Aircon diagnostic cases
Diagnostic case notes: the fault pattern, what we tested, what we found, and why we called it that way. Details anonymised, diagnostics intact.
Find a similar case
Search by what you're noticing or what you're comparing: symptom, quote concern, brand, property type, location, or confirmed fault.
Changi landed home breaker trips clustered around rainy evenings. Compressor tested normal. A rusty outdoor switch box was the cause.
Daikin C4 in Clementi caused mid-cycle shutdowns. The temperature sensor was giving false readings. Sensor replacement cleared the fault.
A shophouse kitchen unit in Outram lost airflow faster after every clean. Grease had cured through the fin depth, so an overhaul was right.
All four units in a Tampines condo showed LG CH05 at once. Wiring tested fine. Outdoor control board had failed. Replaced the board.
All four rooms in a Sengkang flat lost cooling at once. The LG outdoor unit leaked at the pipe connections, needing full replacement.
Jurong East aircon auto mode kept shutting off every few minutes. The sensor read the room as colder than it was. One swap fixed it.
Bukit Batok HDB bedroom unit leaked after servicing. The drain joint was slightly loose, not a cracked tray or major repair.
Pasir Ris HDB bedroom was slow to cool near a green edge. A privacy screen too close to the outdoor unit trapped its exhaust. Clearance fixed it.
Changi Village HDB wall unit buzzing loudly when running. Mounting plate had loosened from the wall. Resecured bracket stopped the noise.
A Novena clinic watched its bill climb while rooms warmed. Servicing ran on an annual calendar, but the units work far past that.
A Jurong East outdoor unit rocked on startup. A corroded, seized mounting bolt let one corner shift, not a fault inside the compressor.
An older Woodlands HDB block tripped its breaker after routine servicing. A capacitor cover was left open, not a new electrical fault.
A Tengah BTO unit was never cold from day one. The system was undercharged for the pipe run length, so topping up started the cooling.
Toa Payoh HDB breaker trips with a hot smell pointed to compressor failure. Heat-damaged isolator connection was the actual cause.
A Sengkang BTO bedroom leaked at the trunking. A renovation-era shelf had crushed the drain pipe's bore, so the fix relieved the pinch.
A new Marina East café leaked after installation. The drain line was pitched the wrong way on the new run, not a defective unit.
A cafe unit in Outram lost cooling despite quarterly servicing. Thick grease sludge on the evaporator. An overhaul restored cooling.
Sembawang Canberra flat had weak airflow after nearby renovation. Fine dust loaded the blower, not a gas leak or failing motor.
MHI unit in Jurong East still faulted after a capacitor swap. The outdoor control board output path had no output to the compressor.
A Hougang ceiling cassette had weak airflow. Corroded motor contacts were reducing fan speed, not a blocked filter. Cleaning restored it.
Raffles Place office cassette started dripping after routine cleaning. Debris in the drain line caused a partial blockage.
Cassette unit in Choa Chu Kang leaking onto office equipment. Drain line was fully blocked with sludge. Drain pan was intact.
Marina Bay condo cassette leaking during heavy tropical rain. The condensate pump float switch was slow to trigger at peak load.
Joo Koon factory office cassette blew warm air. A gas-flow valve was stuck partly closed, starving the indoor coil. Compressor was fine.
Marina South office cassette rattled after ceiling service. The panel was not seated flat, not a failed fan motor or compressor.
Dhoby Ghaut office cassette rattled at medium fan speed. Loose fan blade retaining clip was the actual cause, not compressor bearing fault.
Intermittent ceiling drip in Marina South office persisted after a drain replacement. A concealed joint gap upstream was the actual source.
Daikin A3 on a ceiling-concealed unit in Bukit Timah. Drain pump motor had failed. Water backed up. Replaced the drain pump.
Dhoby Ghaut office ceiling unit dripped after quarterly service. Drain fitting was loose from reassembly. Reconnected and tested. Leak stopped.
Fujitsu ceiling-concealed case in Bukit Timah: coil fouling behind the filter, not the compressor, explained a year of fading cooling.
