Daikin Aircon E9 Error Code
Use this Daikin E9 error code guide to confirm the source table meaning, capture the reporting equipment and model, and match the service manual before diagnosis. Match the model first; same-looking codes can point to different rows.
What does Daikin E9 mean?
Daikin E9 is listed as malfunction of electronic expansion valve coil, electronic expansion valve coil abnormality, and upper heat-exchanger electronic expansion-valve malfunction at Y1E on main PCB connector X21A in mixed model-family source rows, including VRV X RXQ-A(N)R cooling only, VRV IV+ REYQ / REMQ heat recovery, VRV 5-S RXYSA R32, VRV 5 Heat Recovery REMA / REYA R32, VRV 5 Heat Pump RYMA / RXYA R32, and ERA-AYF AHU / air curtain. The loaded row is source-backed by official diagnostic material. Do not collapse this code across model families; use the model, series, or system type to choose the right row. Confirm the exact model, series, or signal row before accepting a parts quote.
Choose the matching source row
The same visible code has more than one source-backed meaning. Match the model family, system type, or reporting unit before approving parts.
| Code | What it means | What to check first |
|---|---|---|
| SkyAir | Malfunction of electronic expansion valve coil | Match this row to the installed model or reporting unit, then use the source-specific checks below. |
| VRV X RXQ-A(N)R cooling only | Electronic expansion valve coil abnormality | Match this row to the installed model or reporting unit, then use the source-specific checks below. |
| E9-01 - master / E9-05 - slave 1 / E9-08 - slave 2 | Upper heat-exchanger electronic expansion-valve malfunction at Y1E on main PCB connector X21A | Check the connection on the PCB or actuator. Match the alternating E9-01 display to the master source row. |
| E9-04 - master / E9-07 - slave 1 / E9-10 - slave 2 | Lower heat-exchanger electronic expansion-valve malfunction at Y3E on main PCB connector X23A | Check the connection on the PCB or actuator. Match the alternating E9-04 display to the master source row. |
| E9-03 - master / E9-06 - slave 1 / E9-09 - slave 2 | Subcool heat-exchanger electronic expansion-valve malfunction at Y2E on main PCB connector X22A | Check the connection on the PCB or actuator. Match the alternating E9-03 display to the master source row. |
| E9-26 - master / E9-27 - slave 1 / E9-28 - slave 2 | Receiver-gas electronic expansion-valve malfunction at Y4E on main PCB connector X25A | Check the connection on the PCB or actuator. Match the alternating E9-26 display to the master source row. |
| E9-29 - master / E9-34 - slave 1 / E9-39 - slave 2 | Inverter-cooling electronic expansion-valve malfunction at Y5E on sub PCB connector X8A | Check the connection on the PCB or actuator. Match the alternating E9-29 display to the master source row. |
| E9-31 - master / E9-36 - slave 1 / E9-41 - slave 2 | Auto-charge electronic expansion-valve malfunction at Y6E on sub PCB connector X10A | Check the connection on the PCB or actuator. Match the alternating E9-31 display to the master source row. |
| VRV 5-S R32 - E9 / VRV 5 Heat Recovery R32 - E9 / VRV 5 Heat Pump R32 - E9 | Outdoor electronic expansion-valve malfunction | Check the Y1E or Y3E expansion-valve connection at the outdoor PCB or actuator. |
| ERA-AYF AHU / air curtain | Electronic expansion-valve malfunction (E9-01/04/26/29) | Match this row to the installed model or reporting unit, then use the source-specific checks below. |
- Code
- SkyAir
- What it means
- Malfunction of electronic expansion valve coil
- What to check first
- Match this row to the installed model or reporting unit, then use the source-specific checks below.
- Code
- VRV X RXQ-A(N)R cooling only
- What it means
- Electronic expansion valve coil abnormality
- What to check first
- Match this row to the installed model or reporting unit, then use the source-specific checks below.
- Code
- E9-01 - master / E9-05 - slave 1 / E9-08 - slave 2
- What it means
- Upper heat-exchanger electronic expansion-valve malfunction at Y1E on main PCB connector X21A
- What to check first
- Check the connection on the PCB or actuator. Match the alternating E9-01 display to the master source row.
- Code
- E9-04 - master / E9-07 - slave 1 / E9-10 - slave 2
- What it means
- Lower heat-exchanger electronic expansion-valve malfunction at Y3E on main PCB connector X23A
- What to check first
- Check the connection on the PCB or actuator. Match the alternating E9-04 display to the master source row.
- Code
- E9-03 - master / E9-06 - slave 1 / E9-09 - slave 2
- What it means
- Subcool heat-exchanger electronic expansion-valve malfunction at Y2E on main PCB connector X22A
- What to check first
- Check the connection on the PCB or actuator. Match the alternating E9-03 display to the master source row.
- Code
- E9-26 - master / E9-27 - slave 1 / E9-28 - slave 2
- What it means
- Receiver-gas electronic expansion-valve malfunction at Y4E on main PCB connector X25A
- What to check first
- Check the connection on the PCB or actuator. Match the alternating E9-26 display to the master source row.
- Code
- E9-29 - master / E9-34 - slave 1 / E9-39 - slave 2
- What it means
- Inverter-cooling electronic expansion-valve malfunction at Y5E on sub PCB connector X8A
- What to check first
- Check the connection on the PCB or actuator. Match the alternating E9-29 display to the master source row.
