Haier Aircon 24 Error Code
Confirm the listed meaning of Haier 24, note the unit that shows the code and its model, and match the service manual before diagnosis. Match the model first; same-looking codes can point to different rows.
What does Haier 24 mean?
Haier 24 is listed as compressor startup failure, discharge-pipe restriction or refrigerant shortage, and module heat sensor Th failure in the S2 R32 split-system outdoor unit, FlexFit Pro large cassette, MRV5 AV08-AV26IMVEVA - outdoor failure table, 2024 1U90-1U160 S2 outdoor units, and 2024 3U / 4U / 5U S2 multi-split outdoor units fault lists. This meaning comes from the manufacturer's own diagnostic material. Do not collapse this code across model families; use the model, series, or system type to choose the right row. Confirm the exact model, series, or signal row before accepting a parts quote.
What to do now
Use these steps to record evidence and match the installed model to its service manual before diagnosis or a repair quote.
Record 24 and match the service manual
Record 24 and stop there; the manufacturer gives no customer reset procedure. Arrange diagnosis with the matching service manual.
No manufacturer reset steps listed for 24
Capture the complete 24 error code and model stickers first. The manufacturer lists the meaning but no customer reset procedure; do not treat a generic power-cycle as manufacturer guidance.
Send these to us
24 error code, a clear display photo, Haier indoor and outdoor model stickers, the controller, gateway, or unit that reported the code, operating mode and affected area, and any power or setting changes made after the code appeared
Choose the listing that matches your unit
The same code has more than one listed meaning. Match the model family, the system type and the unit that shows the code before approving parts.
| Code | What it means | What to check first |
|---|---|---|
| S2 R32 split-system outdoor unit / 2024 1U90-1U160 S2 outdoor units / 2024 3U / 4U / 5U S2 multi-split outdoor units | Compressor startup failure | Match this meaning to your installed model and the unit that shows the code, then use the checks below. |
| FlexFit Pro large cassette | Discharge-pipe restriction or refrigerant shortage | Match this meaning to your installed model and the unit that shows the code, then use the checks below. |
| MRV5 AV08-AV26IMVEVA - outdoor failure table — Module heat sensor Th failure | Module heat sensor Th failure | Match this meaning to your installed model and the unit that shows the code, then use the checks below. |
| MRV5 AV08-AV26IMVEVA - outdoor failure table — Oil temperature sensor Toil1 failure | Oil temperature sensor Toil1 failure | Match this meaning to your installed model and the unit that shows the code, then use the checks below. |
| MRV5 AV08-AV26IMVEVA - outdoor failure table — Oil temperature sensor Toil2 failure | Oil temperature sensor Toil2 failure | Match this meaning to your installed model and the unit that shows the code, then use the checks below. |
- Code
- S2 R32 split-system outdoor unit / 2024 1U90-1U160 S2 outdoor units / 2024 3U / 4U / 5U S2 multi-split outdoor units
- What it means
- Compressor startup failure
- What to check first
- Match this meaning to your installed model and the unit that shows the code, then use the checks below.
- Code
- FlexFit Pro large cassette
- What it means
- Discharge-pipe restriction or refrigerant shortage
- What to check first
- Match this meaning to your installed model and the unit that shows the code, then use the checks below.
- Code
- MRV5 AV08-AV26IMVEVA - outdoor failure table — Module heat sensor Th failure
- What it means
- Module heat sensor Th failure
- What to check first
- Match this meaning to your installed model and the unit that shows the code, then use the checks below.
- Code
- MRV5 AV08-AV26IMVEVA - outdoor failure table — Oil temperature sensor Toil1 failure
- What it means
- Oil temperature sensor Toil1 failure
- What to check first
- Match this meaning to your installed model and the unit that shows the code, then use the checks below.
