Verified meanings of Daikin A1 and A6
Daikin split aircons isolate indoor electronics faults under the A-series prefix. Code A1 points to indoor PCB defectiveness, such as corrupted memory, burnt drive circuits, or failed voltage regulation on the FCU control board. Code A6 signals a fan motor fault, where the indoor blower stalls, draws abnormal current, or fails to send rotation feedback pulses.
Although A1 and A6 sit side by side in Daikin diagnostics, a shorted DC fan motor can damage the driver stage on the indoor PCB. Replacing a board blindly without bench-testing the motor often destroys the fresh replacement board on initial startup.
| Daikin code | Fault category | Verified meaning and key check |
|---|---|---|
| A1 | PCB / Electrical Fault | Indoor PCB defectiveness; check 5-pin motor resistance and supply voltage before fitting a new indoor PCB. |
| A6 | Fan Motor Fault | Fan motor fault; spin blower wheel freely by hand, inspect wiring plug, and verify Hall sensor feedback. |
Why winding and hall sensor testing comes first
During on-site troubleshooting, a technician disconnects the indoor fan plug and measures coil resistance across the motor pins with a multimeter. Low resistance or an open winding confirms a failed motor rather than a healthy blower starved of signal. Checking the blower drum bearings also rules out dried grease or trapped debris causing mechanical lock.
Next, the technician verifies DC rail voltage and Hall sensor feedback coming out of the indoor PCB. Because damaged control boards are always replaced outright and never soldered at component level, confirming whether the motor, the PCB, or both failed prevents repeat breakdowns.
Safe steps before booking Daikin troubleshooting
Turn the affected Daikin FCU off using the wireless remote and avoid flipping wall isolators or tripped breakers back on to force a restart. Repeated power cycling can worsen shorted motor windings and erase live diagnostic clues needed during inspection.
Note whether other rooms on your HDB or condo multi-split still run normally, then photograph the side model label. WhatsApp the image and fault code so Snowflake Aircon Services can prepare accurate Daikin testing and parts matching.
Common questions
Can a bad Daikin indoor fan motor cause an A1 board failure?
Does Daikin error A1 mean the indoor board can be repaired?
Will cleaning the blower drum clear a Daikin A6 alarm?