A Hitachi ceiling unit in a Serangoon condo leaked only after power outages. The pump's own safety cut-off needed a reset, not a swap.
LG CH38 hit one Yishun condo bedroom on a multi-split while other rooms stayed cold. The leak was a pinhole in that room's own indoor coil.
LG CH10 in Woodlands HDB looked like a control board fault. Actual cause was a cracked blower wheel catching on the housing.
A Novena clinic's outdoor unit buzzed between patient sessions. The compressor mount rubber had hardened from long runtimes, not a motor fault.
Recurring clinic faults were being treated as one system problem. An asset map separated one replacement, one repair, and one retained unit.
A Novena clinic room shut down after long sessions. Dust on the condenser trapped heat, so cleaning came before any control-board work.
Outram clinic room cooled weakly after long runtime. A return grille packed with lint was restricting airflow, not a gas issue.
A Changi coastal condo bedroom was not cooling well. Salt and grit packed the condenser fins, so airflow was restored before any gas work.
Katong condo aircon blowing but not cold. A gas leak and a new coil looked likely. Chemical servicing of the caked evaporator restored cooling.
Sentosa unit kept losing gas after top-ups. Salt-air corrosion had damaged the outdoor pipe fitting. Resealing stopped the repeat loss.
A Bishan unit blew cold air but airflow kept weakening each week. We opened it and traced it to heavy buildup on the fan barrel and coil.
A Bukit Merah flat was quoted a compressor swap on a fourteen-year-old system. Testing confirmed it, and the sums pointed at replacement.
Novena condo concealed unit dripping from two points. Drain pump had seized from scale buildup. Pump replaced, dripping stopped.
River Valley condo bedroom had musty aircon smell. A wet coil and blocked drain pan held moisture inside the unit after rainy days.
A Bishan condo cassette blew weak air right after a chemical wash. A filter clip was never reseated, letting the filter sag into the path.
A Paya Lebar condo aircon started dripping after renovation. Fine dust had collected in the drain path, so the choke was cleared first.
A Clementi condo quote hung the outdoor unit on the balcony wall. Estate rules did not allow it, and the approved ledge added pipe run.
Marine Parade condo trunking leaked after servicing. Drain insulation was left open in humid trunking, causing condensation drip.
A Newton condo's high-floor outdoor unit hummed through the wall. Anti-vibration pads had flattened over the years, not a compressor fault.
A Marine Parade condo outdoor unit wobbled slightly out of balance. Salt residue had built up unevenly on the fan blade, not a motor fault.
A new Clementi condo unit ran warm after installation. An energy-saving mode left on from setup capped the compressor, not a defect.
A riverside Singapore River condo's new unit never cooled properly. The refrigerant line was not fully purged of air before charging.
A Kallang River condo bedroom stayed warm despite a working aircon. Site hoarding was blocking the outdoor unit's air path, not a sizing issue.
Marine Parade condo cooling cut out under load after gas top-ups. The fault was a salt-corroded outdoor terminal, not the refrigerant joint.
A York multi-split in a landed Hougang home lost cooling evenly over a year. A full check confirmed genuine compressor wear, not a quick fix.
A Teck Ghee unit worked mornings but cut out every afternoon. The outdoor unit sat in an alcove with blocked airflow, tripping protection.
An Upper Thomson wall unit dripped on humid days. Mineral buildup at a downstream joint had narrowed the drain, so it was cleared.
A Mitsubishi Heavy ducted system at a Sembawang site kept resetting itself. A loose terminal was the cause, not the control board.
An Orchard office ducted system gradually lost airflow. Staff feared duct decay. The ceiling-void return filter had never been cleaned.
A Tuas factory unit was washed twice a year and still lost capacity. The cleaning was working. The metal underneath had run out of life.
Hougang HDB aircon showed an error after renovation works nearby. The fault was a nicked communication wire in trunking, not a failed board.
Samsung E1 after renovation in Jurong West HDB. Cable insulation nicked during drilling. Exposed wire shorted against trunking.
Panasonic H11 appeared after a Bedok thunderstorm. A loose indoor connection caused the fault. Reseating it cleared the error.
