On this page
How This Presents
Every wall unit in a Bishan condo living room and two bedrooms runs on fan only with zero chilled air. Indoor status lamps blink gently without showing a clear code on the front cover. Outside in the enclosed balcony bay, the inverter condenser stays silent.
- Setup
- Daikin Wall-mounted7-9 yearsCondoBishan
- Misread as
- Replacing a whole condo Daikin multi-split condenser and lifting units through a tight Bishan balcony bay after cooling vanished in every room.
- Check first
- Inspecting the red LED bank on the outdoor fault panel, decoding the Daikin sensor fault, and checking thermistor ohms against ambient temperature
- Actual finding
- Open-circuit Daikin outdoor heat-exchanger thermistor halting multi-split cooling via outdoor safety protection while the inverter compressor stays healthy
- Scope saved
- Targeted repair instead of full replacement

What Else Produces This
Losing cool air in all rooms at once points straight outside. Checking the outdoor fault panel first saves guesswork and skips an unneeded condenser swap.
Taking off the outdoor service lid shows red fault LEDs lit along the main board bank.
Matching the outdoor LED state with remote check mode confirms a J6 outdoor heat-exchanger thermistor fault.
Unplugging the coil sensor lead and testing ohms on a meter gives an open reading instead of normal warm-air range.
Checking compressor phase coils, outdoor fan spin, and 230V mains confirms the mechanical drive stays completely sound.
Why It Happens
Years of trapped balcony heat and driving monsoon spray inside the Bishan condo ledge rusted the thin wire join inside the outdoor coil sensor sleeve. Once the probe broke open, Daikin safety logic blocked compressor start in every room.
What Resolution Involves
Keep the sound Daikin condenser, outdoor board, and gas charge sealed in place. Switch off balcony power, slide the failed coil thermistor out of its copper clip, fit a matched Daikin replacement probe tightly into the pocket, and route the wire clear of sharp metal.
How to Tell It Worked
Switch balcony mains back on and verify the outdoor red fault LEDs clear cleanly. Start the living room and bedrooms together on cool mode. Confirm smooth compressor ramp-up and brisk cold air across the Bishan condo.
Before You Approve a Quote
Read the Daikin outdoor LED bank before quoting a new condenser
- Whole-flat cooling loss on a Daikin multi-split often stems from a small outdoor sensor locking out compressor startup.
- The red diagnostic LED bank inside the condenser panel narrows the fault straight to the outdoor coil thermistor circuit.
- Swapping the drifted sensor probe keeps an otherwise healthy eight-year-old Singapore condo inverter unit running smoothly.