Real jobs we've worked on: the fault pattern, what we tested, what we found, and why we called it that way. Details anonymized, diagnostics intact.

Find A Similar Case

Search by what you're noticing or what you're comparing: symptom, quote concern, brand, property type, location, or confirmed fault.

Filter by case type
Air Felt Cold But Barely Any Wind: Dust-caked Blower And Coil

Bishan HDB unit blowing cold air but airflow kept weakening each week. We opened the unit and traced it to heavy buildup on the fan barrel and coil.

Aircon Cuts Out Every Afternoon: Trapped Heat In Outdoor Alcove

Teck Ghee HDB unit worked in the morning but cut out every afternoon. Outdoor unit in an alcove with blocked airflow. Thermal protection was tripping.

Aircon Only Trips When It Rains: Water In The Outdoor Switch Box

Changi landed home breaker trips clustered around rainy evenings. Compressor tested normal. Rusty outdoor switch box with failed seals was the cause.

Aircon Shutting Off Mid-cycle: Temperature Sensor Gone Bad

Daikin C4 caused mid-cycle shutdowns in Clementi. Thermistor had drifted with age. Not wiring or PCB. Sensor replaced in 20 minutes.

All Four Rooms Down At Once: Outdoor Board Died

All four units in a Tampines condo showed LG CH05 at once. Wiring tested fine. Outdoor PCB had failed. Replaced the board.

All Four Rooms Went Warm: Single Leak At The Outdoor Unit

All four rooms in a Sengkang HDB lost cooling simultaneously. The LG outdoor unit had a gas leak at the pipe connections, requiring full system replacement.

Auto Mode Kept Shutting Off: Sensor Thought The Room Was Already Cold

Jurong East HDB aircon auto mode kept shutting off every few minutes. Sensor was reading 19 degrees in a 26-degree room. One part swap restored stable cycling.

Bedroom Unit Buzzing At Night: Loose Wall Bracket, Not Compressor

Changi Village HDB wall unit buzzing loudly when running. Mounting plate had loosened from the wall. Resecured bracket stopped the noise. Compressor was fine.

Brand-new BTO Unit Never Felt Cold: Undercharged From Install

Tengah BTO unit was never cold from day one. System was undercharged by the installer for the pipe run length. Topped up to correct charge and cooling started.

Breaker Tripping With A Hot Smell: Damaged Isolator, Not Compressor

Toa Payoh HDB breaker trips with a hot smell pointed to compressor failure. Heat-damaged isolator connection was the actual cause. No compressor work needed.

Cafe Unit Barely Cooling: Years Of Grease Sludge On The Evaporator Coil

Cafe unit in Outram losing cooling despite quarterly servicing. Thick grease sludge on evaporator. Chemical overhaul restored cooling, no parts needed.

Capacitor Swap Didn't Fix It: Outdoor Board Was The Actual Fault

MHI unit in Jurong East still faulted after a capacitor swap. The outdoor PCB driver circuit had no output to the compressor. Board replacement fixed it.

Cassette Airflow Getting Weaker: Corrosion Slowing The Fan Motor

Hougang HDB ceiling cassette with weak airflow. Corroded motor contacts were reducing fan speed, not a blocked filter. Motor contacts cleaned and restored.

Cassette Dripping Onto Desks: Drain Sludge, Not A Cracked Pan

Cassette unit in Choa Chu Kang leaking onto office equipment. Drain line was fully blocked with sludge. Drain pan was intact. Drain flush fixed it.

Cassette Leaking After Heavy Rain: Drain Outlet Froze Briefly

Marina Bay condo cassette leaking water during heavy tropical rain. Drain line froze briefly from extremely cold aircon output. Cleared and insulated the line.

Cassette Not Cooling: Stuck Expansion Valve, Not Compressor

Joo Koon factory office cassette blowing warm air. Electronic expansion valve was stuck partially closed, restricting refrigerant flow. Compressor was fine.

Cassette Rattling At Certain Speeds: Loose Fan Blade Clip

Dhoby Ghaut office cassette rattled at medium fan speed. Loose fan blade retaining clip was the actual cause, not compressor bearing fault.

Cassette Started Dripping After Routine Cleaning: Drain Trap Dried Out

Raffles Place office cassette started dripping after routine filter cleaning. Drain trap had lost its water seal. No cracked coil, no pump fault.

Ceiling Drip Only On Humid Afternoons: Hidden Gap In The Drain Pipe

Intermittent ceiling drip in Marina South office persisted after a drain replacement. A concealed joint gap upstream was the actual source.