Samsung error appeared after servicing in Marina East. The board was locked in fault state, not dead. Reset and checks restored cooling.
A Tengah error code appeared right after renovation. The signal wire had been nicked and rejoined with wires swapped. Correcting it cleared.
Mitsubishi E6 in Yishun traced to a corroded wire splice in a ceiling void junction box. Weatherproof re-splice resolved it.
Daikin A3 kept returning after drain clearing in Toa Payoh. A sag in the drain line inside the false ceiling trapped sludge. Rerouted the line.
York E6 in Jurong East kept returning after resets. Corroded outdoor wire connections were cleaned and refitted. No board replacement needed.
LG CH05 in Ang Mo Kio kept returning. The outdoor wire connector was corroded, not the control board. Cleaned and refitted the connection.
Choa Chu Kang ducted LG office system showed CH38 with every zone fading. The leak traced to the branch distributor, not the outdoor unit.
Pioneer factory office cassette dripped again after cleaning. Dust sludge blocked the drain line, not a cracked pan or failed pump.
A Pioneer factory cassette leaked after a chemical wash. The drain pump hose was reassembled loose, not a new pump failure.
Cassette unit in Tuas factory losing cooling gradually. Condenser coil coated in industrial dust. Chemical servicing restored full capacity.
On-and-off aircon trips in a Sungei Kadut factory office traced to a corroded isolator switch. Wiring was intact. No cable replacement needed.
A Pioneer factory office became warm again. Years of oily grit cracked the condenser fan blade, cutting airflow though the coil looked fine.
Sungei Kadut factory office cassette had weak airflow. Sawdust coated the blower wheel, not a motor or gas fault from workshop dust.
A Tuas factory unit's drain pump siphoned water back after servicing. The non-return valve was installed backwards, not a pump failure.
A Sungei Kadut factory outdoor unit vibrated against its frame. Mounting isolators had perished from heat exposure, not a compressor fault.
Bedok HDB unit stopped cooling two days after routine service. Service valve left partially closed, restricting refrigerant flow.
A Telok Blangah flat was not cold at five years old. The condenser coil was crusted with salt from sea breeze; servicing restored it.
A Sembawang HDB flat's drain backed up and overflowed after routine servicing. The drain outlet cap was left on, not a new blockage.
A Hougang HDB flat leaked days after routine servicing. The pump's mounting bracket screws were left loose, not a new fault in the pump itself.
An Ang Mo Kio flat leaked days after a routine service. The drain hose had been reseated at the wrong angle behind the trunking.
A Yishun flat leaked near a trunking joint after routine servicing. The drain pipe had been reconnected with far too little fall.
A Kallang flat near Little India cooled poorly. Grease from food stalls had coated the condenser fins, not a leak or failing compressor.
An LG outdoor unit on a high-floor Punggol condo corroded in four years from wind and rain, leaking far earlier than expected.
Museum area gallery office felt warm after a display partition was added. The return air path was blocked, not a gas or compressor fault.
Tanglin landed room became warm in the afternoon. Seed pods blocked the garden-facing condenser, so heat could not escape properly.
Newton condo unit topped up twice in one year but kept losing cooling. A pinhole leak in the concealed copper pipe behind the wall was the cause.
A welded gas leak on an LG outdoor unit in Woodlands failed again. Cooling returned briefly before a new leak on the same corroded pipe.
A Yishun flat kept losing cooling after several top-ups. Focused checks on the service port traced it to a faulty service valve core.
Sharp 6-0 in Woodlands HDB. Fan motor grinding on a 13-year-old unit. Bearings worn out. Owner chose replacement over repair given the age.
Tampines HDB bedroom aircon dripped after years of use. A drain choke behind the trunking caused backup, not a cracked tray or gas problem.
Ang Mo Kio condo with three ceiling cassettes struggling to cool and high monthly bills. Outdoor unit was too small for the indoor capacity.
A Downtown Core high-rise unit hummed through the wall. Its internal compressor mounts had perished from wind sway, not the outer feet.
