Aircon Gas Leakage Repair: What Happens, Step by Step

A gas leakage repair is often quoted as one line, a top-up. The real job has six steps in a fixed order, and skipping one leaves the leak open or the circuit wet.

On this page

What does an aircon gas leakage repair involve?

A gas leakage repair is six steps: confirm, pressure test, find, seal, vacuum, then charge and check. Refrigerant goes in last, after the leak is sealed and the circuit is dry.

Each step answers a different question. A visit that only adds gas answers none of them.

What does an aircon gas leakage repair involve? summary table
StepWhat happensWhat it proves
1. ConfirmPressures and temperatures are read against the maker's dataThe charge is low, not an airflow or coil fault
2. Pressure testThe circuit is filled with dry nitrogen and watched on a gaugeThe circuit leaks, and roughly how fast
3. FindJoints, valves, pipe and coil are searched with a detector or bubble solutionWhere the opening is
4. SealThe flare is remade, or the valve, pipe section or coil is replacedThe opening is closed
5. VacuumA pump draws out air and moisture, then the gauge is watched with the pump offThe circuit is dry and holds
6. Charge and checkThe specified weight of refrigerant goes in, and the unit is run and measuredThe repair restored cooling

Why the order cannot change

Gas added before the seal leaves through the same opening. Mitsubishi Electric's FAQ says adding refrigerant to a leak is not a solution.

Nitrogen carries the pressure test because it is inert. The Australia and New Zealand refrigerant handling code bars refrigerant as a test gas. It also bars any top-up until every leak is repaired.

The vacuum comes after the seal, because opening the circuit lets in air and moisture. Where the maker gives no figure, the code sets a target below 500 microns. A gauge that creeps back up with the pump off means moisture or a leak remains.

Where the leak is decides step 4

Steps 1 to 3 and 5 to 6 are the same on every job. Step 4 changes with the leak's location, and so does the length of the visit.

A concealed pipe run is the hard case. A section test can prove that stretch leaks without placing the point. The choice is then to open the wall or ceiling, or replace the run.

Where the leak is decides step 4 summary table
Leak locationUsual repairWhat can extend the job
Flare joint or service valveFlare remade or valve core replacedLittle; these are reached directly
Exposed copper pipeDamaged section cut out and brazed under nitrogenTrunking covers to remove
Pipe in a wall or false ceilingSection replaced or run re-routedOpening finishes, or a new route
Indoor or outdoor coilCoil replaced, or a brazed repair where the tube is reachablePart supply for the exact model

What the job sheet should record

A finished repair leaves evidence on paper. Four lines show whether the job was a repair or a refill.

  • Where the leak was found, and the test that found it.
  • What was replaced or remade at that point.
  • That the circuit was retested and evacuated before charging.
  • The refrigerant type and the weight charged, against the rated charge.

R32 systems and repeat leaks

R32 work needs a trained technician. NEA states that manufacturers must ensure R32 service staff have completed ITE training, in line with SCDF requirements.

Snowflake Aircon Services treats a second top-up on the same system as a near-certain sign of an open leak. When sealing stops being worth it after repeat top-ups is covered in a separate guide. Gas leak detection is the booking that covers steps 1 to 3.

Common questions

What are the steps in an aircon gas leakage repair?
An aircon gas leakage repair has six steps in order. The technician confirms the charge is low, proves the leak with a nitrogen pressure test, and finds the leak. The leak is then sealed, a vacuum removes air and moisture, and refrigerant is charged by weight. Gas always goes in last.
Can a technician just top up the gas instead of repairing the leak?
A top-up on a leaking aircon restores cooling only until the new charge escapes through the same opening. Mitsubishi Electric's guidance says adding refrigerant to a leak is not a solution. Refrigerant handling codes also bar any top-up until every leak has been found and repaired.
Why is nitrogen used to test an aircon for leaks?
Dry nitrogen is inert, so it can be pushed above an aircon's normal working pressure without harm. A small leak then shows as a falling gauge. Refrigerant is never used as the test gas, because a failed test would release it into the air.
Why does an aircon need a vacuum after a gas leak repair?
Opening the refrigerant circuit for a repair lets in air and moisture. A vacuum pump draws them out before the new charge goes in. A hold test with the pump switched off then shows whether the circuit is dry and sealed, or still leaking.
What should an aircon gas leak repair invoice show?
An aircon gas leak repair invoice should state where the leak was and how it was found. It should list what was replaced or remade, confirm the circuit was retested and evacuated, and give the refrigerant type and the weight charged against the rated charge.