- 5.0Google & Carousell
- 15,000+jobs completed
Aircon Plenum Box: The One Part That Gets Made on Site
Every other part of a ducted system arrives with a model number and a page of test data. The chamber joining the machine to its ducts gets made on site, from flat sheet, and carries neither.
By Team Snowflake | Updated 16 Sept 2026
The box between the machine and the ducts
A plenum box is a chamber wider than the pipes leaving it. Air arrives through one opening and leaves through several, at lower speed. Ducted systems carry them in two positions: at the discharge of the indoor unit, dividing flow into branches, and above a ceiling outlet, spreading a single duct across the face of the fitting.
None of it comes out of a carton. The Daikin FDXM installer reference guide states the position in one line: the ducting is to be field supplied. Its diagram labels the flange, insulation and aluminium tape the same way.
Mitsubishi Electric writes the job as a short list. Its PEAD ducted range asks for a canvas duct between unit and duct, incombustible material for duct parts, and full insulation on the inlet and outlet duct flanges. None arrives finished; they get cut, fitted and wrapped by hand above a ceiling.
So the box is the one component whose quality is settled entirely on site. The machine was tested before it shipped, and so was the diffuser; what joins them was folded and taped by whoever worked above that ceiling.
A factory plenum is a designed part
Plenums do get manufactured, and where they are, their shape is engineering. Titus describes its N series slot diffuser as the result of aerodynamic blades. It also points to careful matching of slot and inlet plenum. The plenum is named as half of what produces the discharge pattern.
Price Industries states the same relationship from the other side: some plenum slot diffusers and linear slot plenums are built with a sloped shoulder, and that slope creates a natural spreading of the air pattern, substantially reducing throw. Change the box shape, leave the diffuser alone, and how far the air travels moves with it.
A factory plenum has a part number and a page of performance behind it. A folded box above a ceiling has whatever geometry the void allowed.
What an outlet's published figures assume about its inlet
Every throw, pressure and noise figure in a diffuser catalogue was taken under one inlet condition, and the catalogues say so. Titus bases its data on ASHRAE Standard 70, which requires several diameters of straight duct at the approach. The sentence after it carries the weight: field installations seldom allow these conditions.
The measuring point is written down as well. Titus takes an outlet's total pressure as the sum of static and velocity pressures in the supply duct, one and a half duct diameters ahead of the outlet.
Price Industries arrives at the same place from the design side. Its guidance for quiet air distribution asks for smooth airflow at all duct elements, including branches, elbows, transitions and outlets, with five to ten duct diameters of straight ductwork between them. A ceiling void in a flat has neither the depth nor the length.
Both makers then name the same remedy, a fair measure of how common the problem is. Price asks for equalizing grids when non-ideal inlets cannot be avoided, and Titus lists the same item for direct diffuser connections. That is a bought part costing money and ceiling depth a tight void lacks.
Published means published under a condition
Price puts the pressure side of an outlet beyond calculation. Static pressure loss depends on outlet geometry and free area, it says, and only testing gets to it. A fitting's real behaviour cannot be had except by measuring it under a defined setup.
The consequence runs one way. A catalogue figure is a ceiling on what an outlet can do under laboratory conditions. Everything the ceiling void does to the approach moves the real result away from that number, never toward it.
What a badly made box does to the room
The penalties are published, and they are not small. Titus puts the effect of joining a diffuser straight onto a duct at as much as 12 NC above catalogue levels, caused by regions of high velocity inside the fitting. That gap separates a bedroom somebody sleeps in from one they can hear.
Flexible duct at the inlet was tested as its own case. Titus reports that flexible ducts at a diffuser inlet increase pressure drop, increase sound levels and produce nonuniform air distribution. An ideal gentle 90 degree connection adds about 1 NC; a kinked one adds 7 to 9.
Air pattern moves with all of it, and that part carries no number. The same list records only that the distribution pattern can be greatly affected, varying by diffuser type. A warm corner under a correctly selected diffuser can come from the shape of the metal above it.
The equalizing grid figures show what an approach is worth in decibels. Titus reproduces two cases from the ASHRAE Handbook. With an equalizing grid, sound levels match the maker's rating; without one they run up to 12 dB higher. The second compares eight duct diameters of straight run against two, and the short version measures 12 to 15 dB above rating.
The proportions of the box decide where the air points. Titus tabulates the discharge angle of an end-fed linear diffuser against the ratio of slot area to duct area. At 0.4 the airstream leaves at 15 degrees; at 0.75 at 25, at 1.0 at 35, and at 1.5 at 40. Nothing changed but the relative size of two openings.
Getting a flat discharge back takes a part. Titus assures a 0 degree angle along the whole face by including straightening blades behind the face vanes or bars. Leave those out and the face still looks finished, while the air leaves at an angle nobody chose.