An Ang Mo Kio Daikin had ice on the pipe. Low gas was assumed. Airflow and coil condition pointed to buildup restricting the evaporator.
Punggol HDB indoor unit blew air but the outdoor side stayed silent. A starter relay fault in the start path was the cause.
A Choa Chu Kang industrial unit rattled on startup. Nearby machinery vibration had crumbled its leveling blocks, not a fault in the unit itself.
An older Jurong West outdoor unit rattled at night. Anchor bolts had backed out of aged, crumbling wall concrete, not a loose compressor.
A Dairy Farm landed home gradually lost cooling. Told the compressor was failing, but the condenser mesh was caked with renovation dust.
A Seletar landed home's drain pump never engaged after a chemical wash. The power lead was left unconnected, not a pump failure.
A Tanglin landed home's drain tray filled with dust after a wash. The return-air grille was left unlatched, not a new drain fault.
A Changi landed home aircon tripped once during a storm after a gas top-up. A loose isolator terminal screw, shaken by vibration, did it.
A Seletar landed layout ran pipes the shortest way between rooms. Drain fall could not hold on that route, so gradient set the design instead.
A Serangoon landed outdoor unit rattled after a storm. A bent fan guard mounting tab was touching the blade tip, not a motor failure.
Seletar landed aircon dripped and smelled musty after rain. Biofilm inside the drain tray caused both, not a cracked tray or failed indoor unit.
Macpherson HDB case: regular servicing missed deep evaporator coil fouling. Chemical servicing reopened the coil and restored cooling.
LG CH35 in Bedok: leak tracing found corroded outdoor pipe connections. After sealing and recharge, cooling returned without new parts.
LG CH38 case in Toa Payoh: a chemical wash loosened a nearby joint. Resealing it stopped the leak, without blaming the wash or the unit's age.
LG CH38 in Bukit Panjang: a pressure test found a loose flare-nut joint, not corrosion. Retightening and a recharge restored cooling.
An LG system 3 in Serangoon leaked along a long pipe run. Pressure hold testing narrowed it to the outdoor connections, not the piping.
Cooling kept dropping after gas top-ups in Bukit Batok. We traced the leak to corroded LG outdoor connections and gave three options.
Clementi HDB wall unit rattled loudly during startup then went quiet. Mounting was solid. Worn motor bearings let the rotor shift during spin-up.
Tanglin low-rise condo bedroom aircon rattled at night. A loose trunking cover vibrated, not compressor or indoor fan failure.
A Jurong East mall shop cassette dripped late in the day. The discharge hose had worked loose from the pump outlet, not a cracked tray.
A mall tenancy quote priced the install as one continuous day. Goods lift slots and after-hours drilling staged the work across nights.
Bukit Timah landed master bedroom became weak after pipe work. A loose flare joint was found before replacing the unit or topping up gas blindly.
A Toshiba multi-split in a Bukit Timah condo lost cooling in one bedroom. Pressure checks ruled out a leak; that room's valve had seized.
A Tampines flat smelled musty at every start-up and was quoted a chemical overhaul. The coil did need a wash. It did not need stripping down.
Newton condo outdoor unit cut out on hot afternoons. Storage on a narrow ledge blocked condenser airflow, so the unit overheated.
A brand-new Tampines unit never reached set temperature. The installer blamed settling-in, but a skipped vacuum left air in the line.
A new Punggol HDB outdoor unit hummed near the waterway. The fan guard was resonating in open wind, not a fault with the fan motor itself.
A new Tengah HDB outdoor unit rattled between blocks. A leftover shipping packing block was rattling against the fan guard, not a fan fault.
Cashew condo unit shut down every few hours with no error code. A replaced control board did not fix it. The room sensor was the cause.
One bedroom in a Tengah BTO stayed warm after carpentry work. Comparing the rooms exposed restricted intake air, not a failed aircon part.
New multi-split system in Bukit Panjang cooled unevenly. Two control wire pairs swapped at the wire connection point during installation.
A brand-new LG unit in Hougang threw CH38 within weeks. Leak checks found nothing: the installer never finished charging it correctly at setup.
