Skip to main content

LG CH38 on a Cassette: A Loose Fitting, Not Corrosion

LG CH38 on a Bukit Panjang condo cassette with slow gas loss rarely means corroded pipes. A poorly seated outdoor flare nut is the more common source.

On this page

How This Presents

A fault code appears on a Singapore condo unit cooling poorly, yet exposed pipework along the aircon ledge shows no corrosion anywhere. Connections look clean throughout, and cooling dropped slowly over time rather than all at once.

Setup
LG Cassette7-9 yearsCondoBukit Panjang
Misread as
Corroded pipework needing sections replaced, or a system approaching the end of its life.
Check first
Whether the pipework shows corrosion at all before the joints are examined
Actual finding
A flared connection at the outdoor unit that was never made up correctly
Scope saved
Targeted repair instead of full replacement
Flare connections and service valves at an outdoor unit
Flare connections at an outdoor unit's service valves. A joint made up incorrectly leaks from the day it is assembled, so the connections are tested before the pipe is condemned.

What Else Produces This

Clean pipework changes the search rather than ending it. A joint under-tightened, over-tightened or made on an imperfect surface passes gas from the day it was assembled, with no damaged metal. A leak test on the joints, then the sealing faces inspected before anything is tightened, separates this from corrosion. A loose nut and a cracked flare need different work.

  • No visible corrosion anywhere on the exposed pipework removes the usual explanation.

  • A gradual constant loss rather than an abrupt one fits a small permanent opening at a joint.

  • A loose connection at the outdoor unit accounts for the escape without any damage.

  • Sound metal and clean sealing surfaces at that joint show it can be remade rather than replaced entirely.

Why It Happens

A flared connection seals by pressing a shaped copper face against a fitting under controlled force. Too little and the faces never seat; too much and the flare distorts and cracks. Either way the joint passes refrigerant slowly from the moment it is made, and years can pass before the cooling loss is noticed. Nothing has degraded.

What Resolution Involves

Remake the connection to the correct specification, pressure-test it, then recharge. The rest of the system is sound and stays as it is.

How to Tell It Worked

Pressure holds on the remade joint before the system is charged. A joint that seals correctly does so immediately, so there is no reason to prove it with refrigerant.

Before You Approve a Quote

A leak does not need damaged metal to exist

  • A joint made up incorrectly leaks from the day it was assembled, on pipework that looks perfect.
  • No visible corrosion narrows the search to the joints rather than ending it.
  • Check the connections before condemning the pipe. One is an hour of work and the other is not.

Questions This Case Answers

Can an older LG cassette that keeps losing gas still be worth repairing?
An older cassette with slow, steady gas loss and clean pipework is often worth repairing. A flare joint made up wrongly passes refrigerant from the day it was assembled, and years can pass before the cooling loss shows. Remaking that joint, pressure-testing it and recharging leaves the sound rest of the system in place.
How does a pipe fitting work loose without any corrosion?
A flare fitting that leaks without corrosion was usually never made up correctly. Too little force leaves the copper faces unseated, and too much distorts or cracks the flare. Either way the joint passes refrigerant slowly on pipework that looks perfect. A loose nut and a cracked flare need different work, so the sealing faces are inspected.
What happens if the leak point is never actually found?
An unfound leak keeps passing refrigerant, so the gas keeps needing replacement and LG's CH38 keeps returning. The joints are leak-tested before any pipe is condemned. The fix is remaking the faulty connection to specification and proving pressure holds on it before the system is recharged, rather than topping up again.