Haier Aircon 25 Error Code & Blinking Light

Confirm the listed meaning of Haier 25, note the unit that shows the code and its model, and match the service manual before diagnosis. Match the model first; same-looking signals can point to different rows.

What does Haier 25 mean?

Haier 25 is listed as compressor drive-module input overcurrent, four-way valve reversing abnormality, and heat-exchanger inlet temperature sensor Toci1 failure in the S2 R32 split-system outdoor unit, FlexFit Pro large cassette, MRV5 AV08-AV26IMVEVA - outdoor failure table, 2024 1U71 S2 SG / SR outdoor units, 2024 1U90-1U160 S2 outdoor units, and 2024 3U / 4U / 5U S2 multi-split outdoor units fault lists. This meaning comes from the manufacturer's own diagnostic material. Do not collapse this code across model families; use the model, series, or system type to choose the right row. Confirm the exact model, series, or signal row before accepting a parts quote.

What to do now

Use these steps to record evidence and match the installed model to its service manual before diagnosis or a repair quote.

  • Record 25 and match the service manual

    Record 25 and stop there; the manufacturer gives no customer reset procedure. Arrange diagnosis with the matching service manual.

  • No manufacturer reset steps listed for 25

    Capture the complete 25 error code and blinking light and model stickers first. The manufacturer lists the meaning but no customer reset procedure; do not treat a generic power-cycle as manufacturer guidance.

  • Send these to us

    25 error code and blinking light, a clear display photo and blinking-light video if the unit shows one, Haier indoor and outdoor model stickers, the controller, gateway, or unit that reported the code, operating mode and affected area, and any power or setting changes made after the code appeared

Choose the listing that matches your unit

The same code has more than one listed meaning. Match the model family, the system type and the unit that shows the code before approving parts.

  • Code
    S2 R32 split-system outdoor unit
    What it means
    Compressor drive-module input overcurrent
    What to check first
    Match this meaning to your installed model and the unit that shows the code, then use the checks below.
  • Code
    FlexFit Pro large cassette
    What it means
    Four-way valve reversing abnormality
    What to check first
    Match this meaning to your installed model and the unit that shows the code, then use the checks below.
  • Code
    MRV5 AV08-AV26IMVEVA - outdoor failure table
    What it means
    Heat-exchanger inlet temperature sensor Toci1 failure
    What to check first
    Match this meaning to your installed model and the unit that shows the code, then use the checks below.
  • Code
    2024 1U71 S2 SG / SR outdoor units — Compressor U-phase overcurrent. Shown as: outdoor PCB LED: 25 flashes.
    What it means
    Compressor U-phase overcurrent. Shown as: outdoor PCB LED: 25 flashes.
    What to check first
    Match this meaning to your installed model and the unit that shows the code, then use the checks below.
  • Code
    2024 1U71 S2 SG / SR outdoor units — Compressor V-phase overcurrent. Shown as: outdoor PCB LED: 25 flashes.
    What it means
    Compressor V-phase overcurrent. Shown as: outdoor PCB LED: 25 flashes.
    What to check first
    Match this meaning to your installed model and the unit that shows the code, then use the checks below.
  • Code
    2024 1U71 S2 SG / SR outdoor units — Compressor W-phase overcurrent. Shown as: outdoor PCB LED: 25 flashes.
    What it means
    Compressor W-phase overcurrent. Shown as: outdoor PCB LED: 25 flashes.
    What to check first
    Match this meaning to your installed model and the unit that shows the code, then use the checks below.
  • Code
    2024 1U90-1U160 S2 outdoor units
    What it means
    Compressor driver-module input overcurrent
    What to check first
    Match this meaning to your installed model and the unit that shows the code, then use the checks below.
  • Code
    2024 3U / 4U / 5U S2 multi-split outdoor units
    What it means
    Power-module input overcurrent
    What to check first
    Match this meaning to your installed model and the unit that shows the code, then use the checks below.

How this fault may be shown

Match every scope item the source provides—exact model where listed, PCB or panel where listed, and reporting device—before using a displayed value. These manufacturer crosswalks are display evidence, not universal codes or repair instructions.