Marina South office stayed warm after fit-out works. A supply grille was boxed in by ceiling works, not a gas or compressor issue.
PRISM+ wall unit case in Serangoon: a nearly-new unit rattled at certain fan speeds. A front panel clip had not fully engaged.
A new aircon unit in Tengah started leaking after its first service. The drain pan had not been reseated properly, not a defective unit.
Europace case in Serangoon: a new wall unit dripped only in humid weather. An out-of-level bracket was tilting the drain pan.
A Serangoon flat's aircon ran noisier and weaker after a chemical servicing. The blower wheel had been reassembled off-centre on its shaft.
A River Valley office cassette leaked after being relocated. The drain hose was kinked on the new run, not a new cassette fault.
Straits View office cassette leaked after servicing. The drain pump cover was misaligned, so water escaped inside the cassette.
Paya Lebar office cassette had weak airflow. Road dust loaded the return filter, so the unit needed cleaning, not gas top-up.
A Paya Lebar office ducted unit whistled above the workstations at high fan speed. A duct clamp was loose, not a fault with the unit.
Straits View office aircon showed an error after peak load. A drain overflow switch stopped the unit, not a failed board.
An office fit-out drawing spaced ceiling units evenly across the grid. Two had no return air path, so the void and partitions set it.
An office was quoted a full replacement after the outdoor unit failed. Testing the ceiling units and pipe run showed a smaller job held.
A Robertson Quay office aircon tripped only under heavy load. Wiring had worn through at a tight bend in a cramped condenser recess.
A Straits View ceiling-concealed office unit hummed through the marina-facing wall. Suspension rods were sitting uneven, not a fault.
A Marina South office outdoor unit rattled against the wall in waterfront gusts. Refrigerant pipe clips were loose, not a fault.
River Valley office aircon tripped after long runs. A stuck drain float switch stopped the unit, not a failed control board.
A Downtown Core office got warm by afternoon. The condenser was recycling hot air inside a service recess, so airflow mattered, not gas.
A Museum-district office zone stayed warm after a ducted unit relocation. The return damper was left closed, not a new cooling fault.
An older Bukit Merah block leaked after a chemical wash. The drain pump's discharge tube was crimped during reassembly, not a new failure.
An older Sengkang HDB outdoor unit rattled after storms. Wind-driven rain had loosened the fan guard, not a fault with the fan motor.
An older Bedok HDB outdoor unit rocked on startup. It was sitting on an unlevel ledge base, not a fault with the compressor.
An older Tampines HDB outdoor unit tapped the wall on every cycle. The support frame was flexing with age, not a compressor fault.
Newton condo trunking dripped after long cooling. A small insulation gap caused pipe sweat, not a cracked drain or gas problem.
Sembawang HDB unit rattled at night. The issue was hardened wall-bracket rubber transferring vibration, not a failing compressor.
A Choa Chu Kang room had weak airflow even with a clean filter. A gapped replacement filter let dust bypass onto the coil, not the blower.
Hougang HDB trunking drip came from a cracked drain elbow behind the casing. The indoor unit and gas circuit were not the problem.
An older Queenstown unit dripped along the trunking. The access panel's gasket had perished with age, not a cracked drain fitting.
An older Ang Mo Kio multi-split had three separate faults. Mapping each one showed why another isolated repair was an incomplete comparison.
A single indoor head failed on a Sengkang flat. The replacement was ordered on capacity alone, and the outdoor unit could not run it.
Orchard office stayed warm after partition works. The supply path was blocked by the new layout, not a weak aircon system.
Gree ducted office case: one zone stayed warm while the rest cooled. The zone's damper actuator had slipped on its shaft, not failed outright.
A Queenstown condo had one room staying warm while others cooled. The fault was indoor airflow and coil condition, not a system gas issue.
Straits View office had one warm zone while the rest cooled. The duct damper was stuck near closed, so cold air could not reach that side.
Daikin cassette in Geylang cooling one side poorly. Stuck louver vane and partial coil fouling on that section. Fixed without any parts.
