Skip to main content
snowflakeaircon.sg
WhatsApp

5.0onGoogle&Carousell

15,000+ jobs completed

Aircon Compressor Windings: The Motor in the Refrigerant

Half of a compressor is a pump and the other half is an electric motor. The motor half usually settles what happens to the machine, because it is the half anyone can put a reading on. A replacement recommendation should rest on that reading.

By Team Snowflake | Updated 16 Sept 2026

What a compressor motor is made of

A compressor motor is copper wire wound into coils and packed into a steel core. Those coils are the windings, and current through them produces the turning force. The pump sits on the same shaft.

Nothing separates one turn of that wire from the next except a film cured onto the copper. The wire arrives at the winding machine already coated, and nothing is wrapped around it afterwards. Two thicknesses of film stand between neighbouring turns.

The same film keeps the windings clear of the metal around them. The core they sit in is steel, fixed to the compressor body, which is earthed through the unit. A coil pressed into a metal slot with a coating between the two is the whole arrangement.

Everything here follows from two facts: the insulation is thin, and nothing else shares that job. Almost every electrical death of a compressor is that film letting go at one point.

Two windings, and three wires out through the shell

Most compressors in local flats run on single-phase supply, which carries two windings rather than one. The run winding does the work once the motor turns; the start winding, helped by a capacitor, breaks it away from standstill.

Three connections leave the shell to serve those two, with one shared. How they cross steel without letting anything out is its own topic. What matters here is that both ends of the wire are reachable from outside, which is why any of this can be read at all.

Why the motor is sealed inside the refrigerant

Putting the motor inside solves a sealing problem. A motor outside would drive the pump through a shaft crossing the shell wall, and a shaft crossing a wall must pass through something that wears. Welding the machine shut removes that joint along with the leak it becomes.

The arrangement also feeds the windings their cooling. Gas returning from the room enters the shell first and washes over the motor before it reaches the pump. Heat coming off the wire is picked up there and leaves with the stream.

That ties the motor to the circuit. What cools the wire is the same refrigerant that cools the room, so less arriving means less heat carried away, and the motor runs hot for reasons sitting nowhere near it.

So a low charge is not only a cooling complaint. A system short of gas returns warmer vapour to the compressor, and warmer vapour cannot pull the same heat out of the windings. A circuit quietly undercharged has held its motor above design temperature for just as long.

Restriction reaches the same place by another road. Anything narrowing the path back to the compressor reduces what arrives at the windings, while a choked outdoor coil raises the temperature the machine discharges into.

The coating has to survive what surrounds it

Sitting in the stream means sitting in the chemistry. Wire for a sealed motor is qualified against refrigerant and oil under a published magnet-wire standard, because the coating must keep insulating while soaked in both for the machine's working life.

The oil is often the harsher of the two. Testing behind that standard notes that lubricants in current compressors can be more aggressive on wire coatings than the refrigerants they travel with. A circuit given a product it was never matched to becomes a motor question, not only a chemistry one.

What wears the insulation down

Heat is the ordinary one. Every run puts current through the wire, current makes heat, and insulation ages faster the hotter it is held. A motor kept warm season after season arrives there on its own.

Moisture is worth understanding because it never attacks the coating directly. Water left inside a sealed circuit finds the refrigerant and oil to work on, and acid comes out of that reaction; refrigeration guidance ties those acids to winding insulation deterioration. That is why a system is dried before charging, then given a drier to hold it dry.

The drier is a wear part rather than a fitting, and what a filter drier does is written up on its own page. Its condition and the wire's condition are one story told at two places on the circuit.

Starting is where the wire takes its heaviest load. A motor at standstill draws far more current than the same motor turning, and anything making the break-away harder stretches that moment out. Tired starting components belong here, as does a restart attempted before pressures have settled, which compressor lockout holds a unit back to prevent.

  • What the wire is exposed to
    Heat with nowhere to go
    What puts it there
    A charge sitting below the figure the equipment was sized for
    What an owner can act on
    Asking why gas was needed, rather than accepting another top-up
  • What the wire is exposed to
    Acid formed from water, refrigerant and oil
    What puts it there
    A circuit opened and closed again without being dried out
    What an owner can act on
    Asking what was done to dry the system after any repair
  • What the wire is exposed to
    Heavy current on every attempt to start
    What puts it there
    Weak starting components, or restarts against unsettled pressure
    What an owner can act on
    Recording how often the unit stops and tries again
  • What the wire is exposed to
    A product the coating was never matched to
    What puts it there
    Refrigerant or oil of unknown origin put in at some point
    What an owner can act on
    Keeping the paperwork from every gas visit the unit has had
  • What the wire is exposed to
    Warm return vapour on a long run
    What puts it there
    A restriction quietly starving the line that feeds the shell
    What an owner can act on
    Reporting rooms that cool slower than they used to

Nothing about this shows from the room

Insulation ageing announces nothing. The film does not thin evenly and then give a date. It holds, and holds, and then fails at the one place where conditions happened to be worst.

What an owner can see is the history that put it there: a unit topped up more than once, a circuit opened several times, a machine that stops and restarts more than it used to. None are winding faults; all are the conditions a winding fault grows in.