Multi-Split wired controller YR-E17 / YR-E17ASource-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 16
  • Reported by
    Wired controller YR-E17 or YR-E17A
    Shown as
    2D
    Listed meaning
    Power-module input overcurrent
Multi-Split wired controller YR-E16 familySource-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 16
  • Reported by
    Wired controller YR-E16, YR-E16A, or YR-E16B
    Shown as
    45
    Listed meaning
    Power-module input overcurrent
Multi-Split cassette air-conditioner displaySource-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 16
  • Reported by
    Cassette air-conditioner display
    Shown as
    2D
    Listed meaning
    Power-module input overcurrent
Multi-Split cassette TIMER LED5 / RUNNING LED1Source-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 16
  • Reported by
    Cassette unit TIMER LED5 and RUNNING LED1
    Shown as
    LED5 4 / LED1 5
    Listed meaning
    Power-module input overcurrent
Multi-Split ceiling-floor, cassette, or duct LED4 / LED3Source-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 16
  • Reported by
    Ceiling-floor, cassette, or duct unit TIMER LED4 and RUNNING LED3
    Shown as
    LED4 4 / LED3 5
    Listed meaning
    Power-module input overcurrent
Multi-Split wall-unit displaySource-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 16
  • Reported by
    Wall-unit display
    Shown as
    F23
    Listed meaning
    Power-module input overcurrent
Multi-Split alternate table wired controller YR-E17 / YR-E17ASource-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 18
  • Reported by
    Wired controller YR-E17 or YR-E17A
    Shown as
    2D
    Listed meaning
    Power-module input overcurrent
Multi-Split alternate table wired controller YR-E16 familySource-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 18
  • Reported by
    Wired controller YR-E16, YR-E16A, or YR-E16B
    Shown as
    45
    Listed meaning
    Power-module input overcurrent
Multi-Split duct TIMER LED4 / RUNNING LED3Source-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 18
  • Reported by
    Duct unit TIMER LED4 and RUNNING LED3
    Shown as
    LED4 4 / LED3 5
    Listed meaning
    Power-module input overcurrent
Multi-Split ceiling-floor or cassette TIMER LED6 / RUNNING LED1Source-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 18
  • Reported by
    Ceiling-floor or cassette unit TIMER LED6 and RUNNING LED1
    Shown as
    LED6 4 / LED1 5
    Listed meaning
    Power-module input overcurrent
Multi-Split panel display on PCB 0151800644PCB 0151800644 · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 18
  • Reported by
    Duct, ceiling-floor, or cassette panel display
    Shown as
    F25
    Listed meaning
    Power-module input overcurrent
Split outdoor control board - 1U71 SG / SRModels 1U71S2SG1FA, 1U71S2SR2FA · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 20
  • Reported by
    Outdoor control-board diagnostic display
    Shown as
    25
    Listed meaning
    Compressor U-phase overcurrent
  • Reported by
    Outdoor control-board diagnostic display
    Shown as
    25
    Listed meaning
    Compressor V-phase overcurrent
  • Reported by
    Outdoor control-board diagnostic display
    Shown as
    25
    Listed meaning
    Compressor W-phase overcurrent
Split outdoor control board - 1U105 SSModels 1U105S2SS1FA, 1U105S2SS2FA · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 20
  • Reported by
    Outdoor control-board diagnostic display
    Shown as
    25
    Listed meaning
    Driver-module input overcurrent
Split outdoor control board - 1U125 SN / 1U140 SPModels 1U125S2SN1FA, 1U125S2SN1FB, 1U140S2SP1FA, 1U140S2SP1FB · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 20
  • Reported by
    Outdoor control-board diagnostic display
    Shown as
    25
    Listed meaning
    Driver-module input overcurrent
Low-static duct PCB 0151800267 LED4 / LED3PCB 0151800267 · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 21
  • Reported by
    Low-static duct TIMER LED4 and RUNNING LED3
    Shown as
    LED4 4 / LED3 5
    Listed meaning
    Compressor U-phase overcurrent
  • Reported by
    Low-static duct TIMER LED4 and RUNNING LED3
    Shown as
    LED4 4 / LED3 5
    Listed meaning
    Compressor V-phase overcurrent
  • Reported by
    Low-static duct TIMER LED4 and RUNNING LED3
    Shown as
    LED4 4 / LED3 5
    Listed meaning
    Compressor W-phase overcurrent
  • Reported by
    Low-static duct TIMER LED4 and RUNNING LED3
    Shown as
    LED4 4 / LED3 5
    Listed meaning
    Driver-module input overcurrent
Low/medium-static duct PCB 0151800644 LED4 / LED3PCB 0151800644 · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 21
  • Reported by
    Low/medium-static duct TIMER LED4 and RUNNING LED3
    Shown as
    LED4 4 / LED3 5
    Listed meaning
    Compressor U-phase overcurrent
  • Reported by
    Low/medium-static duct TIMER LED4 and RUNNING LED3
    Shown as
    LED4 4 / LED3 5
    Listed meaning