Samsung E1 on one unit in a Sengkang condo system-3. Other two worked fine. Control board swap test confirmed indoor board fault. Replaced it.
An original Queenstown block leaked after a chemical wash. The drain line was not pushed fully home at the pump, not a new pump fault.
An original Toa Payoh HDB block's unit wouldn't restart after a chemical wash. The isolator switch was left off, not a new fault.
A Sungei Kadut industrial office cooled weakly. A past pressure-wash had flattened the condenser fins, so fin combing came first.
A Seletar outdoor unit buzzed after a windstorm. A prior repair left the fan blade off-centre, grazing the guard under storm sway.
A Jurong West outdoor unit buzzed but would not start. It sounded like compressor failure. One capacitor test settled it in a minute.
A Bukit Batok HDB outdoor unit clicked on every rotation in the afternoon. The fan blade had warped from heat, not a motor fault.
A Choa Chu Kang Daikin outdoor unit went silent. We tested and cleared the capacitor, starter relay, and wiring before confirming the fault.
Outdoor unit rattling loudly at night in Woodlands HDB. Mounting rubber had hardened and bracket bolts loosened. No compressor fault.
A Pasir Ris HDB outdoor unit rattled in the sea breeze. Salt-laden wind had loosened the fan guard, not a fault with the fan itself.
Bukit Timah landed outdoor unit rattled after storms. Leaves were caught behind the fan guard, not a failing compressor.
Boon Lay HDB unit had no airflow despite clean filters and blower. Power reached the fan motor, but it would not run. Burnt motor, not blockage.
A Pasir Ris flat's aircon tripped after rain. A loose terminal inside the isolator was condensing to earth in humid weather, not a seal.
Bukit Batok outdoor unit tripped on start. Rain and humidity had corroded the ledge isolator contact, found before quoting compressor work.
A renovation put four ageing systems in a Bukit Timah house up for replacement. Whether the buried copper could be reused set the scope.
Kampong Glam shophouse unit smelled musty even after servicing. Mould had colonised the evaporator coil fins behind the filter.
Tuas port-side office aircon tripped intermittently. Salt-air corrosion damaged the isolator, not the compressor or indoor board.
A pre-war Kallang shophouse aircon threw a random error code. An aged signal wire had chafed through inside old trunking, not the board.
A PRISM+ cassette in a Kallang office answered the remote on and off. A service cover left ajar let dust settle on the sensor window.
A Bishan condo was quoted a full chemical overhaul on all four units. Assessment found one blocked drain line and light coil dust, nothing more.
Mitsubishi E6 in Bishan condo appeared only when the drain pump ran. Communication cable alongside pump cable caused interference.
Wall unit rattling on startup in Boon Keng. Quoted for fan motor replacement. Blower barrel setscrew was loose. Tightened and noise stopped.
Pasir Ris HDB remote stopped controlling the unit. Power light stayed on, but no buttons worked. The receiver failed; the main board was fine.
Three fan coils in a Sengkang rental flat showed different conditions. A room-by-room check supported one overhaul and two lighter scopes.
A Yishun flat faced replacement of a twelve-year-old system. The outdoor unit never received a start signal, and the compressor tested sound.
A high-floor Newton condo was quoted to replace both ageing systems at once. Separate testing showed only one had finished its life.
A Yishun reservoir-side flat smelled musty when the aircon started. A blocked fresh-air path trapped humidity in the bedroom, not coil dirt.
A Clarke Quay restaurant unit dripped during dinner service. The drain line sagged around a heritage structural beam, not a cracked pan.
An Orchard retail outdoor unit buzzed above the street. Traffic and escalator vibration had loosened the mounting bracket.
An Orchard retail unit shut down at fixed early and closing hours. A shared corridor exhaust fan being off was the cause, not the condenser.
A Southern Islands outdoor unit rattled near the seafront. A rubber isolation mount had perished from exposure, not the fan motor.
A Carrier ceiling unit in a Serangoon shop buzzed for months. Support rod bolts had loosened from foot traffic, not a failing fan motor.
Bukit Merah shop aircon dripped near closing time. Long runtime exposed a jammed drain pump float, not a cracked tray or major unit fault.
