How unbalanced kitchen exhaust hoods starve dining-room aircons
Every cubic metre of hot smoke pulled up a commercial F&B exhaust canopy must be replaced immediately by fresh air entering the unit. When a kitchen lacks dedicated tempered or outdoor make-up air ducts (or staff switch the make-up fan off), the exhaust hood pulls chilled air straight out of the dining room instead.
That negative building pressure slams doors shut, sucks muggy 85% RH street air through shopfront gaps and coats dining cassettes in ceiling condensation.
| Dining-room symptom | Hidden F&B root cause | Correct commercial fix |
|---|---|---|
| Shopfront door feels heavy or slams hard when opened | Severe negative pressure from uncompensated exhaust hood | Restore or balance dedicated kitchen make-up air supply |
| Hot dining hall only during peak lunch/dinner rush | Exhaust running high + cooking heat + frequent door openings | Add doorway air curtain, partition kitchen pass & verify tonnage |
| Cassettes blowing weakly with amber oil around grilles | Aerosolised cooking grease clogging indoor fins and drain pump | Monthly filter degreasing + bi-monthly/quarterly chemical coil wash |
| Sweating ceiling diffusers & dripping grilles | Humid outdoor air sucked straight across freezing supply vents | Fix negative room pressure first before blaming cassette insulation |
Why adding another cassette rarely fixes negative pressure
Installing an extra 36,000 BTU ceiling cassette inside a negative-pressure shophouse simply gives the kitchen hood more chilled air to throw up the roof flue, driving monthly SP Group electricity bills sky-high while diners still sweat near the entrance.
Check exhaust-to-make-up air ratios alongside SCDF Fire Code Clause 7.1 ACMV compliance and NEA environmental health ventilation standards before upgrading tonnage.
Preventive degreasing schedule for F&B indoor units
Commercial F&B fan coils collect ten times the airborne grease and lint of an office unit. Once oil coats evaporator fins and condensate lift-pump floats, cooling collapses within weeks and dirty water overflows right above dining tables.
Put F&B cassettes and ceiling-suspended units on a strict monthly filter-and-drain check paired with quarterly chemical degreasing outside trading hours.