Skip to main content
snowflakeaircon.sg

Haier Aircon 27 Error Code

Use this Haier 27 error code guide to confirm the source table meaning, capture the reporting equipment and model, and match the service manual before diagnosis. Match the model first; same-looking codes can point to different rows.

What does Haier 27 mean?

Haier 27 is listed as drive-module input-current sampling-circuit fault, oil temperature Toil1 too-high protection, and oil temperature Toil2 too-high protection in S2 R32 split-system outdoor unit, MRV5 AV08-AV26IMVEVA - outdoor failure table, 2024 1U90-1U160 S2 outdoor units, and 2024 3U / 4U / 5U S2 multi-split outdoor units source rows. The loaded row is source-backed by official diagnostic material. Do not collapse this code across model families; use the model, series, or system type to choose the right row. Confirm the exact model, series, or signal row before accepting a parts quote.

Choose the matching source row

The same visible code has more than one source-backed meaning. Match the model family, system type, or reporting unit before approving parts.

  • Code
    S2 R32 split-system outdoor unit
    What it means
    Drive-module input-current sampling-circuit fault
    What to check first
    Match this row to the installed model or reporting unit, then use the source-specific checks below.
  • Code
    MRV5 AV08-AV26IMVEVA - outdoor failure table — Oil temperature Toil1 too-high protection
    What it means
    Oil temperature Toil1 too-high protection
    What to check first
    Match this row to the installed model or reporting unit, then use the source-specific checks below.
  • Code
    MRV5 AV08-AV26IMVEVA - outdoor failure table — Oil temperature Toil2 too-high protection
    What it means
    Oil temperature Toil2 too-high protection
    What to check first
    Match this row to the installed model or reporting unit, then use the source-specific checks below.
  • Code
    2024 1U90-1U160 S2 outdoor units
    What it means
    Driver-module input-current sampling-circuit failure
    What to check first
    Match this row to the installed model or reporting unit, then use the source-specific checks below.
  • Code
    2024 3U / 4U / 5U S2 multi-split outdoor units
    What it means
    Power-module current-detection circuit failure
    What to check first
    Match this row to the installed model or reporting unit, then use the source-specific checks below.

How this fault may be shown

Match every scope item the source provides—exact model where listed, PCB or panel where listed, and reporting device—before using a displayed value. These manufacturer crosswalks are display evidence, not universal codes or repair instructions.

