Skip to main content

Heat Load: What a Room Actually Asks an Aircon to Remove

Heat load is how fast a room gains heat. It determines how much cooling the aircon needs to provide. Two rooms of the same size can need different units if one gets more sun or has more people and equipment.

On this page

Quick summary

Heat load is the rate heat arrives in a room, and the aircon must remove it as fast as it arrives. Window direction, floor level, shading, occupants and moisture set it, which is why two rooms of the same size can need different units.

Heat load is a rate, not a size

Heat load is the rate at which heat arrives in a room, in the same units as cooling capacity: BTU per hour or kW. A room holds its temperature only while removal keeps pace with arrival. Faster removal drops the temperature; faster arrival raises it.

The load moves through the day and with use, so size against the peak the room must hold, not the average. A room that gives up every afternoon can still have a fine average.

Why floor area is a weak stand-in

Floor area creates no heat. It stands in for wall, glass and people, and does so loosely.

Two bedrooms of identical size can sit far apart. One faces an internal corridor through a single small window, flanked by cooled bedrooms. The other looks west over an open car park through a wide window, directly under the roof. A floor plan cannot tell them apart.

A per-square-metre figure fits ordinary rooms and fails on the hard ones, which are the rooms the complaints come from.

Sun through glass, and the shade around the window

Sun through glass is the biggest difference between Singapore rooms. Glass passes most solar radiation inside, where it becomes heat on floors and furniture. A solid wall passes only a fraction.

Singapore sits near the equator, so the sun is steep at midday and low in the east and west at either end. Vertical glass takes its worst dose when the sun is low enough to shine straight in. West-facing rooms therefore struggle late in the afternoon, when outdoor air is warmest and the structure has soaked up heat since morning. East-facing rooms take a similar dose earlier, onto walls that shed heat overnight.

What stands opposite the glass matters. A west window facing the next block sees direct sun for a fraction of the time an open one does, and a deep reveal, an overhanging slab or a ledge cut the beam. Solar film and low-emissivity glazing cut transmission; clear glass stops little.

Shading works better outside the glass

Curtains and blinds act after the radiation has crossed the glass, so most of that energy is already in the room. External shading stops the beam first: an awning, a deep ledge, planting or the block opposite beats any curtain. Film on the glass is next best, heavy curtains last.

Heat through the structure, and heat made inside

Conduction pushes heat through any surface in proportion to the temperature gap. Walls, ceiling, floor and door all carry load whenever the room is cooler than the other side. Internal boundaries count: a wall shared with an uncooled living room, a kitchen wall, a door to a warm corridor, the floor above a flat with no aircon.

Each person gives off heat, more when active, plus moisture. A bedroom sized for two sleepers behaves differently with four. Nearly every watt used in the room becomes heat: television, desktop, router, downlights. Filament and halogen fittings give off far more than LEDs.

Outdoor air leaking under doors, around old window frames or through an open door is the source most often left out. It brings both heat and a large amount of moisture.

Heat through the structure, and heat made inside summary table
Load sourceWhat sets its sizeWhat to check or report
Sun through glassWindow direction, glass area, and what stands oppositeWhich way each window faces, and whether anything blocks it
Roof and external wallsSun landing on the surface and how heavy the structure isWhich floor the flat is on, and which walls face outdoors
OccupantsHow many people, and how active they areWho uses the room, and at which hours
Appliances and lightingElectrical load running inside the roomScreens, kitchen equipment, and the type of light fittings
Air leaking inGaps, open doors, and extract fans drawing air throughDoor and window sealing, and whether the room stays shut

The top floor is its own case

The roof slab takes the midday sun on a horizontal face, absorbs a lot of energy and warms the ceiling below. Mass delays that heat: the slab keeps releasing it after sunset, so the ceiling still radiates into the bedroom at bedtime. It reads as an aircon getting worse at night, when the load is simply arriving late.

The moisture half of the load

Cooling load has two parts. Sensible load is the heat a thermometer reads. Latent load is moisture in the air, removed only by condensing it on a cold coil, and in Singapore it is large. Energy spent condensing water does not lower the temperature.

Leakage is the main route for moisture in. Cooking, showers, wet laundry and occupants add more. Rules of thumb from cooler countries undersize systems here because they assume a small moisture share.

Oversizing does not fix this. An oversized unit reaches the set point fast and stops, so the coil warms back up and condenses little. The room ends up cold and damp.

What a sizing survey actually looks at

A sizing survey is mostly questions about the room: window direction and glass area, floor level, what lies above the ceiling, which walls face outdoors, ceiling height, door and window sealing, who uses the room, what runs in it, and whether it opens onto anything uncooled.

The outdoor unit is checked too. A condenser boxed into a tight ledge, breathing its own exhaust, cannot reject heat at its rating, so the room behaves undersized with a correctly sized indoor unit. On an existing system, a fouled coil, a refrigerant leak or a blocked drain give the same symptoms as a capacity shortfall, so restore known-good condition before judging size.

A capacity quoted from floor area alone is an estimate. Ask which window direction and floor it assumed. Load also changes after installation: a partition removed, a bedroom turned into an office, a block that shaded the west window rebuilt taller. The BTU calculator does the arithmetic; this page lists what it needs to be told.

What a sizing survey actually looks at summary table
Sizing inputWhat a floor-area estimate assumesWhat it costs when the assumption is wrong
Window directionAverage exposure, neither shaded nor facing westA room that holds through the morning and gives up after lunch
Floor levelConditioned space sitting above the ceilingA top-floor bedroom that gets harder to cool after dark
OccupancyOne or two people for part of the dayA living room that copes until the whole family is home
Moisture loadA modest share of the totalCold air that never stops feeling damp
Room boundariesA closed room with doors kept shutA unit sized for a bedroom trying to cool half the flat

Common questions

What is heat load in a Singapore flat?
Heat load is the rate at which heat arrives in a room, quoted in the same units as cooling capacity. It decides what a unit must remove to hold a temperature, and it changes through the day.
Why is floor area a poor guide to aircon size?
Floor area stands in for the things that create load, so it misses window direction, floor level and what shades the glass. Two same-sized bedrooms can need different capacities.
Does a top-floor flat need more cooling capacity?
Usually yes. The roof slab absorbs the midday sun and releases that heat into the ceiling after dark, so a top-floor bedroom carries a load the identical room below does not.
What does a sizing survey actually check?
Window direction and glass area, floor level, ceiling height, who uses the room, appliances inside it, and whether doors stay shut. Floor area is one line on that list rather than the whole sum.
Can an aircon unit be too large for a room?
Yes. An oversized unit reaches the set temperature quickly and stops, so the coil spends little time cold and the room can stay cold and damp. Correctly sized capacity runs longer at lower output.

Sources