Ceiling Drip With Error Code: Drain Pump Motor Failed

Daikin A3 on a ceiling-concealed unit in Bukit Timah. Condensate pump motor had failed. Water backed up. Replaced the drain pump.

Ceiling Unit Dripping After Quarterly Service: Drain Left Loose

Dhoby Ghaut office ceiling unit dripped after quarterly service. Drain fitting was loose from reassembly. Reconnected and tested. Leak stopped.

Clicking Sound Then Shutdown: Cracked Blower Catching On Housing

LG CH10 in Woodlands HDB. Diagnosed as PCB fault. Actual cause was a cracked blower wheel catching on the housing. Wheel replaced, motor fine.

Coastal Condo Not Cold: Evaporator Grime, Not A Gas Leak

Katong condo aircon blowing but not cold. Previous company said gas leaked and coil needed replacing. Chemical servicing of caked evaporator restored cooling.

Coastal Unit Losing Gas Again: Salt Ate Through The Pipe Fitting

Sentosa condo aircon topped up twice in one year. Salt-air corrosion had thinned the flare nut at the outdoor pipe joint. Replaced the fitting. Gas holds now.

Concealed Unit Dripping From The Panel: Condensate Pump Seized

Novena condo concealed unit dripping from two points. Condensate pump had seized from scale buildup. Pump replaced, dripping stopped.

Cooling And Dripping Both Worse After Chemical Servicing: Bad Reassembly

Serangoon HDB cooling dropped and water dripped after a chemical servicing. Drain pan cover and blower wheel both left out of position during reassembly.

Drips Only On Humid Days: Drain Pipe Sagged And Water Pools Inside

Upper Thomson landed home wall unit dripping intermittently on humid days. Drain pipe had sagged over the years. Resupported pipe to restore gradient.

Ducted System Getting Weaker For A Year: Ceiling Filter Never Cleaned

Orchard office ducted system gradually lost airflow. Staff feared duct deterioration. Return air filter in the ceiling void had not been cleaned in years.

Error Appeared After Thunderstorm: Connection Shaken Loose

Panasonic H11 error appeared after a power trip in Bedok. Traced to a loose terminal at the indoor PCB connector block. Re-seated connections cleared the fault.

Error Appeared Right After Servicing: Board Locked, Not Dead

Marina East condo error code appeared right after servicing. PCB was locked in fault state from abrupt power cut. Manufacturer reset sequence cleared it.

Error Code The Day Renovation Finished: Signal Wire Nicked

Tengah HDB error code appeared right after renovation. Signal wire had been nicked and rejoined with wires swapped. Correcting the sequence cleared the error.

Error Keeps Coming Back After Every Reset: Corroded Wire Connection

LG CH05 appeared intermittently in Ang Mo Kio HDB. Quoted outdoor PCB replacement. Actual fault was a corroded terminal. Cleaned and re-crimped.

Error Keeps Returning After Drain Clearing: Sagging Pipe Trapping Sludge

Daikin A3 kept returning after drain clearing in Toa Payoh. A sag in the drain line inside the false ceiling trapped sludge. Rerouted the line.

Error Only After Running For Hours: Corroded Wire Joint In The Ceiling

Mitsubishi E6 in Yishun traced to a corroded wire splice in a ceiling void junction box. Weatherproof re-splice resolved it.

Error Returns After Every Reset: Corroded Outdoor Connections

York E1 in Jurong East HDB. Previous contractor could not diagnose it. Corroded outdoor terminals. Cleaned and re-crimped to clear the fault.

Error Started After Neighbour's Renovation: Cable Insulation Nicked

Samsung E1 after renovation in Jurong West HDB. Cable insulation nicked during drilling. Exposed wire shorted against trunking. Fixed with no parts replaced.

Factory Office Aircon Keeps Tripping: Corroded Isolator Switch

On-and-off aircon trips in a Sungei Kadut factory office traced to a corroded isolator switch. Wiring was intact. No cable replacement needed.

Factory Office Barely Cooling: Condenser Coated In Industrial Dust

Cassette unit in Tuas factory losing cooling gradually. Condenser coil coated in industrial dust. Chemical servicing restored full capacity.

Five-year-old Unit Losing Cooling: Salt Crust On The Condenser

Telok Blangah HDB aircon not cold at five years old. Condenser coil was crusted with salt residue from sea breeze. Chemical servicing restored cooling.

