Haier Aircon 45 Error Code
Confirm the listed meaning of Haier 45, note the unit that shows the code and its model, and match the service manual before diagnosis. Match the model first; same-looking codes can point to different rows.
What does Haier 45 mean?
Haier 45 is listed as system low-pressure protection, communication failure between outdoor units, and low-pressure switch protection in the S2 R32 split-system outdoor unit, MRV5 AV08-AV26IMVEVA - outdoor failure table, 2024 1U90-1U160 S2 outdoor units, and 2024 3U / 4U / 5U S2 multi-split outdoor units fault lists. This meaning comes from the manufacturer's own diagnostic material. Do not collapse this code across model families; use the model, series, or system type to choose the right row. Confirm the exact model, series, or signal row before accepting a parts quote.
What to do now
Use these steps to record evidence and match the installed model to its service manual before diagnosis or a repair quote.
Record 45 and match the service manual
Record 45 and stop there; the manufacturer gives no customer reset procedure. Arrange diagnosis with the matching service manual.
No manufacturer reset steps listed for 45
Capture the complete 45 error code and model stickers first. The manufacturer lists the meaning but no customer reset procedure; do not treat a generic power-cycle as manufacturer guidance.
Send these to us
45 error code, a clear display photo, Haier indoor and outdoor model stickers, the controller, gateway, or unit that reported the code, operating mode and affected area, and any power or setting changes made after the code appeared
Choose the listing that matches your unit
The same code has more than one listed meaning. Match the model family, the system type and the unit that shows the code before approving parts.
| Code | What it means | What to check first |
|---|---|---|
| S2 R32 split-system outdoor unit / 2024 1U90-1U160 S2 outdoor units | System low-pressure protection | Match this meaning to your installed model and the unit that shows the code, then use the checks below. |
| MRV5 AV08-AV26IMVEVA - outdoor failure table | Communication failure between outdoor units | Match this meaning to your installed model and the unit that shows the code, then use the checks below. |
| 2024 3U / 4U / 5U S2 multi-split outdoor units | Low-pressure switch protection | Match this meaning to your installed model and the unit that shows the code, then use the checks below. |
- Code
- S2 R32 split-system outdoor unit / 2024 1U90-1U160 S2 outdoor units
- What it means
- System low-pressure protection
- What to check first
- Match this meaning to your installed model and the unit that shows the code, then use the checks below.
- Code
- MRV5 AV08-AV26IMVEVA - outdoor failure table
- What it means
- Communication failure between outdoor units
- What to check first
- Match this meaning to your installed model and the unit that shows the code, then use the checks below.
- Code
- 2024 3U / 4U / 5U S2 multi-split outdoor units
- What it means
- Low-pressure switch protection
- What to check first
- Match this meaning to your installed model and the unit that shows the code, then use the checks below.
How this fault may be shown
Match every scope item the source provides—exact model where listed, PCB or panel where listed, and reporting device—before using a displayed value. These manufacturer crosswalks are display evidence, not universal codes or repair instructions.