Multi-Split wired controller YR-E17 / YR-E17ASource-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 16
  • Reported by
    Wired controller YR-E17 or YR-E17A
    Shown as
    2F
    Source meaning
    Power-module current-detection circuit failure
Multi-Split wired controller YR-E16 familySource-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 16
  • Reported by
    Wired controller YR-E16, YR-E16A, or YR-E16B
    Shown as
    47
    Source meaning
    Power-module current-detection circuit failure
Multi-Split cassette air-conditioner displaySource-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 16
  • Reported by
    Cassette air-conditioner display
    Shown as
    2F
    Source meaning
    Power-module current-detection circuit failure
Multi-Split cassette TIMER LED5 / RUNNING LED1Source-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 16
  • Reported by
    Cassette unit TIMER LED5 and RUNNING LED1
    Shown as
    LED5 4 / LED1 7
    Source meaning
    Power-module current-detection circuit failure
Multi-Split ceiling-floor, cassette, or duct LED4 / LED3Source-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 16
  • Reported by
    Ceiling-floor, cassette, or duct unit TIMER LED4 and RUNNING LED3
    Shown as
    LED4 4 / LED3 7
    Source meaning
    Power-module current-detection circuit failure
Multi-Split wall-unit displaySource-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 16
  • Reported by
    Wall-unit display
    Shown as
    F24
    Source meaning
    Power-module current-detection circuit failure
Multi-Split alternate table wired controller YR-E17 / YR-E17ASource-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 18
  • Reported by
    Wired controller YR-E17 or YR-E17A
    Shown as
    2F
    Source meaning
    Power-module current-detection circuit failure
Multi-Split alternate table wired controller YR-E16 familySource-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 18
  • Reported by
    Wired controller YR-E16, YR-E16A, or YR-E16B
    Shown as
    47
    Source meaning
    Power-module current-detection circuit failure
Multi-Split duct TIMER LED4 / RUNNING LED3Source-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 18
  • Reported by
    Duct unit TIMER LED4 and RUNNING LED3
    Shown as
    LED4 4 / LED3 7
    Source meaning
    Power-module current-detection circuit failure
Multi-Split ceiling-floor or cassette TIMER LED6 / RUNNING LED1Source-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 18
  • Reported by
    Ceiling-floor or cassette unit TIMER LED6 and RUNNING LED1
    Shown as
    LED6 4 / LED1 7
    Source meaning
    Power-module current-detection circuit failure
Multi-Split panel display on PCB 0151800644PCB 0151800644 · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 18
  • Reported by
    Duct, ceiling-floor, or cassette panel display
    Shown as
    F27
    Source meaning
    Power-module current-detection circuit failure
Split outdoor control board - 1U105 SSModels 1U105S2SS1FA, 1U105S2SS2FA · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 20
  • Reported by
    Outdoor control-board diagnostic display
    Shown as
    27
    Source meaning
    Input-current circuit failure
Split outdoor control board - 1U125 SN / 1U140 SPModels 1U125S2SN1FA, 1U125S2SN1FB, 1U140S2SP1FA, 1U140S2SP1FB · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 20
  • Reported by
    Outdoor control-board diagnostic display
    Shown as
    27
    Source meaning
    Input-current circuit failure
Low-static duct PCB 0151800267 LED4 / LED3PCB 0151800267 · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 22
  • Reported by
    Low-static duct TIMER LED4 and RUNNING LED3
    Shown as
    LED4 4 / LED3 7
    Source meaning
    Input-current circuit failure
Low/medium-static duct PCB 0151800644 LED4 / LED3PCB 0151800644 · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 22
  • Reported by
    Low/medium-static duct TIMER LED4 and RUNNING LED3
    Shown as
    LED4 4 / LED3 7
    Source meaning
    Input-current circuit failure
Low/medium-static duct panel on PCB 0151800644PCB 0151800644 · Panels P1B-890IA/D, P1B-1210IA/D · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 22
  • Reported by
    Low/medium-static duct panel display
    Shown as
    F27
    Source meaning
    Input-current circuit failure
AC ceiling/floor TIMER LED6 / RUNNING LED1Models AC35S2SG1FA, AC50S2SG1FA, AC71S2SG1FA, AC90S2SH1FA, AC105S2SH1FA, AC125S2SK1FA, AC140S2SK1FA, AC160S2SK1FA · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 23
  • Reported by
    AC ceiling/floor TIMER LED6 and RUNNING LED1
    Shown as
    LED6 4 / LED1 7
    Source meaning
    Input-current circuit failure
AC ceiling/floor displayModels AC35S2SG1FA, AC50S2SG1FA, AC71S2SG1FA, AC90S2SH1FA, AC105S2SH1FA, AC125S2SK1FA, AC140S2SK1FA, AC160S2SK1FA · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 23
  • Reported by
    AC ceiling/floor display
    Shown as
    F27
    Source meaning
    Input-current circuit failure
AF floor TIMER LED6 / RUNNING LED1Models AF25S2SD1FA, AF35S2SD1FA, AF42S2SD1FA · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 24
  • Reported by
    AF floor TIMER LED6 and RUNNING LED1
    Shown as
    LED6 4 / LED1 7
    Source meaning
    Input-current circuit failure
AF floor displayModels AF25S2SD1FA, AF35S2SD1FA, AF42S2SD1FA · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 24
  • Reported by
    AF floor display
    Shown as
    F27
    Source meaning
    Input-current circuit failure
Source-labelled cassette TIMER / RUNNING LEDsSource-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 25
  • Reported by
    Cassette TIMER and RUNNING LEDs
    Shown as
    TIMER 4 / RUNNING 7
    Source meaning
    Input-current circuit failure
Source-labelled cassette displaySource-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 25
  • Reported by
    Cassette display
    Shown as
    2F
    Source meaning
    Input-current circuit failure

What to do now

Use these steps to record evidence and match the installed model to its service manual before diagnosis or a repair quote.

  • Record 27 and match the service manual

    Record 27 and stop there; the source table gives no customer reset procedure. Arrange diagnosis with the matching service manual.

  • No manufacturer reset steps listed for 27

    Capture the complete 27 error code and model stickers first. The source table lists the meaning but no customer reset procedure; do not treat a generic power-cycle as manufacturer guidance.

