filter. The blower wheel behind the cover was packed with dust, not a motor fault.
Marine Parade condo trunking leaked after servicing. Drain insulation was left open in humid trunking, causing condensation drip.
Newton condo trunking dripped after long cooling. A small insulation gap caused pipe sweat, not a cracked drain or gas problem.
Sembawang HDB unit rattled at night. The issue was hardened wall-bracket rubber transferring vibration, not a failing compressor.
Choa Chu Kang HDB room had weak airflow even with a clean filter. The blower wheel behind the cover was packed, so cleaning solved it without parts.
Queenstown older HDB unit dripped from trunking. The original drain coupling had cracked, so the fix was drainage repair, not a new indoor unit.
Hougang HDB trunking drip came from a cracked drain elbow behind the casing. The indoor unit and gas circuit were not the problem.
Queenstown condo with only one room staying warm while others cooled normally. Fault was in the indoor airflow and coil condition, not a system-wide gas issue.
Straits View office had one warm zone while the rest cooled. The duct damper was stuck near closed, so cold air could not reach that side.
Daikin cassette in Geylang cooling one side poorly. Stuck louver vane and partial coil fouling on that section. Fixed without any parts.
Samsung E1 on one unit in a Sengkang condo system-3. Other two worked fine. control board swap test confirmed indoor board fault. Replaced it.
Sungei Kadut industrial office cooled weakly. Workshop dust packed the outdoor condenser, so airflow was restored before gas or compressor work.
Seletar outdoor unit buzzed after a windstorm. A fan guard screw loosened and vibrated, not the compressor or motor during startup.
Jurong West HDB outdoor unit buzzing but not starting. Sounded like compressor failure. Capacitor test pinpointed the cause, one swap restored cooling.
Choa Chu Kang Daikin outdoor unit went silent. We tested and cleared the capacitor, starter relay, and wiring before confirming compressor failure.
Outdoor unit rattling loudly at night in Woodlands HDB. Mounting rubber had hardened and bracket bolts loosened. No compressor fault.
Sharp 7-0 in Bedok. Outdoor unit not starting. Diagnosed as compressor failure. We found a failed capacitor instead. A forty-dollar fix.
Bukit Timah landed outdoor unit rattled after storms. Leaves were caught behind the fan guard, not a failing compressor.
Boon Lay HDB unit had no airflow despite clean filters and blower. Power reached the fan motor, but it would not run. Burnt motor, not blockage.
Pasir Ris HDB aircon tripped after rain. The exposed outdoor isolator gasket had failed, not the compressor or indoor unit.
Bukit Batok HDB outdoor unit tripped when starting. A loose isolator contact on the ledge was corrected before quoting compressor work.
Bedok HDB unit stopped cooling two days after routine service. Service valve left partially closed, restricting refrigerant flow. No parts needed.
Kampong Glam shophouse unit smelled musty even after servicing. Mould had colonised the evaporator coil fins behind the filter. Chemical servicing resolved it.
Tuas port-side office aircon tripped intermittently. Salt-air corrosion damaged the isolator, not the compressor or indoor board.
Mitsubishi E6 in Bishan condo appeared only when the drain pump ran. Communication cable alongside pump cable caused interference.
Wall unit rattling on startup in Boon Keng. Quoted for fan motor replacement. Blower barrel setscrew was loose. Tightened and noise stopped.
Pasir Ris HDB remote stopped controlling the unit. Power light stayed on, but no buttons worked. The receiver failed; the main board was fine.
Yishun reservoir-side flat had a musty smell when the aircon started. Moisture, blower dirt, and coil film were the cause, not a gas issue.
Orchard retail aircon shut down after long runtime. The condenser was starved for airflow in a service corridor, not failing internally.
Geylang shophouse aircon tripped after rain. A cracked outdoor isolator cover was letting water in, so the power path was fixed before blaming the unit.
Southern Islands outdoor unit rattled near the seafront. Bracket rubber had failed from exposure, not compressor or fan motor failure.
Bukit Merah shop aircon dripped near closing time. Long runtime exposed a jammed drain pump float, not a cracked tray or major unit fault.
Rochor shophouse aircon was not cooling well. The condenser was trapped in a narrow airwell, so hot air recirculated around it.
Outram shophouse trunking kept dripping. A retrofit drain pipe had backfall, so water sat in the line and leaked back before more drain clearing.
Paya Lebar unit started short cycling after servicing. The temperature sensor had been knocked out of its clip. Reseating it fixed the cycle.
River Valley office with one room staying warm while others cooled normally. We confirmed a jammed damper linkage, not low refrigerant or compressor failure.
All three Starmex units showed E7 at once in Punggol. Wiring was clean. Outdoor control board had stopped receiving signals. Board replacement resolved it.
Canberra HDB cooling faded across two linked bedrooms after repeated top-ups. Leak tracing confirmed a pin-hole leak at an indoor coil return bend.
Seletar industrial cassette blowing unevenly across vanes. Compacted dust on one side of the blower wheel caused the imbalance. Chemical clean restored it.
Clementi HDB cooling faded after every top-up. We ran a pressure test overnight and traced the leak to the indoor pipe joint. No more repeated top-ups.
Southern Islands villa cassette dripped during humid weather. The drain pump chamber was dirty and could not keep up with the moisture load.
Balestier HDB wall unit dripping onto bedroom floor. Drain tray was choked with algae blocking the outlet. Cleaned tray and flushed drain. Drip stopped.
Ducted unit water overflow in a Tanglin landed home was caused by a stuck drain pump water-level switch, not a failed pump needing full replacement.
Marina East waterfront condo kept losing cooling. The leak was at a salt-corroded outdoor flare joint, not inside the wall.
Marina East condo aircon smelled musty after idle periods. Drain tray film and moisture were the cause, not gas or a failed indoor unit.
Buona Vista system-4 tripped when one bedroom unit switched on. One faulty indoor board triggered outdoor protection. Replacing it fixed the system.
Tuas workshop office had weak airflow. The return filter was loaded with industrial dust, not a gas leak or failed cassette fan.