A conservation shophouse had one airwell and three outdoor units to place. Stacking them would have left each breathing the others.
A Geylang shophouse leaked after a cleaning visit. The drain hose was never properly seated behind the access panel, not a new drainage fault.
Rochor shophouse aircon was not cooling well. The condenser was trapped in a narrow airwell, so hot air recirculated around it.
A Rochor shophouse outdoor unit rattled in its narrow airwell. The bracket never sat flush against uneven brickwork, not a fan fault.
An Outram conservation shophouse outdoor unit rattled on the five-foot way. Street-level traffic had shaken the bracket loose, not a fan fault.
A Rochor shophouse aircon tripped after rain. A sun-cracked cable sheath on an exposed rooftop run let moisture in, not the isolator.
A Geylang shophouse aircon tripped after rain. The isolator's cable entry had never been sealed, letting water track in during storms.
Outram shophouse trunking kept dripping. A retrofit drain pipe had backfall, so water sat in the line and leaked back before more drain clearing.
Paya Lebar unit started short cycling after servicing. The temperature sensor had been knocked out of its clip. Reseating it fixed the cycle.
A Southern Islands villa smelled of drains after its first heavy rain post-install. The new drain trap was left dry, letting air back.
A River Valley office had one room staying warm while others cooled. We confirmed a jammed damper linkage, not low gas or a compressor.
A Tengah BTO quote listed a four-outlet system because the flat has four rooms. Two of them are never cooled. The survey resized the job.
Gas kept disappearing from a Pasir Ris system across three visits. A held test traced it to pinhole corrosion at more than one point.
All three Mitsubishi Electric units showed E7 in Punggol. Wiring was clean. The outdoor board had stopped receiving signals entirely.
A near-new Punggol unit was quoted for chemical washing at its first service. The fins were bright metal and a filter rinse sufficed.
Sharp 7-0 in Bedok. Outdoor unit hard-starting and tripping on hot afternoons. A capacitor reading low, not a failed compressor, was the cause.
Canberra HDB cooling faded across two linked bedrooms after repeated top-ups. A pin-hole leak at a shared distributor joint fed both coils.
Seletar industrial cassette blowing unevenly across vanes. Compacted dust on one side of the blower wheel caused the imbalance.
Clementi HDB cooling faded after every top-up. We ran a pressure test overnight and traced the leak to the indoor pipe joint.
A Bukit Panjang HDB outdoor unit rocked on a hillside ledge in wind gusts. Support brackets were never fully tightened at install.
Southern Islands villa cassette dripped during humid weather. The drain pump chamber was dirty and could not keep up with the moisture load.
A Kallang meeting room stayed warm while nearby desks felt cold. The control sensor was serving the wrong zone, so no extra unit was needed.
Balestier HDB wall unit dripping onto bedroom floor. Drain tray was choked with algae blocking the outlet. Cleaned tray and flushed drain.
Ducted unit water overflow in a Tanglin landed home came from a stuck drain pump level switch, not a failed pump needing replacement.
Marina East office aircon smelled musty after idle weekends. Drain tray film and moisture were the cause, not gas or a failed indoor unit.
Marina East waterfront shop kept losing cooling after repeat gas top-ups. Salt corrosion had degraded the condenser coil, not a refrigerant leak.
Weak airflow returned in one Tampines bedroom after servicing. A room comparison showed why one fan coil needed deeper cleaning, not all three.
Europace cassette in Geylang: fading airflow traced to a grease film on the blower wheel, not the compressor. A degreasing clean fixed it.
Bukit Merah HDB room had weak airflow despite a clean filter. The blower wheel behind the cover was packed with dust, not a motor fault.
A Marine Parade condo cooled poorly and was quoted one overhaul price. Washing fixed the indoor side; salt damage outdoors did not.
A Buona Vista system-4 tripped when one bedroom unit switched on. A single faulty indoor board was triggering outdoor protection.
Tuas workshop office had weak airflow. The return filter was loaded with industrial dust, not a gas leak or failed cassette fan.
Ready to get started?