New Aircon Never Cooled Properly: Installer Undercharged The Gas
A brand-new unit had never cooled the bedroom to the set temperature. After two weeks of running, the room still hovered several degrees above target. The installer said new units need time to settle in.
Case Details
| Unit | DaikinWall-mounted |
|---|---|
| Age | 2 years old |
| Location | HDBTampines, Singapore |
| Reported | The unit was installed two weeks ago and has never cooled the bedroom properly. At 24 degrees, the room still sits around 27 to 28 after running for two hours. The installer came back once and said new units take time to reach full performance. |
Diagnostic Turning Point
- Concern: Previous advice was that poor cooling from a new unit was normal and that it needed time to settle in
- Key check: Low-side pressure measured well below normal operating range for the ambient conditions. Confirmed undercharge, not a leak
What We Checked
A brand-new unit that cannot reach its set temperature from day one has a very short list of possible causes. The unit itself is factory-tested, so the compressor, coil, and control board are unlikely to be faulty. That leaves the installation, specifically the refrigerant charge, pipe connections, and expansion device setup. We went straight to measuring refrigerant pressure on both high and low sides, because the pressure profile tells you immediately whether the charge is correct for the installed pipe length.
- Low-side pressure well below the manufacturer spec for this model at the ambient conditions.
- High-side pressure correspondingly low, pointing to undercharge rather than a restriction or expansion device fault.
- Leak check on all pipe connections, flare joints, and service ports found no leak, the charge had been set too low at installation.
- Airflow, filter, and coil condition all normal. No obstruction or mechanical issue apart from the refrigerant deficit.
The Diagnosis
The unit had been undercharged at installation. Refrigerant was approximately 35 percent below the manufacturer specification for the installed pipe length. Either the installer did not connect gauges to verify the final charge, or the reading was taken but not compared against the manufacturer table for this specific pipe run distance. Both high-side and low-side pressures were proportionally low, which confirmed a simple refrigerant shortfall rather than a restriction, blockage, or expansion device fault. There was no leak at any connection point. The unit had been running with this deficit since the day it was installed, which is why cooling had never reached the expected level.
What Fixed It
We added refrigerant incrementally while monitoring both high-side and low-side pressures live. The charge was brought up to the correct specification for the installed pipe length as listed in the manufacturer table for this Daikin model. After reaching the target pressures, we re-measured under steady-state operation to confirm both readings fell within the acceptable range. Supply air temperature at the vent dropped significantly compared to before the correction. We documented the before and after pressure readings so the client could raise the issue with the original installer.
The bedroom reached set temperature for the first time since installation. The client was advised to raise the undercharge with the original installer.
Why This Happens
New units should cool properly from day one.
- There is no settling-in period for air conditioning. A correctly charged unit reaches its rated capacity from the first day. If it does not, the installation needs checking.
- Undercharge happens when the installer does not verify final pressure against the manufacturer spec for the installed pipe length. It is a process gap, not a product defect.
- An undercharged new unit behaves the same as an older unit that has lost gas over time. The compressor runs and airflow feels normal, but the air never gets as cold as it should.
- If a new unit underperforms, get an independent pressure check before accepting any explanation about settling in. The readings will confirm or rule out undercharge in minutes.
Related Reading
Ready to Get Started?
Tell us what’s going on. Symptoms, setup, photos, anything we should know. We’ll assess and come back with the right next step.