Skip to main content

Why Is My Aircon Leaking Water from the Indoor Unit?

A blocked drain, an iced coil and bad pipe slope all leak inside Singapore HDB and condo rooms. Steady fixed drips mean drainage, bursts after weak cooling mean ice, and shifting drips mean slope.

On this page

Summary

Safety warning. If water is near electrical parts, stop using the aircon and leave it off until a technician checks it.

Likely Causes

  • A blocked drain path causes steady indoor dripping.
  • Ice melting off the coil releases water in bursts.
  • Condensation on an exposed pipe or a drain slope fault causes hidden or recurring drips.
Two dismantled indoor units with mould on the casings
Two dismantled indoor units with mould on their casings. Algae and mould in the drain tray block its outlet, and water then spills over the front.

Quick Fault Summary

  • Likely cause
    Drain-path blockage
    What to check
    Steady drip pattern during runtime.
    Typical next step
    A technician checks whether water backs up in the tray or pipe, clears the obstruction and flushes the drain, then retests under cooling load to confirm the leak stops.
  • Likely cause
    Freeze-thaw cycle
    What to check
    Leak appears in bursts, not a constant flow.
    Typical next step
    Once the ice has thawed, a technician removes the cause of the freeze-up: airflow is restored, or a refrigerant leak is located and sealed.
  • Likely cause
    Condensation routing or slope issue
    What to check
    Drip location shifts along trunking or wall path.
    Typical next step
    A technician traces the full water path, corrects the slope, re-routes or re-insulates the affected section, and retests under cooling load to confirm the leak stops.

1. Drain-Path Blockage

Steady dripping from one spot with normal cooling means water is backing up in the drain tray or pipe. Humid dust and mineral residue collect until water spills over. The aircon water leak checker helps if the pattern is unclear.

How to Tell

Steady, fixed dripping while the unit runs points to a blocked drain, not a freeze-thaw cycle. The drip point does not move along the trunking, unlike a slope fault.

  • Steady drip pattern during runtime.
  • Gurgling water sound near the indoor unit.
  • Cooling can still feel acceptable at first.
  • Drip always from the same fixed point on the casing.

How We Confirm It

A technician checks whether water backs up in the tray or pipe, clears the obstruction and flushes the drain, then retests under cooling load to confirm the leak stops.

Refrigerant work does not fix a drain obstruction, so drainage is checked before any gas work.

Related Cases

2. Freeze-Thaw Cycle

A leak that comes in bursts after weaker cooling or after shutdown is meltwater from ice on the coil. Low airflow or low refrigerant pushes the coil below freezing, and it dumps water when the ice releases. From the room it often looks like a drain problem.

How to Tell

Water in bursts after weaker cooling or shutdown points to freeze-thaw, not a blocked drain. Ice or frost on the copper pipe confirms freeze-up.

  • Leak appears in bursts, not a constant flow.
  • Cooling weakens before leakage worsens.
  • Ice beads or white frost crystals on the copper pipe, if the pipe is already visible.

How We Confirm It

Once the ice has thawed, a technician removes the cause of the freeze-up: airflow is restored, or a refrigerant leak is located and sealed. Cooling is then tested for stable running without icing.

If frost or ice shows, switch the unit off. Clearing the drain alone will not stop leaks that come from an iced coil.

Related Cases

3. Condensation Routing or Slope Issue

Wet patches shifting along HDB or condo trunking mean slope, routing or bare insulation, not a tray clog. Water pools in dips or sweats on uninsulated cold copper.

How to Tell

A drip point that shifts along the route points to slope or a dip, not a fixed blockage. Unlike freeze-thaw, it follows the exposed cold pipe rather than thermal bursts.

  • Drip location shifts along trunking or wall path.
  • Leak timing changes with weather or runtime.
  • Moisture appears even when cooling output seems normal.

How We Confirm It

A technician traces the full water path, corrects the slope, re-routes or re-insulates the affected section, and retests under cooling load to confirm the leak stops.

A new coil or complete re-piping will not fix a slope problem. The leak returns after each humid period until the slope is corrected or the pipe re-routed.

Related Cases