- Code
- MRV5 AV08-AV26IMVEVA - outdoor failure table — Oil temperature sensor Toil2 failure
- What it means
- Oil temperature sensor Toil2 failure
- What to check first
- Match this meaning to your installed model and the unit that shows the code, then use the checks below.
How this fault may be shown
Match every scope item the source provides—exact model where listed, PCB or panel where listed, and reporting device—before using a displayed value. These manufacturer crosswalks are display evidence, not universal codes or repair instructions.
Multi-Split wired controller YR-E17 / YR-E17ASource-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 16
| Reported by | Shown as |
|---|---|
| Wired controller YR-E17 or YR-E17A | 2C |
- Reported by
- Wired controller YR-E17 or YR-E17A
- Shown as
- 2C
Multi-Split wired controller YR-E16 familySource-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 16
| Reported by | Shown as |
|---|---|
| Wired controller YR-E16, YR-E16A, or YR-E16B | 44 |
- Reported by
- Wired controller YR-E16, YR-E16A, or YR-E16B
- Shown as
- 44
Multi-Split cassette air-conditioner displaySource-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 16
| Reported by | Shown as |
|---|---|
| Cassette air-conditioner display | 2C |
- Reported by
- Cassette air-conditioner display
- Shown as
- 2C
Multi-Split cassette TIMER LED5 / RUNNING LED1Source-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 16
| Reported by | Shown as |
|---|---|
| Cassette unit TIMER LED5 and RUNNING LED1 | LED5 4 / LED1 4 |
- Reported by
- Cassette unit TIMER LED5 and RUNNING LED1
- Shown as
- LED5 4 / LED1 4
Multi-Split ceiling-floor, cassette, or duct LED4 / LED3Source-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 16
| Reported by | Shown as |
|---|---|
| Ceiling-floor, cassette, or duct unit TIMER LED4 and RUNNING LED3 | LED4 4 / LED3 4 |
- Reported by
- Ceiling-floor, cassette, or duct unit TIMER LED4 and RUNNING LED3
- Shown as
- LED4 4 / LED3 4
Multi-Split wall-unit displaySource-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 16
| Reported by | Shown as |
|---|---|
| Wall-unit display | F2 |
- Reported by
- Wall-unit display
- Shown as
- F2
Multi-Split alternate table wired controller YR-E17 / YR-E17ASource-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 18
| Reported by | Shown as |
|---|---|
| Wired controller YR-E17 or YR-E17A | 2C |
- Reported by
- Wired controller YR-E17 or YR-E17A
- Shown as
- 2C
Multi-Split alternate table wired controller YR-E16 familySource-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 18
| Reported by | Shown as |
|---|---|
| Wired controller YR-E16, YR-E16A, or YR-E16B | 44 |
- Reported by
- Wired controller YR-E16, YR-E16A, or YR-E16B
- Shown as
- 44
Multi-Split duct TIMER LED4 / RUNNING LED3Source-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 18
| Reported by | Shown as |
|---|---|
| Duct unit TIMER LED4 and RUNNING LED3 | LED4 4 / LED3 4 |
- Reported by
- Duct unit TIMER LED4 and RUNNING LED3
- Shown as
- LED4 4 / LED3 4
Multi-Split ceiling-floor or cassette TIMER LED6 / RUNNING LED1Source-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 18
| Reported by | Shown as |
|---|---|
| Ceiling-floor or cassette unit TIMER LED6 and RUNNING LED1 | LED6 4 / LED1 4 |
- Reported by
- Ceiling-floor or cassette unit TIMER LED6 and RUNNING LED1
- Shown as
- LED6 4 / LED1 4
Multi-Split panel display on PCB 0151800644PCB 0151800644 · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 18
| Reported by | Shown as |
|---|---|
| Duct, ceiling-floor, or cassette panel display | F24 |