The machine end has a geometry rule of its own. The PEAD guidance warns that intake noise increases dramatically if the intake sits directly beneath the main body. It asks for the intake to be fitted as far from the body as possible, with an inlet duct of 850 mm or more.
| What the box does | What the published figure assumed | What the room gets |
|---|---|---|
| Duct joined straight onto the fitting | A settled, even approach at the neck | Up to 12 NC above the catalogue figure |
| Flexible duct kinked into the inlet | A gentle bend, worth about 1 NC | 7 to 9 NC added, and the pattern shifts |
| No equalizing grid on a direct connection | Sound at the maker's own rating | Up to 12 dB above that rating |
| Two duct diameters of straight run | Eight duct diameters ahead of the outlet | 12 to 15 dB above the published rating |
| A wide box feeding a narrow slot | The area ratio the maker tabulated | Air leaving at 40 degrees instead of 15 |
- What the box does
- Duct joined straight onto the fitting
- What the published figure assumed
- A settled, even approach at the neck
- What the room gets
- Up to 12 NC above the catalogue figure
- What the box does
- Flexible duct kinked into the inlet
- What the published figure assumed
- A gentle bend, worth about 1 NC
- What the room gets
- 7 to 9 NC added, and the pattern shifts
- What the box does
- No equalizing grid on a direct connection
- What the published figure assumed
- Sound at the maker's own rating
- What the room gets
- Up to 12 dB above that rating
- What the box does
- Two duct diameters of straight run
- What the published figure assumed
- Eight duct diameters ahead of the outlet
- What the room gets
- 12 to 15 dB above the published rating
- What the box does
- A wide box feeding a narrow slot
- What the published figure assumed
- The area ratio the maker tabulated
- What the room gets
- Air leaving at 40 degrees instead of 15
Insulation and sealing: two jobs finished behind a board
Insulation on the box answers condensation before comfort, and the manuals give that as the reason. Daikin's FDXM guidance asks that the duct be insulated to prevent condensation, naming glass wool or polyethylene foam 25 mm thick. Mitsubishi asks for full insulation on the inlet duct flange and outlet duct, for the same reason.
Climate is what those instructions were written against, and the PEAD manual sets a threshold. Where air above the ceiling runs hot and humid, with a dew point above 26 degrees C, condensation may form in the indoor unit, and the manual asks for 10 to 20 mm of insulation across the whole unit surface. A closed void above a flat here is warm and still, and nobody measures its dew point after handover.
An uninsulated box behaves like a cold glass. Moisture in the surrounding air condenses on the metal and runs to the lowest point it can find, usually the ceiling board. The fault then presents as a stain or a drip in a room, with nothing wrong inside the machine.
Sealing is the second job, and a standard sits behind it. The 1995 edition of SMACNA's duct construction standard defines sealing as closing openings in ductwork and field-erected plenums and casings through which air leakage would occur. The words field-erected sit inside the standard's own definition, so a box made on site falls within its scope.
Whatever escapes goes into the ceiling, where nobody sees it. Cooled air leaving an unsealed seam still crossed the coil and was still paid for, and no room received it. Daikin is direct: wind aluminium tape around the intake side flange and duct connection, and make sure there are no air leaks elsewhere.
How much sealing depends on a number nobody stated
The standard sets sealing by pressure class. SMACNA asks for transverse joints only at 2 inches of water, joints and longitudinal seams at 3 inches, and every joint, seam and duct wall penetration from 4 inches upward.
It also covers the case where nobody specified anything. Where no pressure classes are specified by the designer, the standard makes the 1 inch water gage class the basis of compliance. A domestic job with no drawing and no specification defaults to the lightest treatment the standard recognises.
What an owner can settle about a box they never see
No code reaches into a flat to govern this. SS 553 sets out good practice for air-conditioned and mechanically ventilated buildings in Singapore, scoped to commercial, office and institutional buildings except hospitals. It contains a ductwork and other air passages clause, a seal requirements table and minimum duct R-values. A home falls outside the building types it applies to.
The construction standard says as much about itself. SMACNA records that duct systems for residences are not ordinarily subject to its provisions. Where its own pages are silent, it hands the choice over: the contractor shall select configurations suitable for the service.
So the answer to who decided the box's shape is always the same. It was not a maker, an engineer or a code, but the installer, working to whatever depth the ceiling left.
One request tests a quotation without argument. Ask for the outlet selection in writing, along with the approach condition it assumed and how the box and its joints will be insulated and sealed. A contractor who picked the outlet off a selection table already holds both on paper; where the answer comes back as a machine size, the path from machine to room was never priced.
What is worth reporting once the ceiling is closed
Three things are worth writing down before anybody climbs up. Whether a fitting hisses or whistles, whether one room runs warm while air feels cold at every other outlet, and whether a stain has appeared on the ceiling near a fitting. The third gets reported as a leak far more often than as an insulation fault.
Timing carries as much information as the symptom. A noise or warm corner present since commissioning points at how the ceiling was built; one that started after later work points at what that work disturbed above the board. Naming which it was removes much of the guessing.