- Code
- E9-31 - master / E9-36 - slave 1 / E9-41 - slave 2
- What it means
- Auto-charge electronic expansion-valve malfunction at Y6E on sub PCB connector X10A
- What to check first
- Check the connection on the PCB or actuator. Match the alternating E9-31 display to the master source row.
- Code
- VRV 5-S R32 - E9 / VRV 5 Heat Recovery R32 - E9 / VRV 5 Heat Pump R32 - E9
- What it means
- Outdoor electronic expansion-valve malfunction
- What to check first
- Check the Y1E or Y3E expansion-valve connection at the outdoor PCB or actuator.
- Code
- ERA-AYF AHU / air curtain
- What it means
- Electronic expansion-valve malfunction (E9-01/04/26/29)
- What to check first
- Match this row to the installed model or reporting unit, then use the source-specific checks below.
What to do now
Use these steps to record evidence and match the installed model to its service manual before diagnosis or a repair quote.
Record E9 and match the service manual
Record E9 and stop there; the source table gives no customer reset procedure. Arrange diagnosis with the matching service manual.
No manufacturer reset steps listed for E9
Capture the complete E9 error code and model stickers first. The source table lists the meaning but no customer reset procedure; do not treat a generic power-cycle as manufacturer guidance.
Send these to us
E9 error code, a clear display photo, Daikin indoor and outdoor model stickers, the controller, gateway, or unit that reported the code, operating mode and affected area, and any power or setting changes made after the code appeared
Source-specific guidance
These diagnostic-reference notes help match the code to the exact model. Electrical, refrigerant, wiring, resistance, and component checks are technician work, not DIY steps.
| Source detail | What it says |
|---|---|
| Singapore / model note | Official Daikin SM-TS3 self-diagnosis row. Manual causes: Electronic expansion valve connector disconnected; Defective electronic expansion valve coil; Defective outdoor unit control PCB. |
| Singapore / model note | Official Daikin RXQ6-48A(N)R cooling-only service-manual row. Confirm the installed model and matching regional manual before diagnosis; this source is not claimed as universal across every Daikin VRV generation. |
| Singapore / model note | Official Daikin 4PEN561154-1C overview row for REYQ8~20 and REMQ5U7Y1B VRV IV+ heat-recovery systems. The guide refers technicians to the service manual for the complete code list and detailed troubleshooting. |
- Source detail
- Singapore / model note
- What it says
- Official Daikin SM-TS3 self-diagnosis row. Manual causes: Electronic expansion valve connector disconnected; Defective electronic expansion valve coil; Defective outdoor unit control PCB.
- Source detail
- Singapore / model note
- What it says
- Official Daikin RXQ6-48A(N)R cooling-only service-manual row. Confirm the installed model and matching regional manual before diagnosis; this source is not claimed as universal across every Daikin VRV generation.
- Source detail
- Singapore / model note
- What it says
- Official Daikin 4PEN561154-1C overview row for REYQ8~20 and REMQ5U7Y1B VRV IV+ heat-recovery systems. The guide refers technicians to the service manual for the complete code list and detailed troubleshooting.
What to check before repair
The source table establishes the code meaning, not a repair procedure. Capture evidence first; model-specific tests belong to the matching service manual.
| You can check | Technician should confirm |
|---|---|
| Photograph the complete E9 error code before taking any action. | Confirm E9 exactly and record which controller, gateway, or unit reported it. |
| Capture the Daikin indoor and outdoor model stickers and identify which controller or unit reported it. | Match the indoor and outdoor model stickers, installed family, and reporting equipment to the source scope. |
| The source table provides no customer reset procedure. Preserve the evidence and use the matching service manual for any system action. | Follow the matching service-manual procedure and keep measured test evidence before naming a failed part. |
- You can check
- Photograph the complete E9 error code before taking any action.
- Technician should confirm
- Confirm E9 exactly and record which controller, gateway, or unit reported it.
- You can check
- Capture the Daikin indoor and outdoor model stickers and identify which controller or unit reported it.
- Technician should confirm
- Match the indoor and outdoor model stickers, installed family, and reporting equipment to the source scope.
- You can check
- The source table provides no customer reset procedure. Preserve the evidence and use the matching service manual for any system action.
- Technician should confirm
- Follow the matching service-manual procedure and keep measured test evidence before naming a failed part.
Source-bounded repair decision
Daikin E9 confirms the source-table fault label, not a failed part or repair procedure. Match the installed model to its service manual and require measured diagnostic evidence before approving parts, settings, or refrigerant work.
Whether the reporting controller or unit and exact installed model are confirmed.
What the matching service-manual procedure and measured tests show.
Whether the proposed repair names the evidence for the failed part or condition.
Daikin E9 questions
What does the Daikin E9 error mean?
Can I fix a Daikin E9 error myself?
Is it safe to keep running the aircon with an E9 error?
What causes a Daikin E9 error?
Will a Daikin E9 error need a repair or a full replacement?
What should I send a technician about a Daikin E9 error?
Confirm the fault
Share the error code, model number and symptoms so we can assess the likely cause.
Not the right code?
Browse the full Daikin list or check a few codes in the same fault category.