Cooling kW vs Power kW: The Two Numbers on a Spec Sheet
A spec sheet states two figures in kilowatts, and they measure opposite things. One is the heat pulled out of the room. The other is the electricity bought to move it, and reading them as one number inflates every running-cost estimate that follows.
By Team Snowflake | Updated 15 Sept 2026
Two kW figures that measure opposite things
A spec sheet gives cooling capacity and power input in the same unit, and readers routinely collapse them into one number. Cooling capacity is heat leaving the room; power input is electricity entering the machine. A model listed at 2.6 kW of cooling does not pull 2.6 kW from the socket, and the gap between them is wide.
Cooling capacity answers what the machine does to the room. It counts heat removed, measured against fixed indoor and outdoor test conditions, and it is the figure the trade means by size. It is what an aircon horsepower bracket stands in for, and the number a room load has to be matched against.
Power input answers what the machine costs to run. It counts the electrical energy drawn by the compressor, the two fans and the control board while the unit holds rated output. Nothing else on the sheet feeds a bill estimate. Capacity does not, and neither does the BTU/h figure, which is only capacity restated in another unit.
The confusion has one source. Kilowatts describe a rate of energy, and heat and electricity are both energy, so the unit really is the same. What differs is the direction and the medium: a kilowatt of heat leaving a bedroom and a kilowatt of electricity arriving at a wall socket are the same quantity pointed at different things.
Getting this wrong compounds quietly. Multiply a capacity figure by a tariff and the answer overstates the truth by a factor of three to five, and every conclusion inherits the error. That arithmetic sits behind most of the alarm that arrives before anyone has read a meter.
Why the cooling figure is always the larger one
An aircon does not manufacture cold. It relocates heat the room already contained, and shifting heat that exists takes far less electricity than conjuring a cold from nothing would.
Refrigerant does the carrying. It evaporates at a temperature below the room and soaks up heat from air crossing the indoor coil. The compressor then squeezes it until it condenses above outdoor air temperature, and the condenser fins hand that heat off outside. Electricity pays the compressor for the transport, not the heat itself.
Output larger than input looks like something for nothing, and it is not. Add the heat removed to the electricity consumed, and the outdoor unit rejects the sum of both. That is why condenser air runs hotter than anything the room held, and why a blocked outdoor unit punishes a system so fast.
The same hardware runs backwards in colder countries. Point the cycle the other way and it delivers heat indoors, still moving it rather than generating it. A fridge does the identical job on a smaller box, which is why its back is warm while the inside is cold.
The ratio has a ceiling, and physics sets it rather than marketing. A wider temperature gap costs more electricity for every unit of heat shifted, so the same machine buys cooling at a worse rate on a hot afternoon than at night. Any claim of an output multiple far outside the range below quotes a laboratory corner, not a living room in Singapore.
The relationship also explains a pattern homeowners report often. A system losing its ability to shed heat outdoors keeps drawing electricity while moving less of it, so the ratio collapses even though input holds steady. The bill stays where it was, or climbs, while the room gets warmer. That combination points at heat rejection, not a machine that has stopped trying.
The ratio between them is COP
Divide cooling capacity by power input and the answer is the coefficient of performance. A unit shifting 3.5 kW of heat while drawing 1.0 kW has a COP of 3.5. That value is the honest way to read a spec sheet, because it holds the two figures against each other instead of quoting whichever flatters the model.
COP describes one measured moment, not a season. Rated cooling capacity and rated power input are both taken at a defined indoor and outdoor temperature with the compressor held at full output. The ratio belongs to that condition, and it compares two machines fairly because both went through the same test.
Singapore publishes the pair for every registered household model, so none of this has to be taken on trust. The NEA register carries rated cooling capacity and full-load COP against each of 340 models. The lowest ratio in that set is 3.0, and not one registered machine draws anything near the electricity its cooling figure states.
The table below pairs the capacity bands homeowners actually shop in with the input figures sitting behind them. Read it as the shape of the relationship rather than a lookup for a specific model.
Two machines in the same band can separate sharply on input. The register holds a pair of single splits both rated near 3.5 kW of cooling, one drawing 0.70 kW at full output and the other 0.96 kW. Same heat out of the room, one bought with a quarter less electricity. Capacity alone cannot see that difference; the ratio can.
A second efficiency figure exists for behaviour away from full output, and the register carries that one too. It answers a different question about the same machine. It does not change what either nameplate number means.