- Reported by
- Duct, ceiling-floor, or cassette panel display
- Shown as
- F24
Split outdoor control board - 1U105 SSModels 1U105S2SS1FA, 1U105S2SS2FA · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 20
| Reported by | Shown as |
|---|---|
| Outdoor control-board diagnostic display | 24 |
- Reported by
- Outdoor control-board diagnostic display
- Shown as
- 24
Split outdoor control board - 1U125 SN / 1U140 SPModels 1U125S2SN1FA, 1U125S2SN1FB, 1U140S2SP1FA, 1U140S2SP1FB · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 20
| Reported by | Shown as |
|---|---|
| Outdoor control-board diagnostic display | 24 |
- Reported by
- Outdoor control-board diagnostic display
- Shown as
- 24
Low-static duct PCB 0151800267 LED4 / LED3PCB 0151800267 · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 21
| Reported by | Shown as |
|---|---|
| Low-static duct TIMER LED4 and RUNNING LED3 | LED4 4 / LED3 4 |
- Reported by
- Low-static duct TIMER LED4 and RUNNING LED3
- Shown as
- LED4 4 / LED3 4
Low/medium-static duct PCB 0151800644 LED4 / LED3PCB 0151800644 · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 21
| Reported by | Shown as |
|---|---|
| Low/medium-static duct TIMER LED4 and RUNNING LED3 | LED4 4 / LED3 4 |
- Reported by
- Low/medium-static duct TIMER LED4 and RUNNING LED3
- Shown as
- LED4 4 / LED3 4
Low/medium-static duct panel on PCB 0151800644PCB 0151800644 · Panels P1B-890IA/D, P1B-1210IA/D · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 21
| Reported by | Shown as |
|---|---|
| Low/medium-static duct panel display | F24 |
- Reported by
- Low/medium-static duct panel display
- Shown as
- F24
AC ceiling/floor TIMER LED6 / RUNNING LED1Models AC35S2SG1FA, AC50S2SG1FA, AC71S2SG1FA, AC90S2SH1FA, AC105S2SH1FA, AC125S2SK1FA, AC140S2SK1FA, AC160S2SK1FA · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 23
| Reported by | Shown as |
|---|---|
| AC ceiling/floor TIMER LED6 and RUNNING LED1 | LED6 4 / LED1 4 |
- Reported by
- AC ceiling/floor TIMER LED6 and RUNNING LED1
- Shown as
- LED6 4 / LED1 4
AC ceiling/floor displayModels AC35S2SG1FA, AC50S2SG1FA, AC71S2SG1FA, AC90S2SH1FA, AC105S2SH1FA, AC125S2SK1FA, AC140S2SK1FA, AC160S2SK1FA · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 23
| Reported by | Shown as |
|---|---|
| AC ceiling/floor display | F24 |
- Reported by
- AC ceiling/floor display
- Shown as
- F24
AF floor TIMER LED6 / RUNNING LED1Models AF25S2SD1FA, AF35S2SD1FA, AF42S2SD1FA · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 24
| Reported by | Shown as |
|---|---|
| AF floor TIMER LED6 and RUNNING LED1 | LED6 4 / LED1 4 |
- Reported by
- AF floor TIMER LED6 and RUNNING LED1
- Shown as
- LED6 4 / LED1 4
AF floor displayModels AF25S2SD1FA, AF35S2SD1FA, AF42S2SD1FA · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 24
| Reported by | Shown as |
|---|---|
| AF floor display | F24 |
- Reported by
- AF floor display
- Shown as
- F24
Source-labelled cassette TIMER / RUNNING LEDsSource-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 25
| Reported by | Shown as |
|---|---|
| Cassette TIMER and RUNNING LEDs | TIMER 4 / RUNNING 4 |
- Reported by
- Cassette TIMER and RUNNING LEDs
- Shown as
- TIMER 4 / RUNNING 4
Source-labelled cassette displaySource-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 25
| Reported by | Shown as |
|---|---|
| Cassette display | 2C |
- Reported by
- Cassette display
- Shown as
- 2C
Guidance for your model
Notes that match the code to your exact model. Electrical, refrigerant, wiring, resistance and component checks are for a technician.