Four-year-old LG Losing Gas: High-floor Wind Corroding The Pipes

An LG outdoor unit on a high-floor Punggol condo corroded in just 4 years due to direct wind and rain exposure, causing a gas leak far earlier than expected.

Gas Keeps Running Out: Pinhole Leak In Pipe Behind The Wall

Newton condo unit topped up twice in one year but kept losing cooling. A pinhole leak in the concealed copper pipe behind the wall was the cause.

Gas Leak Returned After Weld Repair: Corroded Section Too Far Gone

A welded gas leak on an LG outdoor unit in Woodlands failed again. Cooling returned briefly before a new leak appeared on the same corroded pipe section.

Gas Topped Up Three Times: Hidden Leak At The Service Valve

Yishun HDB with repeated cooling loss after multiple top-ups. Focused leak checks on the service port traced the hidden source to a faulty Schrader valve core.

Getting Less Cold Despite Regular Servicing: Deep Coil Buildup

Macpherson HDB case: regular servicing missed deep evaporator coil fouling. Chemical servicing reopened the coil and restored cooling.

Grinding Noise Then Shutdown: Fan Motor Bearings Worn Out

Sharp 6-0 in Woodlands HDB. Fan motor grinding on a 13-year-old unit. Bearings worn out. Owner chose replacement over repair given the age.

High Electricity Bill And Weak Cooling: Outdoor Unit Undersized

Ang Mo Kio condo with three ceiling cassettes struggling to cool and high monthly bills. Outdoor unit was too small for the indoor capacity.

Ice Forming On The Copper Pipe: Airflow Blockage, Not Low Gas

Ang Mo Kio Daikin with ice on pipe. Assumed low gas. Airflow pattern and coil condition pointed to buildup restricting the evaporator, not a refrigerant issue.

Indoor Fan Blowing But Outdoor Silent: Faulty Starter Relay

Punggol HDB indoor unit blew air but the outdoor side stayed silent. A contactor relay fault in the start path was the cause. Not a compressor failure.

Landed Home Cooling Fading: Condenser Choked With Leaf Litter

Dairy Farm landed home aircon gradually lost cooling. Told the compressor was failing. Outdoor condenser was choked with leaf litter from nearby trees.

LG CH35 Error In Bedok: Gas Leak At The Outdoor Connections

LG CH35 case in Bedok: leak tracing found corroded outdoor pipe connections. After sealing and recharge, cooling returned without parts replacement.

LG System-3 Losing Gas: Leak At Outdoor Unit, Not Inside Walls

LG system 3 in Serangoon had a gas leak along a long pipe run. Nitrogen testing narrowed it to the outdoor unit connections, not the concealed piping.

LG Unit Topped Up Twice: Corroded Outdoor Pipe Connections

Cooling kept dropping after gas top-ups in Bukit Batok. We traced the leak to corroded LG outdoor unit connections and presented three repair options.

Loud Rattle On Startup That Fades: Motor Bearings Worn Out

Clementi HDB wall unit rattled loudly during startup then went quiet. Mounting was solid. Worn motor bearings let the rotor shift during spin-up.

New Aircon Never Cooled Properly: Installer Undercharged The Gas

Brand-new unit in Tampines never reached set temperature. Installer said it needed time to settle in. Refrigerant was 35% below spec from day one.

New Board Didn't Fix It: Temperature Sensor Was The Problem All Along

Cashew condo unit shut down every few hours with no error code. PCB had already been replaced by another company. A drifted room thermistor was the cause.

New Install Acting Strange: Two Wires Swapped During Installation

New multi-split system in Bukit Panjang cooled unevenly. Two control wire pairs swapped at the terminal block during installation.

New Unit Dripping After First Service: Drain Pan Not Reseated

A new aircon unit in Tengah started leaking after its first service. The drain pan had not been reseated properly, not a defective unit.

One Room Warm, Other Rooms Fine: Coil Buildup, Not Low Gas

Queenstown condo with only one room staying warm while others cooled normally. Fault was in the indoor airflow and coil condition, not a system-wide gas issue.

One Side Of Office Warm, Other Side Fine: Zone Damper Stuck

Straits View office ducted system with one zone getting warm air while others stayed cold. Motorised zone damper had jammed near-closed. Freed the actuator.

One Side Of The Room Always Warmer: Stuck Louver Vane

Daikin cassette in Geylang cooling one side poorly. Stuck louver vane and partial coil fouling on that section. Fixed without any parts.