| Rated cooling capacity (kW) | Rated power input (kW) | Full-load COP |
|---|---|---|
| 2.45 to 2.92 | 0.50 to 0.63 | 4.4 to 5.4 |
| 3.24 to 3.73 | 0.70 to 0.96 | 3.6 to 5.0 |
| 4.84 to 5.48 | 0.99 to 1.38 | 3.7 to 5.1 |
| 6.90 to 7.65 | 1.46 to 1.92 | 3.7 to 5.0 |
- Rated cooling capacity (kW)
- 2.45 to 2.92
- Rated power input (kW)
- 0.50 to 0.63
- Full-load COP
- 4.4 to 5.4
- Rated cooling capacity (kW)
- 3.24 to 3.73
- Rated power input (kW)
- 0.70 to 0.96
- Full-load COP
- 3.6 to 5.0
- Rated cooling capacity (kW)
- 4.84 to 5.48
- Rated power input (kW)
- 0.99 to 1.38
- Full-load COP
- 3.7 to 5.1
- Rated cooling capacity (kW)
- 6.90 to 7.65
- Rated power input (kW)
- 1.46 to 1.92
- Full-load COP
- 3.7 to 5.0
How the ratio shifts by system format
Format moves the ratio more than brand does. A portable rejects its heat through a hose and fights its own exhaust doing it; a split system puts the condenser outside where the heat belongs. The register shows what that choice is worth before any badge is considered.
The right-hand column matters as much as the ratio. On a multi-split, the input figure covers the outdoor unit serving every head at once. It is not the draw of the one bedroom running, and it cannot be divided by the number of rooms.
| System format | Full-load COP on the register | What the input figure covers |
|---|---|---|
| Portable | 3.0 to 3.5 | The whole unit, exhaust hose included |
| Casement or window | 3.8 to 4.2 | One machine serving one room |
| Single split | 3.6 to 5.4 | Indoor and outdoor unit together |
| Multi-split | 4.4 to 5.7 | The shared condenser, not one room's share |
- System format
- Portable
- Full-load COP on the register
- 3.0 to 3.5
- What the input figure covers
- The whole unit, exhaust hose included
- System format
- Casement or window
- Full-load COP on the register
- 3.8 to 4.2
- What the input figure covers
- One machine serving one room
- System format
- Single split
- Full-load COP on the register
- 3.6 to 5.4
- What the input figure covers
- Indoor and outdoor unit together
- System format
- Multi-split
- Full-load COP on the register
- 4.4 to 5.7
- What the input figure covers
- The shared condenser, not one room's share
Where both numbers sit on a real unit
The rating label carries both figures, printed close enough together to be conflated at a glance. Cooling capacity usually comes first, and power input follows, printed as rated input, input power or power consumption depending on the maker. On a wall unit the sticker hides behind the front flap or along the lower edge of the casing.
A brochure states the same pair inside a specification table, with more columns and more room for error. Capacity appears as a rated value flanked by a lowest and a highest figure, and input appears the same way. Read across a single column: pairing a rated capacity with a minimum input produces a ratio no machine on the register reaches.
A cost estimate uses power input and nothing else. Capacity in kW and the BTU/h figure are one statement in two units, and neither is electricity. A calculator or salesperson asking only for the BTU figure is treating capacity as a stand-in for input, which holds only while efficiency is assumed rather than checked.
A third electrical figure on the same label catches people out. Rated current, printed in amps, describes what the circuit has to carry rather than what the meter records. Multiplying amps by voltage overstates the draw on any motor load, because current and voltage do not stay in step across the cycle. Take the kW input figure for cost; leave the amp figure to whoever sizes the breaker.
Where the label has gone, the model number settles it. The NEA register publishes capacity and full-load COP against the model, and dividing the first by the second returns the input figure with no sticker left to read. Sun and repainting take the indoor label long before the machine gives up.
The outdoor unit carries its own label, and on a shared system that one is the honest total. Two bedrooms running together on a single condenser draw less than two separate systems would, a genuine advantage and a complication for anyone costing one room. The per-room answer is not printed anywhere, and it is not the head's capacity divided by anything.
What an inverter does to the input figure
The rated input figure is one point on a curve, and a modulating unit spends most of its life elsewhere on it. The compressor changes speed continuously to match what the room loses, and input power tracks that speed minute by minute. The nameplate states what the machine draws while holding rated output, a condition it passes through on the way to comfortable and seldom returns to.
This is why multiplying the nameplate input by runtime overestimates. The multiplication assumes full output for the whole session. A correctly sized inverter in a settled room does the opposite. It pulls hard until the set point arrives, then drops to a fraction of rated input and holds there against whatever the walls and windows let back in.
The overestimate is not guaranteed, and that is worth knowing. An undersized machine, a room with heavy afternoon glass, or a coil fouled enough to blunt heat transfer never lets the compressor back off, so the nameplate input is close to the sustained truth. A bill matching the naive multiplication is a symptom worth investigating, not a coincidence.
The published range shows how much modulation there is to work with. Input shown as a rated value between a minimum and a maximum describes how far the compressor can wind down. A wide span means it can idle genuinely low; a narrow one means it stays nearer rated whatever the room is doing, so the naive multiplication is closer to right on that unit.
Turning input power into a bill is arithmetic, and it needs runtime, room count and the tariff alongside the figure. The aircon running cost tool does that sum. This page settles which nameplate number belongs in it. The label states factory condition, so servicing keeps a machine near its published ratio and neglect walks it away.
Ask for both figures before signing anything. A quote naming a capacity and no input has described what the machine does to a room and said nothing about what it costs. Both numbers are printed on the same sheet, and the one left off is never the flattering one.