Multi-Split wired controller YR-E17 / YR-E17ASource-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 17
| Reported by | Shown as | Listed meaning |
|---|---|---|
| Wired controller YR-E17 or YR-E17A | 41 | Low-pressure switch protection |
- Reported by
- Wired controller YR-E17 or YR-E17A
- Shown as
- 41
- Listed meaning
- Low-pressure switch protection
Multi-Split wired controller YR-E16 familySource-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 17
| Reported by | Shown as | Listed meaning |
|---|---|---|
| Wired controller YR-E16, YR-E16A, or YR-E16B | 65 | Low-pressure switch protection |
- Reported by
- Wired controller YR-E16, YR-E16A, or YR-E16B
- Shown as
- 65
- Listed meaning
- Low-pressure switch protection
Multi-Split cassette air-conditioner displaySource-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 17
| Reported by | Shown as | Listed meaning |
|---|---|---|
| Cassette air-conditioner display | 41 | Low-pressure switch protection |
- Reported by
- Cassette air-conditioner display
- Shown as
- 41
- Listed meaning
- Low-pressure switch protection
Multi-Split cassette TIMER LED5 / RUNNING LED1Source-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 17
| Reported by | Shown as | Listed meaning |
|---|---|---|
| Cassette unit TIMER LED5 and RUNNING LED1 | LED5 6 / LED1 5 | Low-pressure switch protection |
- Reported by
- Cassette unit TIMER LED5 and RUNNING LED1
- Shown as
- LED5 6 / LED1 5
- Listed meaning
- Low-pressure switch protection
Multi-Split ceiling-floor, cassette, or duct LED4 / LED3Source-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 17
| Reported by | Shown as | Listed meaning |
|---|---|---|
| Ceiling-floor, cassette, or duct unit TIMER LED4 and RUNNING LED3 | LED4 6 / LED3 5 | Low-pressure switch protection |
- Reported by
- Ceiling-floor, cassette, or duct unit TIMER LED4 and RUNNING LED3
- Shown as
- LED4 6 / LED3 5
- Listed meaning
- Low-pressure switch protection
Multi-Split wall-unit displaySource-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 17
| Reported by | Shown as | Listed meaning |
|---|---|---|
| Wall-unit display | F42 | Low-pressure switch protection |
- Reported by
- Wall-unit display
- Shown as
- F42
- Listed meaning
- Low-pressure switch protection
Multi-Split alternate table wired controller YR-E17 / YR-E17ASource-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 19
| Reported by | Shown as | Listed meaning |
|---|---|---|
| Wired controller YR-E17 or YR-E17A | 41 | Low-pressure switch protection |
- Reported by
- Wired controller YR-E17 or YR-E17A
- Shown as
- 41
- Listed meaning
- Low-pressure switch protection
Multi-Split alternate table wired controller YR-E16 familySource-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 19
| Reported by | Shown as | Listed meaning |
|---|---|---|
| Wired controller YR-E16, YR-E16A, or YR-E16B | 65 | Low-pressure switch protection |
- Reported by
- Wired controller YR-E16, YR-E16A, or YR-E16B
- Shown as
- 65
- Listed meaning
- Low-pressure switch protection
Multi-Split duct TIMER LED4 / RUNNING LED3Source-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 19
| Reported by | Shown as | Listed meaning |
|---|---|---|
| Duct unit TIMER LED4 and RUNNING LED3 | LED4 6 / LED3 5 | Low-pressure switch protection |
- Reported by
- Duct unit TIMER LED4 and RUNNING LED3
- Shown as
- LED4 6 / LED3 5
- Listed meaning
- Low-pressure switch protection
Multi-Split ceiling-floor or cassette TIMER LED6 / RUNNING LED1Source-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 19
| Reported by | Shown as | Listed meaning |
|---|---|---|
| Ceiling-floor or cassette unit TIMER LED6 and RUNNING LED1 | LED6 6 / LED1 5 | Low-pressure switch protection |
- Reported by
- Ceiling-floor or cassette unit TIMER LED6 and RUNNING LED1
- Shown as
- LED6 6 / LED1 5
- Listed meaning
- Low-pressure switch protection
Multi-Split panel display on PCB 0151800644PCB 0151800644 · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 19
| Reported by | Shown as | Listed meaning |
|---|---|---|
| Duct, ceiling-floor, or cassette panel display | F45 | Low-pressure switch protection |
- Reported by
- Duct, ceiling-floor, or cassette panel display
- Shown as
- F45
- Listed meaning
- Low-pressure switch protection
Split outdoor control board - 1U105 SSModels 1U105S2SS1FA, 1U105S2SS2FA · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 20
| Reported by | Shown as | Listed meaning |
|---|---|---|
