On this page
Quick summary
A flashing Toshiba display means the unit has stored a two-character check code, which the remote controller's service mode shows. Sensor codes such as 0C and 0D let the unit keep running. Serial, outdoor and compressor codes stop the outdoor unit while the indoor fan can keep blowing.
What Each Toshiba Indicator Lamp Does
Most Toshiba wall units in Singapore carry an operation lamp, a timer lamp and a pre-defrost or fan-only lamp. The remote controller holds the check-code display. Lamp layout varies by model, so confirm it in the manual before reading a fault from it.
| Lamp | Role | Fault relevance |
|---|---|---|
| Operation lamp or display | Run status and service-mode display | Flashes when a check code is stored |
| Timer lamp | Timer and sleep status | Supports the service-mode display |
| Pre-defrost or fan-only lamp | Defrost and fan-only states | Normal on heat-pump models during defrost |
| Remote controller display | Shows the two-character check code | Read through remote-controller service mode |
Normal Toshiba Lamp Behaviour and Protection States
The display flashes when a fault is detected, and the check code is held for service mode. Behaviour differs by code. Codes 0C and 0D let operation continue. Code 1B may continue. Code 04 stops the outdoor unit while the indoor unit keeps running.
Code 11 turns off all indoor indicators and flashes the display. Code 21 flashes after repeated detection, and the outdoor unit resumes only when the return signal is normal.
Two patterns are not faults: test operation in progress, and a cooling or heating setting the model cannot accept.
Toshiba Fault Patterns and the Check Codes
Every Toshiba residential fault is a two-character check code. The table groups the common ones by the part that reports them; the Toshiba error code list covers the full set. A code names the circuit to test. The failed component is confirmed by measurement.
| Code | What it means | Unit behaviour |
|---|---|---|
| 0C | TA room temperature sensor short or disconnected | Operation continues, display flashes |
| 0D | TC indoor coil sensor out of place or faulty | Operation continues, display flashes |
| 11 | Indoor fan motor failure or fan circuit fault | All indoor indicators turn off, display flashes |
| 12 | Other indoor board fault | Behaviour depends on the cause |
| 04 | Serial signal or connecting cable fault | Indoor unit continues, outdoor unit stops |
| 07 | Outdoor return signal stopped | Indoor unit may continue, outdoor unit stops |
| 18 | Outdoor TE or TS sensor fault | Outdoor unit stops, display flashes |
| 1A | Outdoor fan failure or drive fault | Outdoor unit stops, display flashes |
| 1B | TO outdoor temperature sensor fault | Operation may continue |
| 1C | Compressor drive output fault | Outdoor unit stops, display flashes |
| 1E | Discharge temperature exceeded the limit | Outdoor unit stops, display flashes |
| 21 | Outdoor return signal stopped repeatedly | Outdoor resumes when the signal is normal |
How to Retrieve a Toshiba Check Code
Use the remote-controller service mode in the unit's manual to display the stored code. It appears on the remote while the indoor display flashes. Write both characters down first.
If no code can be read, record which lamps flash. On a multi-split, read each indoor unit in turn, since different heads can store different codes.
Toshiba Multi-Split Systems and Shared Faults
YouMe 2.0 multi-splits run several indoor units from one outdoor unit. All heads flashing together points to the shared outdoor unit or the serial link. One head flashing while the rest cool normally points to that unit: 0C or 0D for its sensors, 11 or 12 for its fan or board.
Some outdoor faults leave the indoor fans blowing. A room can then seem to cool while the system carries a fault or the outdoor unit has stopped.