Two Top-ups, Still Losing Gas: Leak at Outdoor Pipe Joint
Aircon case in Pasir Ris, Singapore: cooling loss traced to refrigerant leak at outdoor unit pipe connection after targeted diagnosis checks.
Case Details
| Unit | Mitsubishi ElectricWall-mounted |
|---|---|
| Age | 6 years old |
| Location | HDBPasir Ris, Singapore |
| Reported | Gas had been topped up twice in roughly six months — each time cooling returned briefly then faded again. Two different technicians had checked and neither found a leak. |
What We Checked
- Refrigerant pressure below normal — confirmed low gas on arrival.
- Nitrogen pressure test held for two hours — pressure dropped, confirming an active leak.
- Indoor pipe connections checked with bubble solution — no leak visible.
- Outdoor pipe connection at the service valve showed bubbles — leak confirmed there.
The Diagnosis
The leak was at the outdoor service valve — the brass fitting where the copper refrigerant pipe connects to the condenser unit on the ledge. The connection had loosened over six years of compressor vibration. Each compressor start-stop cycle transmits a small mechanical pulse through the pipe, and over thousands of cycles the flare nut had backed off just enough to let refrigerant seep past the seal. The loss rate was slow — a few grams per day — which is why cooling held for weeks after each top-up before dropping below the threshold. Previous technicians found tight joints at the indoor unit and stopped there, never checking the outdoor end of the pipe run.
What Fixed It
The outdoor connection was accessible on the ledge. We disconnected the flare fitting, inspected the flare face for deformation, and found the seat was still serviceable. The nut was retorqued to the manufacturer-specified value with a calibrated torque wrench, and we applied a fresh nitrogen pressure test to confirm the seal held for two hours with no measurable drop. Once the hold was confirmed, the system was evacuated and recharged to the correct gas weight. No pipe replacement or additional parts were needed.
The outdoor connection was sealed and the system recharged — cooling has held since with no further top-ups needed.
Why This Happens
Why leak locations are sometimes missed.
- Most technicians start at the indoor unit because that is the most accessible point. If the indoor joints are tight, some stop there. But the outdoor service valve connection is equally prone to leaks, especially in exposed ledge environments where thermal cycling and vibration are constant.
- Bubble solution must be applied to every connection in sequence — indoor flare joints, pipe bends at trunking exits, and outdoor service valve fittings. Skipping any section means a leak in that section goes undetected.
- A nitrogen pressure test confirms whether a leak exists somewhere in the system. It does not tell you where. Locating the exact point requires checking each joint individually with bubble solution or electronic detection after the pressure test flags the system as leaking.
- Ask your technician whether they tested both the indoor and outdoor connections. If they only checked one end and found nothing, the leak may simply be at the other end of the pipe run.
Related Reading
Guides, troubleshooting, and diagnostic case studies to help you make informed decisions.
Same situation with your aircon?
Describe what’s happening. We’ll work out the likely cause and tell you the right next step.
WhatsApp us