Told the Housing Cracked: Just a Clogged Drain Tray
Aircon case in Bugis, Singapore: water leakage traced to drain tray clogged with compacted dust and biofilm, causing condensate to overflow forward instead of draining to the pipe after targeted diagnosis checks.
Case Details
| Unit | DaikinWall-mounted |
|---|---|
| Age | 6 years old |
| Location | OfficeBugis, Singapore |
| Reported | Water has been dripping from the front of the indoor unit and pooling on the office carpet. Building management sent their contractor and he said the plastic housing had hairline cracks from age. They quoted us for a full unit replacement. |
What We Checked
- No visible cracks or deformation on the housing — seams were intact and clips seated correctly.
- Drain tray had a thick layer of compacted dust mixed with biofilm covering the outlet.
- The blockage caused condensate to back up and spill forward over the tray lip.
- Drain pipe itself was clear downstream — the restriction was only at the tray outlet.
The Diagnosis
Dust from the office environment had mixed with moisture to form a biofilm layer across the tray, narrowing the outlet to almost nothing. Condensate backed up behind it and overflowed — the housing was structurally fine.
What Fixed It
We cleared the biofilm from the tray, flushed the outlet, and tested drainage by running the unit at full cooling. Water flowed cleanly to the drain pipe with no overflow.
Dripping stopped on the same visit — the unit ran normally for the rest of the afternoon with no water on the floor, no parts replaced, and no unit swap needed.
Why This Happens
Drain tray blockage vs cracked housing.
- Water dripping from the front of the unit usually means the drain tray is overflowing, not that the housing has cracked. Cracked housings are rare on units under ten years old.
- Dust and biofilm build up in the tray over time, especially in office environments where the unit runs long hours. The blockage forms at the tray outlet where it narrows.
- A clogged tray is cleared by flushing the outlet and wiping down the tray surface. It does not require parts or unit replacement.