  • Send these to us

    27 error code, a clear display photo, Haier indoor and outdoor model stickers, the controller, gateway, or unit that reported the code, operating mode and affected area, and any power or setting changes made after the code appeared

Source-specific guidance

These diagnostic-reference notes help match the code to the exact model. Electrical, refrigerant, wiring, resistance, and component checks are technician work, not DIY steps.

  • Source detail
    Singapore / model note
    What it says
    Official Haier Australia S2 split-system manual row. Confirm the exact 1U S2 outdoor model before using the meaning; no universal Haier-model parity is claimed.
  • Source detail
    Singapore / model note
    What it says
    Official regional Haier MRV5 row from outdoor-unit manual 0150525031. Confirm an AV08IMVEVA through AV26IMVEVA system, the reporting unit, and the complete suffix. The source does not enumerate connected indoor models and is not claimed to cover every Haier system or establish universal Singapore-model parity.
  • Source detail
    Singapore / model note
    What it says
    Regional manufacturer handbook, PDF page 14. Confirm the exact listed model and reporting display; this meaning is not claimed for every Haier system.

What to check before repair

The source table establishes the code meaning, not a repair procedure. Capture evidence first; model-specific tests belong to the matching service manual.

  • You can check
    Photograph the complete 27 error code before taking any action.
    Technician should confirm
    Confirm 27 exactly and record which controller, gateway, or unit reported it.
  • You can check
    Capture the Haier indoor and outdoor model stickers and identify which controller or unit reported it.
    Technician should confirm
    Match the indoor and outdoor model stickers, installed family, and reporting equipment to the source scope.
  • You can check
    The source table provides no customer reset procedure. Preserve the evidence and use the matching service manual for any system action.
    Technician should confirm
    Follow the matching service-manual procedure and keep measured test evidence before naming a failed part.

Source-bounded repair decision

Haier 27 confirms the source-table fault label, not a failed part or repair procedure. Match the installed model to its service manual and require measured diagnostic evidence before approving parts, settings, or refrigerant work.

  • Whether the reporting controller or unit and exact installed model are confirmed.

  • What the matching service-manual procedure and measured tests show.

  • Whether the proposed repair names the evidence for the failed part or condition.

Haier 27 questions

What does the Haier 27 error mean?
Haier 27 is listed as drive-module input-current sampling-circuit fault, oil temperature Toil1 too-high protection, and oil temperature Toil2 too-high protection in S2 R32 split-system outdoor unit, MRV5 AV08-AV26IMVEVA - outdoor failure table, 2024 1U90-1U160 S2 outdoor units, and 2024 3U / 4U / 5U S2 multi-split outdoor units source rows. The loaded row is source-backed by official diagnostic material. Do not collapse this code across model families; use the model, series, or system type to choose the right row. Confirm the exact model, series, or signal row before accepting a parts quote.
Can I fix a Haier 27 error myself?
No. 27 needs a technician's measurement before parts are decided. Photograph the complete 27 error code before taking any action. Capture the Haier indoor and outdoor model stickers and identify which controller or unit reported it.
Is it safe to keep running the aircon with a 27 error?
Record 27 and stop there; the source table gives no customer reset procedure. Arrange diagnosis with the matching service manual.
What causes a Haier 27 error?
Haier 27 has source-backed wording that depends on the exact model, source row, or reporting unit. Use the decoder on this page before assuming a specific cause.
Will a Haier 27 error need a repair or a full replacement?
Haier 27 confirms the source-table fault label, not a failed part or repair procedure. Match the installed model to its service manual and require measured diagnostic evidence before approving parts, settings, or refrigerant work.
What should I send a technician about a Haier 27 error?
Before booking, send: 27 error code, a clear display photo, Haier indoor and outdoor model stickers, the controller, gateway, or unit that reported the code, operating mode and affected area, and any power or setting changes made after the code appeared.

Confirm the fault

Share the error code, model number and symptoms so we can assess the likely cause.

Not the right code?

Browse the full Haier list or check a few codes in the same fault category.

Ready to get started?

Tell us what’s going on. Symptoms, setup, photos, anything we should know. We’ll assess and come back with the right next step.

WhatsApp us

Read next

Use this quote-check guide only after the matching service manual identifies the diagnostic path.