One Unit Showing Error, Others Fine: Indoor Board Dead

Samsung E1 on one unit in a Sengkang condo system-3. Other two worked fine. PCB swap test confirmed indoor board fault. Replaced it.

Outdoor Unit Buzzing And Clicking: Capacitor, Not Compressor

Jurong West HDB outdoor unit buzzing but not starting. Sounded like compressor failure. Capacitor test pinpointed the cause, one swap restored cooling.

Outdoor Unit Completely Dead: Compressor Confirmed Failed

Choa Chu Kang Daikin outdoor unit went silent. We tested and cleared the capacitor, contactor, and relay before confirming an open compressor winding failure.

Outdoor Unit Getting Louder At Night: Mounting Rubber Hardened

Outdoor unit rattling loudly at night in Woodlands HDB. Mounting rubber had hardened and bracket bolts loosened. No compressor fault.

Outdoor Unit Not Starting: Capacitor Failed, Not Compressor

Sharp 7-0 in Bedok. Outdoor unit not starting. Diagnosed as compressor failure. We found a failed capacitor instead. A forty-dollar fix.

Outdoor Unit Running But No Air Inside: Fan Motor Burnt Out

Boon Lay HDB unit had no airflow despite clean filters and blower. Motor winding check showed open circuit. Burnt motor, not blockage.

Perfectly Fine Before Service, Warm After: Valve Left Half-closed

Bedok HDB unit stopped cooling two days after routine service. Service valve left partially closed, restricting refrigerant flow. No parts needed.

Persistent Musty Smell: Mould Deep Inside The Cooling Coil

Kampong Glam shophouse unit smelled musty even after servicing. Mould had colonised the evaporator coil fins behind the filter. Chemical servicing resolved it.

Random Error Code With No Pattern: Drain Pump Cable Causing Interference

Mitsubishi E6 in Bishan condo appeared only when the drain pump ran. Communication cable alongside pump cable caused interference.

Rattling Every Startup: Blower Wheel Loose On The Shaft

Wall unit rattling on startup in Boon Keng. Quoted for fan motor replacement. Blower barrel setscrew was loose. Tightened and noise stopped.

Remote Stopped Working Completely: Receiver Broken, Not The Board

Pasir Ris HDB remote stopped controlling the unit. Power light was on but no buttons responded. The IR receiver had failed, the main indoor PCB was fine.

Started Short Cycling After Service: Sensor Knocked Out Of Clip

Paya Lebar HDB unit started short cycling right after servicing. Previous company said sensor failure. Thermistor was displaced from its clip during cleaning.

Study Always Warmer Than The Rest: Airflow Damper Jammed Shut

River Valley office with one room staying warm while others cooled normally. We confirmed a jammed damper linkage, not low refrigerant or compressor failure.

Three Zones Failed Overnight: One Relay On The Outdoor Board

All three Starmex units showed E7 at once in Punggol. Wiring was clean. Outdoor PCB had stopped receiving signals. Board replacement resolved it.

Two Bedrooms Losing Cooling Together: Pinhole Coil Leak

Canberra HDB cooling faded across two linked bedrooms after repeated top-ups. Leak tracing confirmed a pin-hole leak at an indoor coil return bend.

Two Sides Blowing Strong, Two Sides Weak: Blower Caked On One Side

Seletar industrial cassette blowing unevenly across vanes. Compacted dust on one side of the blower wheel caused the imbalance. Chemical clean restored it.

Two Top-ups In Four Months: Slow Leak At The Indoor Pipe Joint

Clementi HDB cooling faded after every top-up. We ran a pressure test overnight and traced the leak to the indoor flare joint. No more repeated top-ups.

Water Dripping Onto Parquet Floor: Algae Blocking The Drain Tray

Balestier HDB wall unit dripping onto bedroom floor. Drain tray was choked with algae blocking the outlet. Cleaned tray and flushed drain. Drip stopped.

Water Marks On Ceiling: Drain Pump Switch Stuck By Sludge

Ducted unit water overflow in a Tanglin landed home was caused by a stuck condensate pump float switch, not a failed pump needing full replacement.

Whole System Shuts Down When One Room Turns On: Faulty Indoor Board

Buona Vista condo system-4 tripped whenever one bedroom unit was switched on. A faulty indoor PCB in that unit was triggering the outdoor protection circuit.

Ready to Get Started?

Tell us what’s going on. Symptoms, setup, photos, anything we should know. We’ll assess and come back with the right next step.