Capacitor price, beside the compressor bill
A capacitor replacement is one of the smallest repair bills on an aircon. Published Singapore rates price it as part and labour together.
Snowflake Aircon Services tests the starting circuit and confirms the right capacitor for the model before quoting.
| Job | Market range in Singapore | Our rate |
|---|---|---|
| Run or start capacitor replaced, part and labour | $70–$150 per job | Quoted per job |
| Compressor or condensing unit, if the capacitor tests good | $300–$1,500 per job | |
| Diagnostic visit to confirm the fault | $30 / visit |
The capacitor is priced as part and labour together. The compressor row is there because the same symptom can mean either part, and only the test separates them.
Market ranges: published rates from 4 Singapore operators; published rates from 6 Singapore operators. Checked between 18 Nov 2026 and 20 Nov 2026.
Capacitor alone, or capacitor and compressor?
A capacitor helps a motor start. On non-inverter units it starts the compressor, and many fan motors use one too. An inverter unit starts its compressor from the board instead, so the same symptom there points to the board or the compressor.
A technician measures the capacitor's value with a meter and compares it with the figure printed on it. A reading well below the printed value means the capacitor is the fault.
| Finding | What it means | Likely bill |
|---|---|---|
| Capacitor reads low, compressor starts on a new one | The capacitor was the whole fault | Capacitor only |
| Capacitor reads low, compressor still will not start | Capacitor and compressor both failing | Compressor job |
| Capacitor reads to its printed value | The fault is elsewhere: compressor, board or wiring | Further testing |
| Capacitor bulging or leaking | Replace it, then test the compressor | Capacitor at least |
Signs that point to the capacitor
Do not open the outdoor unit to look. A capacitor holds a charge after the power is off.
- The outdoor unit hums but the fan does not turn.
- The outdoor unit clicks on and off without starting.
- Cooling works some days and not others.
Why a capacitor should not be ignored
A motor that keeps struggling to start runs hot. Left long enough, a weak capacitor can take the compressor or fan motor with it, which turns a small repair into a large one.