What does an aircon gas leakage repair involve?
A gas leakage repair is six steps: confirm, pressure test, find, seal, vacuum, then charge and check. Refrigerant goes in last, after the leak is sealed and the circuit is dry.
Each step answers a different question. A visit that only adds gas answers none of them.
| Step | What happens | What it proves |
|---|---|---|
| 1. Confirm | Pressures and temperatures are read against the maker's data | The charge is low, not an airflow or coil fault |
| 2. Pressure test | The circuit is filled with dry nitrogen and watched on a gauge | The circuit leaks, and roughly how fast |
| 3. Find | Joints, valves, pipe and coil are searched with a detector or bubble solution | Where the opening is |
| 4. Seal | The flare is remade, or the valve, pipe section or coil is replaced | The opening is closed |
| 5. Vacuum | A pump draws out air and moisture, then the gauge is watched with the pump off | The circuit is dry and holds |
| 6. Charge and check | The specified weight of refrigerant goes in, and the unit is run and measured | The repair restored cooling |
Why the order cannot change
Gas added before the seal leaves through the same opening. Mitsubishi Electric's FAQ says adding refrigerant to a leak is not a solution.
Nitrogen carries the pressure test because it is inert. The Australia and New Zealand refrigerant handling code bars refrigerant as a test gas. It also bars any top-up until every leak is repaired.
The vacuum comes after the seal, because opening the circuit lets in air and moisture. Where the maker gives no figure, the code sets a target below 500 microns. A gauge that creeps back up with the pump off means moisture or a leak remains.
Where the leak is decides step 4
Steps 1 to 3 and 5 to 6 are the same on every job. Step 4 changes with the leak's location, and so does the length of the visit.
A concealed pipe run is the hard case. A section test can prove that stretch leaks without placing the point. The choice is then to open the wall or ceiling, or replace the run.
| Leak location | Usual repair | What can extend the job |
|---|---|---|
| Flare joint or service valve | Flare remade or valve core replaced | Little; these are reached directly |
| Exposed copper pipe | Damaged section cut out and brazed under nitrogen | Trunking covers to remove |
| Pipe in a wall or false ceiling | Section replaced or run re-routed | Opening finishes, or a new route |
| Indoor or outdoor coil | Coil replaced, or a brazed repair where the tube is reachable | Part supply for the exact model |
What the job sheet should record
A finished repair leaves evidence on paper. Four lines show whether the job was a repair or a refill.
- Where the leak was found, and the test that found it.
- What was replaced or remade at that point.
- That the circuit was retested and evacuated before charging.
- The refrigerant type and the weight charged, against the rated charge.
R32 systems and repeat leaks
R32 work needs a trained technician. NEA states that manufacturers must ensure R32 service staff have completed ITE training, in line with SCDF requirements.
Snowflake Aircon Services treats a second top-up on the same system as a near-certain sign of an open leak. When sealing stops being worth it after repeat top-ups is covered in a separate guide. Gas leak detection is the booking that covers steps 1 to 3.