Skip to main content
WhatsApp

Two Top-ups in Four Months: Slow Leak at Indoor Flare Joint

Aircon case in Clementi, Singapore: cooling loss traced to slow refrigerant leak at indoor flare joint after targeted diagnosis checks.

Case Details

UnitDaikinWall-mounted
Age8 years old
LocationHDBClementi, Singapore
ReportedThe unit had been topped up twice in about four months. Each time cooling returned for a few weeks, then started to fade. The previous technician had been repeating the top-up without investigating further.

What We Checked

  • Refrigerant pressure well below operating range — confirmed low gas.
  • Applied nitrogen charge and sealed the system for an overnight hold test.
  • Pressure had dropped measurably by the next morning — active leak confirmed.
  • Leak traced to the indoor flare joint using bubble solution — small gap at the connection.

The Diagnosis

The flare joint at the indoor unit connection had developed a slight gap where the copper flare meets the brass fitting. Over years of thermal cycling — the pipe expanding when the compressor runs and contracting when it stops — the flare had deformed just enough to lose its seal. The gap was too small to detect without bubble solution, but large enough for refrigerant molecules to escape steadily. The loss rate was slow, taking weeks to drain below the cooling threshold, which is why each top-up appeared to work before the same pattern returned.

What Fixed It

The joint was fixable without replacing any parts. We removed the old flare, cut back the copper pipe to clean metal, and formed a fresh flare using a calibrated tool to ensure the correct cone angle. The joint was reconnected, torqued to spec, and sealed. We ran a second overnight nitrogen test to confirm the new connection held pressure. Once the hold was verified, the system was evacuated and recharged to the manufacturer-specified gas weight. No compressor or coil work was needed.

The joint was sealed and the system recharged. Cooling has been stable since the repair — no further top-ups have been needed.

Why This Happens

Top-up and hold vs. top-up and repeat.

  • A top-up that holds for years usually means the original charge was slightly low or a hairline gap sealed itself under pressure. No further action needed.
  • A top-up that fades in weeks means gas is actively escaping through a physical gap. Each refill leaks out through the same opening because nothing has changed structurally.
  • A nitrogen pressure test is the only way to confirm whether the system holds or bleeds. Without it, every top-up is a guess — and guessing compounds the cost.
  • Ask your technician whether they pressure-tested before recharging. If they only checked gauge pressure with refrigerant in the system, they confirmed low gas but not whether there is a leak.

Guides, troubleshooting, and diagnostic case studies to help you make informed decisions.

Same situation with your aircon?

Describe what’s happening. We’ll work out the likely cause and tell you the right next step.

WhatsApp us