Daikin Aircon F3 Error Code
Daikin F3 means high temperature discharge pipe control on EZi, iSmart ENVi and iSmile and other models. Do not reset F3; the manufacturer gives no customer reset procedure.
- What it means
- High temperature discharge pipe control on EZi, iSmart ENVi and iSmile and other models. Other Daikin models list a different meaning for F3; match the model first.
- Is it serious?
- Yes. Daikin F3 is a high-severity refrigerant or pressure fault. Have it diagnosed before relying on the unit.
- Can I keep running it?
- Do not reset F3; the manufacturer gives no customer reset procedure. Note the code and arrange diagnosis against the matching service manual. Any homeowner step for F3 depends on which model you have.
- Is it worth repairing?
- Whether Daikin F3 is worth repairing depends on the unit's age, the part that has failed, and that repair's cost against a new unit. For this fault type the part is usually in the refrigerant circuit. A leak has to be found and sealed before any gas goes in, and the leak's location sets most of the cost. The code names the fault, not the failed part, so measure before you decide on F3.Daikin by age, from our Daikin page:
Daikin repair-or-replace guidance by system age System age Usual call Under 5 years Almost always worth repairing. 5–8 years Repair is still the default for most faults. 8–12 years Depends on the fault. Over 12 years Major component failures usually favour replacement. - What it costs to find out
- An on-site check in Singapore costs $30 and finds what is causing Daikin F3 before any repair is quoted. The fee is waived if you go ahead with the quoted work. Rates as of 20 Nov 2026, on our Pricing page.
What Does Daikin F3 Mean?
Daikin F3 means high temperature discharge pipe control on EZi, iSmart ENVi and iSmile and other models. Other Daikin models list a different meaning for F3; match the model first.
What Causes Daikin F3?
Daikin Simple Self-Diagnosis by Malfunction Code (SM-TS3) lists 3 causes for Daikin F3.
Defective discharge pipe thermistor.
Abnormal discharge pipe temperature.
Defective outdoor unit control PCB.
Which Daikin F3 Meaning Matches Your Unit?
Daikin F3 has more than one listed meaning. Your model, the system type and the unit that shows the code decide which one applies.
| Model / series | What it means | What to check first |
|---|---|---|
| EZi | High temperature discharge pipe control | Match this meaning to your model and the unit that shows the code, then use the checks below. |
| General RA self-diagnosis guide | Malfunction of discharge pipe temperature | Match this meaning to your model and the unit that shows the code, then use the checks below. |
| VRV X RXQ-A(N)R cooling only | Discharge-pipe temperature abnormality | Match this meaning to your model and the unit that shows the code, then use the checks below. |
- Model / series
- EZi
- What it means
- High temperature discharge pipe control
- What to check first
- Match this meaning to your model and the unit that shows the code, then use the checks below.
- Model / series
- General RA self-diagnosis guide
- What it means
- Malfunction of discharge pipe temperature
- What to check first
- Match this meaning to your model and the unit that shows the code, then use the checks below.
- Model / series
- VRV X RXQ-A(N)R cooling only
- What it means
- Discharge-pipe temperature abnormality
- What to check first
- Match this meaning to your model and the unit that shows the code, then use the checks below.
Show 4 more meanings
| Model / series | What it means | What to check first |
|---|---|---|
| F3-01 - master / F3-03 - slave 1 / F3-05 - slave 2 | Discharge temperature too high at R21T or R22T because a stop valve is closed or refrigerant is short | Open the stop valves and check the refrigerant amount. The alternating F3-01 display belongs to the master outdoor unit. |
| F3-20 - master / F3-21 - slave 1 / F3-22 - slave 2 | Compressor-casing temperature too high at R15T because a stop valve is closed or refrigerant is short | Open the stop valves and check the refrigerant amount. The alternating F3-20 display belongs to the master outdoor unit. |
| VRV 5-S R32 - F3 / VRV 5 Heat Recovery R32 - F3 / VRV 5 Heat Pump R32 - F3 | Outdoor discharge-temperature malfunction | Check for a closed outdoor stop valve or insufficient refrigerant charge. |
| ERA-AYF AHU / air curtain | Discharge-pipe or compressor-casing temperature too high (F3-01/20) | Match this meaning to your model and the unit that shows the code, then use the checks below. |
- Model / series
- F3-01 - master / F3-03 - slave 1 / F3-05 - slave 2
- What it means
- Discharge temperature too high at R21T or R22T because a stop valve is closed or refrigerant is short
- What to check first
- Open the stop valves and check the refrigerant amount. The alternating F3-01 display belongs to the master outdoor unit.
- Model / series
- F3-20 - master / F3-21 - slave 1 / F3-22 - slave 2
- What it means
- Compressor-casing temperature too high at R15T because a stop valve is closed or refrigerant is short
- What to check first
- Open the stop valves and check the refrigerant amount. The alternating F3-20 display belongs to the master outdoor unit.
- Model / series
- VRV 5-S R32 - F3 / VRV 5 Heat Recovery R32 - F3 / VRV 5 Heat Pump R32 - F3
- What it means
- Outdoor discharge-temperature malfunction
- What to check first
- Check for a closed outdoor stop valve or insufficient refrigerant charge.
- Model / series
- ERA-AYF AHU / air curtain
- What it means
- Discharge-pipe or compressor-casing temperature too high (F3-01/20)
- What to check first
- Match this meaning to your model and the unit that shows the code, then use the checks below.
What Does a Technician Check for Daikin F3?
Before quoting parts for Daikin F3, a technician should confirm F3 exactly and record which controller, gateway, or unit reported it.
Match the indoor and outdoor model stickers, and the unit that shows the code, to the models the manual covers.
Follow the matching service-manual procedure and keep measured test evidence before naming a failed part.
Will Daikin F3 Need a Repair or a New Unit?
Daikin F3 confirms the fault label the manufacturer lists, not a failed part or repair procedure. Match the installed model to its service manual and require measured diagnostic evidence before approving parts, settings, or refrigerant work.