    Compressor V-phase overcurrent
  • Reported by
    Low/medium-static duct TIMER LED4 and RUNNING LED3
    Shown as
    LED4 4 / LED3 5
    Listed meaning
    Compressor W-phase overcurrent
  • Reported by
    Low/medium-static duct TIMER LED4 and RUNNING LED3
    Shown as
    LED4 4 / LED3 5
    Listed meaning
    Driver-module input overcurrent
Low/medium-static duct panel on PCB 0151800644PCB 0151800644 · Panels P1B-890IA/D, P1B-1210IA/D · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 21
  • Reported by
    Low/medium-static duct panel display
    Shown as
    F25
    Listed meaning
    Compressor U-phase overcurrent
  • Reported by
    Low/medium-static duct panel display
    Shown as
    F25
    Listed meaning
    Compressor V-phase overcurrent
  • Reported by
    Low/medium-static duct panel display
    Shown as
    F25
    Listed meaning
    Compressor W-phase overcurrent
  • Reported by
    Low/medium-static duct panel display
    Shown as
    F25
    Listed meaning
    Driver-module input overcurrent
AC ceiling/floor TIMER LED6 / RUNNING LED1Models AC35S2SG1FA, AC50S2SG1FA, AC71S2SG1FA, AC90S2SH1FA, AC105S2SH1FA, AC125S2SK1FA, AC140S2SK1FA, AC160S2SK1FA · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 23
  • Reported by
    AC ceiling/floor TIMER LED6 and RUNNING LED1
    Shown as
    LED6 4 / LED1 5
    Listed meaning
    Compressor U-phase overcurrent
  • Reported by
    AC ceiling/floor TIMER LED6 and RUNNING LED1
    Shown as
    LED6 4 / LED1 5
    Listed meaning
    Compressor V-phase overcurrent
  • Reported by
    AC ceiling/floor TIMER LED6 and RUNNING LED1
    Shown as
    LED6 4 / LED1 5
    Listed meaning
    Compressor W-phase overcurrent
  • Reported by
    AC ceiling/floor TIMER LED6 and RUNNING LED1
    Shown as
    LED6 4 / LED1 5
    Listed meaning
    Driver-module input overcurrent
AC ceiling/floor displayModels AC35S2SG1FA, AC50S2SG1FA, AC71S2SG1FA, AC90S2SH1FA, AC105S2SH1FA, AC125S2SK1FA, AC140S2SK1FA, AC160S2SK1FA · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 23
  • Reported by
    AC ceiling/floor display
    Shown as
    F25
    Listed meaning
    Compressor U-phase overcurrent
  • Reported by
    AC ceiling/floor display
    Shown as
    F25
    Listed meaning
    Compressor V-phase overcurrent
  • Reported by
    AC ceiling/floor display
    Shown as
    F25
    Listed meaning
    Compressor W-phase overcurrent
  • Reported by
    AC ceiling/floor display
    Shown as
    F25
    Listed meaning
    Driver-module input overcurrent
AF floor TIMER LED6 / RUNNING LED1Models AF25S2SD1FA, AF35S2SD1FA, AF42S2SD1FA · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 24
  • Reported by
    AF floor TIMER LED6 and RUNNING LED1
    Shown as
    LED6 4 / LED1 5
    Listed meaning
    Compressor U-phase overcurrent
  • Reported by
    AF floor TIMER LED6 and RUNNING LED1
    Shown as
    LED6 4 / LED1 5
    Listed meaning
    Compressor V-phase overcurrent
  • Reported by
    AF floor TIMER LED6 and RUNNING LED1
    Shown as
    LED6 4 / LED1 5
    Listed meaning
    Compressor W-phase overcurrent
  • Reported by
    AF floor TIMER LED6 and RUNNING LED1
    Shown as
    LED6 4 / LED1 5
    Listed meaning
    Driver-module input overcurrent
AF floor displayModels AF25S2SD1FA, AF35S2SD1FA, AF42S2SD1FA · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 24
  • Reported by
    AF floor display
    Shown as
    F25
    Listed meaning
    Compressor U-phase overcurrent
  • Reported by
    AF floor display
    Shown as
    F25
    Listed meaning
    Compressor V-phase overcurrent
  • Reported by
    AF floor display
    Shown as
    F25
    Listed meaning
    Compressor W-phase overcurrent
  • Reported by
    AF floor display
    Shown as
    F25
    Listed meaning
    Driver-module input overcurrent
Source-labelled cassette TIMER / RUNNING LEDsSource-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 25
  • Reported by
    Cassette TIMER and RUNNING LEDs
    Shown as
    TIMER 4 / RUNNING 5
    Listed meaning
    Compressor U-phase overcurrent
  • Reported by
    Cassette TIMER and RUNNING LEDs
    Shown as
    TIMER 4 / RUNNING 5
    Listed meaning
    Compressor V-phase overcurrent
  • Reported by
    Cassette TIMER and RUNNING LEDs
    Shown as
    TIMER 4 / RUNNING 5
    Listed meaning
    Compressor W-phase overcurrent
  • Reported by
    Cassette TIMER and RUNNING LEDs
    Shown as
    TIMER 4 / RUNNING 5
    Listed meaning
    Driver-module input overcurrent
Source-labelled cassette displaySource-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 25
  • Reported by
    Cassette display
    Shown as
    2D
    Listed meaning
    Compressor U-phase overcurrent
  • Reported by
    Cassette display
    Shown as
    2D
    Listed meaning
    Compressor V-phase overcurrent
  • Reported by
    Cassette display
    Shown as
    2D
    Listed meaning
    Compressor W-phase overcurrent
  • Reported by
    Cassette display
    Shown as
    2D
    Listed meaning
    Driver-module input overcurrent

