On this page
How This Presents
All four rooms on a shared Singapore flat system lose cooling over the same period, with the outdoor condenser sitting on the service ledge. Each indoor unit is clean and running, and the air from every one is cool rather than cold. Nothing was disturbed before the decline.
- Setup
- LG Multi-split10-12 yearsHDBSengkang
- Misread as
- Four separate faults appearing at once, or a system-wide failure needing everything replaced.
- Check first
- How many rooms on the system are affected, and whether they failed together

What Else Produces This
Simultaneous failure across every room costs nothing to read. Separate faults do not arrive together, so the likely reading is one fault at the point the rooms share: the outdoor unit and its refrigerant. The search starts with a leak test at the outdoor connections, and the indoor units wait until the shared end is cleared.
Every room affected over the same period argues strongly against four coincidental faults arriving together.
Clean indoor units running normally remove the indoor half from the explanation.
Cool but not cold air from all of them fits a shared shortfall in circulating refrigerant.
Refrigerant traces found at the outdoor connections locate the loss at the shared end precisely.
Why It Happens
One outdoor unit and one refrigerant charge serve every indoor unit. A leak at the outdoor connections reduces what circulates, and the shortfall is shared between them, so each room loses capacity over the same weeks. Nothing is wrong in the rooms themselves.
What Resolution Involves
The outdoor connections that fail the leak test are repaired and the circuit retested, and only then is the system charged to specification. That restores every room at once, with the indoor units left out of the scope.
How to Tell It Worked
Run all four rooms together under their normal load, not the worst one alone. A shared fault lifts every room; a room still behind has a second problem of its own.
Before You Approve a Quote
All rooms at once means the shared end
- Separate faults do not arrive together. Simultaneous failure across rooms means one cause upstream.
- On a shared system, the outdoor unit and the charge are what every room has in common.
- Count the affected rooms first. That count narrows the search before any tool comes out of the van.