On this page
How This Presents
Meeting-zone ceiling unit in an Orchard office sheds cold drops from one discharge vane onto desks each humid afternoon. The office manager expects a dead condensate pump because no error light is flashing.
- Setup
- Fujitsu Cassette7-9 yearsOfficeOrchard
- Misread as
- Replacing a cassette condensate pump or patching a suspected cracked drain pan.
- Check first
- Inspecting the drain tray level and pump discharge before testing louver airflow

What Else Produces This
Cassette drips divide cleanly between overflowing drain pans and external surface condensation. Checking water depth inside the tray alongside vane temperatures separates a drainage repair from an airflow fix.
Opening the intake grille and checking the drain pan shows low standing water with the condensate pump cycling briskly on test pour.
Foam backing along the pan lip stays completely dry, ruling out a cracked tray or overflowing corner seam.
Airflow out of the dripping louver slot feels noticeably sluggish compared against the three drier sides.
Dust film across the corresponding coil quadrant chills the supply throat below 14°C while humid corridor air enters through nearby glass doors.
Why It Happens
Restricted airflow through one dirty section of the Fujitsu coil slows cold air across that discharge vane, dropping the plastic louver below the office dew point. Whenever staff open the corridor doors in Singapore's afternoon humidity, warm moist air strikes the chilled louver and beads into drops.
What Resolution Involves
Leave the working drain pump and pan alone. Chemically wash the indoor coil evenly across all four faces, wipe and dry the louver blades, verify the foam gasket seals around the discharge neck, and keep the vanes angled for clear horizontal throw.
How to Tell It Worked
Run the office cassette for forty-five minutes at 23°C on medium fan after cleaning. All four outlets should feel evenly balanced and the formerly wet louver blade should remain completely dry to the touch.
Before You Approve a Quote
Water on a cassette vane is not always a blocked drain
- Clear droplets clinging along an office cassette louver point to dew-point condensation when humid air meets an over-chilled plastic blade.
- A dry drain tray and active float switch prove the condensate pump is doing its job and should stay untouched.
- Washing the fouled coil quadrant and setting louvers to horizontal sweep restores velocity so room moisture stops condensing on the grille.