Guidance for your model

Notes that match the code to your exact model. Electrical, refrigerant, wiring, resistance and component checks are for a technician.

  • Detail
    Singapore / model note
    What it says
    Official Haier Australia S2 split-system manual row. Confirm the exact 1U S2 outdoor model before using the meaning; no universal Haier-model parity is claimed.
  • Detail
    Singapore / model note
    What it says
    Official Haier Appliances FlexFit Pro large-cassette display decoder. The source converts an outdoor decimal fault to the hexadecimal code flashed indoors; the exact display identity is retained. Match the named model family before diagnosis.
  • Detail
    Singapore / model note
    What it says
    Official regional Haier MRV5 row from outdoor-unit manual 0150525031. Confirm an AV08IMVEVA through AV26IMVEVA system, which unit shows the code, and the complete suffix. The source does not enumerate connected indoor models and is not claimed to cover every Haier system or establish universal Singapore-model parity.

What to check before repair

The manufacturer's fault table gives the code's meaning, not a repair procedure. Capture evidence first; model-specific tests belong to the matching service manual.

  • You can check
    Photograph the complete 25 error code and blinking light before taking any action.
    Technician should confirm
    Confirm 25 exactly and record which controller, gateway, or unit reported it.
  • You can check
    Capture the Haier indoor and outdoor model stickers and identify which controller or unit reported it.
    Technician should confirm
    Match the indoor and outdoor model stickers, installed family, and reporting equipment to the source scope.
  • You can check
    The manufacturer provides no customer reset procedure. Preserve the evidence and use the matching service manual for any system action.
    Technician should confirm
    Follow the matching service-manual procedure and keep measured test evidence before naming a failed part.

Source-bounded repair decision

Haier 25 confirms the fault label the manufacturer lists, not a failed part or repair procedure. Match the installed model to its service manual and require measured diagnostic evidence before approving parts, settings, or refrigerant work.

  • Whether the reporting controller or unit and exact installed model are confirmed.

  • What the matching service-manual procedure and measured tests show.

  • Whether the proposed repair names the evidence for the failed part or condition.

Haier 25 questions

What does the Haier 25 error mean?
Haier 25 is listed as compressor drive-module input overcurrent, four-way valve reversing abnormality, and heat-exchanger inlet temperature sensor Toci1 failure in the S2 R32 split-system outdoor unit, FlexFit Pro large cassette, MRV5 AV08-AV26IMVEVA - outdoor failure table, 2024 1U71 S2 SG / SR outdoor units, 2024 1U90-1U160 S2 outdoor units, and 2024 3U / 4U / 5U S2 multi-split outdoor units fault lists. This meaning comes from the manufacturer's own diagnostic material. Do not collapse this code across model families; use the model, series, or system type to choose the right row. Confirm the exact model, series, or signal row before accepting a parts quote.
Can I fix a Haier 25 error myself?
No. 25 needs a technician's measurement before parts are decided. Photograph the complete 25 error code and blinking light before taking any action. Capture the Haier indoor and outdoor model stickers and identify which controller or unit reported it.
Is it safe to keep running the aircon with a 25 error?
Record 25 and stop there; the manufacturer gives no customer reset procedure. Arrange diagnosis with the matching service manual.
What causes a Haier 25 error?
Haier 25 has a listed meaning that depends on the exact model and on which unit shows the code. Use the decoder on this page before assuming a specific cause.
Will a Haier 25 error need a repair or a full replacement?
Haier 25 confirms the fault label the manufacturer lists, not a failed part or repair procedure. Match the installed model to its service manual and require measured diagnostic evidence before approving parts, settings, or refrigerant work.
What should I send a technician about a Haier 25 error?
Before booking, send: 25 error code and blinking light, a clear display photo and blinking-light video if the unit shows one, Haier indoor and outdoor model stickers, the controller, gateway, or unit that reported the code, operating mode and affected area, and any power or setting changes made after the code appeared.