On this page
Summary
Likely Causes
- A compressor that fails to start or hold load leaves the fan running with no cooling.
- Refrigerant loss or restriction cuts cooling while the outdoor fan still spins.
- A control fault that interrupts the compressor start command gives partial outdoor operation with no full cooling cycle.

Quick Fault Summary
| Likely cause | What to check | Typical next step |
|---|---|---|
| Compressor not loading while fan runs | Outdoor fan spins but the room stays warm from the first run. | A technician listens for compressor engagement, tests the run capacitor against its rating and checks the contactor. |
| Refrigerant path loss or restriction | Cooling has faded slowly over weeks rather than failing at once. | A technician measures suction and discharge pressure, reads suction line temperature and inspects joints for oil traces. |
| Control path allows partial run only | Cooling works some days and fails others under the same conditions. | A technician checks the indoor-outdoor communication signals and stored codes, then confirms whether the compressor start command fires. |
- Likely cause
- Compressor not loading while fan runs
- What to check
- Outdoor fan spins but the room stays warm from the first run.
- Typical next step
- A technician listens for compressor engagement, tests the run capacitor against its rating and checks the contactor.
- Likely cause
- Refrigerant path loss or restriction
- What to check
- Cooling has faded slowly over weeks rather than failing at once.
- Typical next step
- A technician measures suction and discharge pressure, reads suction line temperature and inspects joints for oil traces.
- Likely cause
- Control path allows partial run only
- What to check
- Cooling works some days and fails others under the same conditions.
- Typical next step
- A technician checks the indoor-outdoor communication signals and stored codes, then confirms whether the compressor start command fires.
1. Compressor Not Loading While Fan Runs
The Singapore ledge fan spins steadily, yet rooms stay warm. When the run capacitor weakens in tropical heat, the compressor hums briefly and quits while the fan runs on.
How to Tell
From a window near the outdoor unit, you hear only fan airflow, never the deeper steady hum of a loaded compressor, and the room is warm from the first run. The failure is sudden, total and the same on every attempt.
- Outdoor fan spins but the room stays warm from the first run.
- The outdoor unit gives only airflow noise, no deep loaded hum.
- A brief hum or click, then nothing, repeats on each start.
How We Confirm It
A technician listens for compressor engagement, tests the run capacitor against its rating and checks the contactor. That separates a failed start part from a failed compressor.
A failed run capacitor mimics a dead compressor, so the capacitor is tested before any compressor decision.
2. Refrigerant Path Loss or Restriction
Rooms cool slower each week while vent air loses chill. A slow flare leak or cracked copper line drops charge, or a partly shut service valve restricts flow.
How to Tell
Refrigerant loss declines gradually: cooling weakens over weeks or months, run times stretch longer, and the vent air feels cool but never cold. Unlike a compressor that will not load, it is slow rather than sudden, and the outdoor unit runs consistently every time.
- Cooling has faded slowly over weeks rather than failing at once.
- Vent airflow feels normal but the air is not properly cold.
- The unit runs longer and longer without the room catching up.
How We Confirm It
A technician measures suction and discharge pressure, reads suction line temperature and inspects joints for oil traces. That separates a leak, a restriction and a charge shortage.
No gas goes in until the leak is located and fixed. A top-up alone fades again while the joint keeps losing charge.
Related Cases
3. Control Path Allows Partial Run Only
Cooling works on some runs and fails on others in similar weather. On the bad runs the outdoor fan spins and the room stays warm. A control or communication fault stops the compressor start command at random.
How to Tell
The giveaway is unpredictability. Refrigerant loss fades steadily and a compressor that will not load fails the same way every run. A control fault gives full cooling one day and none the next, under identical heat.
- Cooling works some days and fails others under the same conditions.
- The fan keeps spinning while the room temperature ignores the setpoint.
- A blinking light or unexpected stop shows when cooling is lost.
How We Confirm It
A technician checks the indoor-outdoor communication signals and stored codes, then confirms whether the compressor start command fires. Send a photo of any blinking light or code with the WhatsApp message.
A board or compressor swap before the start command is checked misses an intermittent communication fault, and healthy parts get replaced.