| Outdoor control-board diagnostic display | 45 | System low-pressure protection |
- Reported by
- Outdoor control-board diagnostic display
- Shown as
- 45
- Listed meaning
- System low-pressure protection
Split outdoor control board - 1U125 SN / 1U140 SPModels 1U125S2SN1FA, 1U125S2SN1FB, 1U140S2SP1FA, 1U140S2SP1FB · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 20
| Reported by | Shown as | Listed meaning |
|---|---|---|
| Outdoor control-board diagnostic display | 45 | System low-pressure protection |
- Reported by
- Outdoor control-board diagnostic display
- Shown as
- 45
- Listed meaning
- System low-pressure protection
Low-static duct PCB 0151800267 LED4 / LED3PCB 0151800267 · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 22
| Reported by | Shown as | Listed meaning |
|---|---|---|
| Low-static duct TIMER LED4 and RUNNING LED3 | LED4 6 / LED3 5 | System low-pressure protection |
- Reported by
- Low-static duct TIMER LED4 and RUNNING LED3
- Shown as
- LED4 6 / LED3 5
- Listed meaning
- System low-pressure protection
Low/medium-static duct PCB 0151800644 LED4 / LED3PCB 0151800644 · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 22
| Reported by | Shown as | Listed meaning |
|---|---|---|
| Low/medium-static duct TIMER LED4 and RUNNING LED3 | LED4 6 / LED3 5 | System low-pressure protection |
- Reported by
- Low/medium-static duct TIMER LED4 and RUNNING LED3
- Shown as
- LED4 6 / LED3 5
- Listed meaning
- System low-pressure protection
Low/medium-static duct panel on PCB 0151800644PCB 0151800644 · Panels P1B-890IA/D, P1B-1210IA/D · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 22
| Reported by | Shown as | Listed meaning |
|---|---|---|
| Low/medium-static duct panel display | F45 | System low-pressure protection |
- Reported by
- Low/medium-static duct panel display
- Shown as
- F45
- Listed meaning
- System low-pressure protection
AC ceiling/floor TIMER LED6 / RUNNING LED1Models AC35S2SG1FA, AC50S2SG1FA, AC71S2SG1FA, AC90S2SH1FA, AC105S2SH1FA, AC125S2SK1FA, AC140S2SK1FA, AC160S2SK1FA · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 23
| Reported by | Shown as | Listed meaning |
|---|---|---|
| AC ceiling/floor TIMER LED6 and RUNNING LED1 | LED6 6 / LED1 5 | System low-pressure protection |
- Reported by
- AC ceiling/floor TIMER LED6 and RUNNING LED1
- Shown as
- LED6 6 / LED1 5
- Listed meaning
- System low-pressure protection
AC ceiling/floor displayModels AC35S2SG1FA, AC50S2SG1FA, AC71S2SG1FA, AC90S2SH1FA, AC105S2SH1FA, AC125S2SK1FA, AC140S2SK1FA, AC160S2SK1FA · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 23
| Reported by | Shown as | Listed meaning |
|---|---|---|
| AC ceiling/floor display | F45 | System low-pressure protection |
- Reported by
- AC ceiling/floor display
- Shown as
- F45
- Listed meaning
- System low-pressure protection
AF floor TIMER LED6 / RUNNING LED1Models AF25S2SD1FA, AF35S2SD1FA, AF42S2SD1FA · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 24
| Reported by | Shown as | Listed meaning |
|---|---|---|
| AF floor TIMER LED6 and RUNNING LED1 | LED6 6 / LED1 5 | System low-pressure protection |
- Reported by
- AF floor TIMER LED6 and RUNNING LED1
- Shown as
- LED6 6 / LED1 5
- Listed meaning
- System low-pressure protection
AF floor displayModels AF25S2SD1FA, AF35S2SD1FA, AF42S2SD1FA · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 24
| Reported by | Shown as | Listed meaning |
|---|---|---|
| AF floor display | F45 | System low-pressure protection |
- Reported by
- AF floor display
- Shown as
- F45
- Listed meaning
- System low-pressure protection
Source-labelled cassette TIMER / RUNNING LEDsSource-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 25
| Reported by | Shown as | Listed meaning |
|---|---|---|
| Cassette TIMER and RUNNING LEDs | TIMER 6 / RUNNING 5 | System low-pressure protection |
- Reported by
- Cassette TIMER and RUNNING LEDs
- Shown as
- TIMER 6 / RUNNING 5
- Listed meaning
- System low-pressure protection
Source-labelled cassette displaySource-labelled equipment family; exact models are not listed in this table · Haier Split and Multi Split Error Codes, version 01/2024, PDF page 25
| Reported by | Shown as | Listed meaning |
|---|---|---|
| Cassette display | 41 | System low-pressure protection |
- Reported by
- Cassette display
- Shown as
- 41
- Listed meaning
- System low-pressure protection
Guidance for your model
Notes that match the code to your exact model. Electrical, refrigerant, wiring, resistance and component checks are for a technician.