The electrical outcomes a technician separates

Every electrical verdict on a compressor lands on one of three findings: the copper path is broken, two things that should stay apart are touching, or a winding is touching the body. Each says something different.

An open winding means the path along the copper is broken somewhere: nothing flows, so nothing turns. The outdoor unit stays silent while the rest of the system behaves normally and the indoor fan carries on.

A short means the film gave way between two conductors meant to stay apart. Current then takes a shorter route than the motor was built around. A machine in this state often still runs: it pulls more than it should, makes heat where it should not, and cools less.

A winding touching the body is the third, and it ends the discussion fastest. The steel shell is earthed through the unit, so a winding in contact with it sends current to earth. Earth-leakage protection exists to catch exactly that, and these usually trip the ELCB the moment the unit is asked to run.

What separates the three in the field is what the machine does while power is still on it. Silent outdoors with everything else alive points one way, running badly another, and cutting the supply the instant it starts points at the third.

  • What has failed
    The copper path along a winding is broken
    What the machine does
    Outdoor unit silent, the rest of the system behaving
    What it means for the compressor
    Finished, once a tripped protector has been ruled out
  • What has failed
    Film gone between turns of the same winding
    What the machine does
    Still runs, pulls more, cools less than it did
    What it means for the compressor
    Failing, and the reading will keep moving
  • What has failed
    Film gone between the two separate windings
    What the machine does
    Struggles to break away, or starts and then stops
    What it means for the compressor
    Finished as a motor, whatever the pump is like
  • What has failed
    A winding is resting against the earthed body
    What the machine does
    Protection cuts in as soon as it is asked to run
    What it means for the compressor
    Finished, and not something to keep retrying
  • What has failed
    Nothing yet, the internal protector has opened
    What the machine does
    Silent while hot, alive again once it has cooled
    What it means for the compressor
    Nothing yet, but something made it that hot

An open reading is not always an open winding

A compressor with a built-in protector reads as an open circuit while that protector is out. The device sits inside the shell among the windings and opens when the motor gets too hot. Until it cools, a meter sees what a broken wire would show it.

That is the most expensive mistake available here. A hot compressor tested on the spot can be condemned for a fault it does not have, and the heavy parts inside hold heat long after the shell feels cool. Letting it come down and reading again settles the question.

A protector that has opened is still worth something as information. It says the motor reached a temperature it was built to retreat from. The pattern of those retreats is the useful part, not the single event.

Why the windings can be measured when the rest cannot

Almost everything else about a sealed compressor is inferred. Pressures, currents and temperatures describe behaviour, and a technician reasons backwards toward what must be happening inside. The windings are different: the wire has ends that come out through the shell.

Two things get read there. One is resistance along the windings, which says whether the copper path is intact and whether the two windings still stand in the right relationship. The other is resistance between a winding and the steel body, which says how well the film holds current away from earth.

That second figure is what people usually mean by the compressor being tested. It measures the coating rather than the copper, and it is the only direct evidence about the insulation; everything else on a sealed part is argument from behaviour.

One figure on one day is not a verdict, and the manufacturers say so. Copeland's published position is that a single poor reading should not condemn a hermetic compressor; contaminated oil and refrigerant both move the number.

Temperature moves it as well. A compressor standing cold with liquid refrigerant in the shell reads lower than the same compressor warm and running, because what surrounds the windings has changed. Two honest technicians can measure one machine hours apart and disagree.

None of that makes the measurement worthless. It makes it evidence rather than a verdict, a distinction worth holding once a large number is attached to the answer.

What to ask before agreeing to a replacement

A verbal summary is not a reading. The figures either got written down or they did not, and asking for them is a reasonable request that a competent supplier answers without friction.

  • The figures themselves rather than a description of them, and what each was read across
  • Which state the compressor was in at that moment: standing cold, warm, or under load
  • Whether it was read again once the compressor had come down to room temperature
  • What got ruled out first, since starting components produce the same complaint for far less money
  • Whether anything was found in the oil, because that widens the job past the part

Where the answer goes from here

A confirmed winding fault does not decide what happens to the unit by itself. Whether a compressor is worth replacing gets weighed against the age of the system and the state of everything around it; repair vs replace sets out that judgement.

An electrical ending also leaves something behind that a mechanical one does not. What that residue does to the pipework, and how the next compressor inherits it, belongs to compressor burnout. This page stops at the wire.

A motor still holding but no longer strong shows itself well before any of this. The signs of a compressor failing describe what that looks like from inside the room, which is the earlier and cheaper place to catch it.

Common questions

How is a failed compressor winding detected?
The winding ends come out through the shell, so they can be measured. Resistance along the coils and resistance between a winding and the earthed body show whether the copper path or the insulation has failed.
Can a hot compressor read as an open winding?
Yes. A built-in protector opens when the motor overheats, so a meter sees an open circuit until the compressor cools. A reading taken while it is hot should not condemn the part.
What should I ask before approving a compressor replacement?
Ask for the actual figures, what each was read across, and the state of the compressor when they were taken. Also ask what was ruled out first, since starting components produce similar symptoms for far less money.

Sources