| Detail | What it says |
|---|---|
| Singapore / model note | Official Haier Australia S2 split-system manual row. Confirm the exact 1U S2 outdoor model before using the meaning; no universal Haier-model parity is claimed. |
| Singapore / model note | Official Haier Appliances FlexFit Pro large-cassette display decoder. The source converts an outdoor decimal fault to the hexadecimal code flashed indoors; the exact display identity is retained. Match the named model family before diagnosis. |
| Singapore / model note | Official regional Haier MRV5 row from outdoor-unit manual 0150525031. Confirm an AV08IMVEVA through AV26IMVEVA system, which unit shows the code, and the complete suffix. The source does not enumerate connected indoor models and is not claimed to cover every Haier system or establish universal Singapore-model parity. |
- Detail
- Singapore / model note
- What it says
- Official Haier Australia S2 split-system manual row. Confirm the exact 1U S2 outdoor model before using the meaning; no universal Haier-model parity is claimed.
- Detail
- Singapore / model note
- What it says
- Official Haier Appliances FlexFit Pro large-cassette display decoder. The source converts an outdoor decimal fault to the hexadecimal code flashed indoors; the exact display identity is retained. Match the named model family before diagnosis.
- Detail
- Singapore / model note
- What it says
- Official regional Haier MRV5 row from outdoor-unit manual 0150525031. Confirm an AV08IMVEVA through AV26IMVEVA system, which unit shows the code, and the complete suffix. The source does not enumerate connected indoor models and is not claimed to cover every Haier system or establish universal Singapore-model parity.
What to check before repair
The manufacturer's fault table gives the code's meaning, not a repair procedure. Capture evidence first; model-specific tests belong to the matching service manual.
| You can check | Technician should confirm |
|---|---|
| Photograph the complete 24 error code before taking any action. | Confirm 24 exactly and record which controller, gateway, or unit reported it. |
| Capture the Haier indoor and outdoor model stickers and identify which controller or unit reported it. | Match the indoor and outdoor model stickers, installed family, and reporting equipment to the source scope. |
| The manufacturer provides no customer reset procedure. Preserve the evidence and use the matching service manual for any system action. | Follow the matching service-manual procedure and keep measured test evidence before naming a failed part. |
- You can check
- Photograph the complete 24 error code before taking any action.
- Technician should confirm
- Confirm 24 exactly and record which controller, gateway, or unit reported it.
- You can check
- Capture the Haier indoor and outdoor model stickers and identify which controller or unit reported it.
- Technician should confirm
- Match the indoor and outdoor model stickers, installed family, and reporting equipment to the source scope.
- You can check
- The manufacturer provides no customer reset procedure. Preserve the evidence and use the matching service manual for any system action.
- Technician should confirm
- Follow the matching service-manual procedure and keep measured test evidence before naming a failed part.
Source-bounded repair decision
Haier 24 confirms the fault label the manufacturer lists, not a failed part or repair procedure. Match the installed model to its service manual and require measured diagnostic evidence before approving parts, settings, or refrigerant work.
Whether the reporting controller or unit and exact installed model are confirmed.
What the matching service-manual procedure and measured tests show.
Whether the proposed repair names the evidence for the failed part or condition.
Haier 24 questions
What does the Haier 24 error mean?
Can I fix a Haier 24 error myself?
Is it safe to keep running the aircon with a 24 error?
What causes a Haier 24 error?
Will a Haier 24 error need a repair or a full replacement?
What should I send a technician about a Haier 24 error?
Where to go next
Confirm the fault
Share the error code, model number and symptoms so we can assess the likely cause.
Not the right code?
Browse the full Haier list or check a few codes in the same fault category.
Read next
Use this quote-check guide only after the matching service manual identifies the diagnostic path.