| Detail | What it says |
|---|---|
| Singapore / model note | Official Haier Australia S2 split-system manual row. Confirm the exact 1U S2 outdoor model before using the meaning; no universal Haier-model parity is claimed. |
| Singapore / model note | Official regional Haier MRV5 row from outdoor-unit manual 0150525031. Confirm an AV08IMVEVA through AV26IMVEVA system, which unit shows the code, and the complete suffix. The source does not enumerate connected indoor models and is not claimed to cover every Haier system or establish universal Singapore-model parity. |
| Singapore / model note | Regional manufacturer handbook, PDF page 14. Confirm the exact listed model and reporting display; this meaning is not claimed for every Haier system. |
- Detail
- Singapore / model note
- What it says
- Official Haier Australia S2 split-system manual row. Confirm the exact 1U S2 outdoor model before using the meaning; no universal Haier-model parity is claimed.
- Detail
- Singapore / model note
- What it says
- Official regional Haier MRV5 row from outdoor-unit manual 0150525031. Confirm an AV08IMVEVA through AV26IMVEVA system, which unit shows the code, and the complete suffix. The source does not enumerate connected indoor models and is not claimed to cover every Haier system or establish universal Singapore-model parity.
- Detail
- Singapore / model note
- What it says
- Regional manufacturer handbook, PDF page 14. Confirm the exact listed model and reporting display; this meaning is not claimed for every Haier system.
What to check before repair
The manufacturer's fault table gives the code's meaning, not a repair procedure. Capture evidence first; model-specific tests belong to the matching service manual.
| You can check | Technician should confirm |
|---|---|
| Photograph the complete 45 error code before taking any action. | Confirm 45 exactly and record which controller, gateway, or unit reported it. |
| Capture the Haier indoor and outdoor model stickers and identify which controller or unit reported it. | Match the indoor and outdoor model stickers, installed family, and reporting equipment to the source scope. |
| The manufacturer provides no customer reset procedure. Preserve the evidence and use the matching service manual for any system action. | Follow the matching service-manual procedure and keep measured test evidence before naming a failed part. |
- You can check
- Photograph the complete 45 error code before taking any action.
- Technician should confirm
- Confirm 45 exactly and record which controller, gateway, or unit reported it.
- You can check
- Capture the Haier indoor and outdoor model stickers and identify which controller or unit reported it.
- Technician should confirm
- Match the indoor and outdoor model stickers, installed family, and reporting equipment to the source scope.
- You can check
- The manufacturer provides no customer reset procedure. Preserve the evidence and use the matching service manual for any system action.
- Technician should confirm
- Follow the matching service-manual procedure and keep measured test evidence before naming a failed part.
Source-bounded repair decision
Haier 45 confirms the fault label the manufacturer lists, not a failed part or repair procedure. Match the installed model to its service manual and require measured diagnostic evidence before approving parts, settings, or refrigerant work.
Whether the reporting controller or unit and exact installed model are confirmed.
What the matching service-manual procedure and measured tests show.
Whether the proposed repair names the evidence for the failed part or condition.
Haier 45 questions
What does the Haier 45 error mean?
Can I fix a Haier 45 error myself?
Is it safe to keep running the aircon with a 45 error?
What causes a Haier 45 error?
Will a Haier 45 error need a repair or a full replacement?
What should I send a technician about a Haier 45 error?
Where to go next
Confirm the fault
Share the error code, model number and symptoms so we can assess the likely cause.
Not the right code?
Browse the full Haier list or check a few codes in the same fault category.
Read next
Use this quote-check guide only after the matching service manual identifies the diagnostic path.