Daikin Aircon LC Error Code
Daikin LC means transmission fault between control PCB and inverter PCB on SkyAir and VRV models. Do not reset LC; the manufacturer gives no customer reset procedure.
- What it means
- Transmission fault between control PCB and inverter PCB on SkyAir and VRV models. Other Daikin models list a different meaning for LC; match the model first.
- Is it serious?
- Yes. Daikin LC is a high-severity communication fault. Have it diagnosed before relying on the unit.
- Can I keep running it?
- Do not reset LC; the manufacturer gives no customer reset procedure. Note the code and arrange diagnosis against the matching service manual. Any homeowner step for LC depends on which model you have.
- Is it worth repairing?
- Whether Daikin LC is worth repairing depends on the unit's age, the part that has failed, and that repair's cost against a new unit. For this fault type the part is usually in the signal link between the units. A loose terminal or damaged signal wire is a targeted repair; a failed board is replaced, not repaired. The code names the fault, not the failed part, so measure before you decide on LC.Daikin by age, from our Daikin page:
Daikin repair-or-replace guidance by system age System age Usual call Under 5 years Almost always worth repairing. 5–8 years Repair is still the default for most faults. 8–12 years Depends on the fault. Over 12 years Major component failures usually favour replacement. - What it costs to find out
- An on-site check in Singapore costs $30 and finds what is causing Daikin LC before any repair is quoted. The fee is waived if you go ahead with the quoted work. Rates as of 20 Nov 2026, on our Pricing page.
What Does Daikin LC Mean?
Daikin LC means transmission fault between control PCB and inverter PCB on SkyAir and VRV models. Other Daikin models list a different meaning for LC; match the model first.
What Causes Daikin LC?
Daikin Simple Self-Diagnosis by Malfunction Code (SM-TS3) lists 3 causes for Daikin LC.
Defective connection between inverter PCB and control PCB.
External noise factor.
Defective inverter compressor.
Which Daikin LC Meaning Matches Your Unit?
Daikin LC has more than one listed meaning. Your model, the system type and the unit that shows the code decide which one applies.
| Model / series | What it means | What to check first |
|---|---|---|
| General RA self-diagnosis guide | Transmission fault between control PCB and inverter PCB | Match this meaning to your model and the unit that shows the code, then use the checks below. |
| VRV X RXQ-A(N)R cooling only | Transmission error between the inverter PCB and outdoor main PCB | Match this meaning to your model and the unit that shows the code, then use the checks below. |
| LC-14 - master / LC-15 - slave 1 / LC-16 - slave 2 | Outdoor inverter INV1 transmission trouble at main PCB connectors X20A, X28A, or X40A | Check the connection. The alternating LC-14 display belongs to the master outdoor unit. |
- Model / series
- General RA self-diagnosis guide
- What it means
- Transmission fault between control PCB and inverter PCB
- What to check first
- Match this meaning to your model and the unit that shows the code, then use the checks below.
- Model / series
- VRV X RXQ-A(N)R cooling only
- What it means
- Transmission error between the inverter PCB and outdoor main PCB
- What to check first
- Match this meaning to your model and the unit that shows the code, then use the checks below.
- Model / series
- LC-14 - master / LC-15 - slave 1 / LC-16 - slave 2
- What it means
- Outdoor inverter INV1 transmission trouble at main PCB connectors X20A, X28A, or X40A
- What to check first
- Check the connection. The alternating LC-14 display belongs to the master outdoor unit.
Show 7 more meanings
| Model / series | What it means | What to check first |
|---|---|---|
| LC-19 - master / LC-20 - slave 1 / LC-21 - slave 2 | Outdoor inverter FAN1 transmission trouble at main PCB connectors X20A, X28A, or X40A | Check the connection. The alternating LC-19 display belongs to the master outdoor unit. |
| LC-24 - master / LC-25 - slave 1 / LC-26 - slave 2 | Outdoor inverter FAN2 transmission trouble at main PCB connectors X20A, X28A, or X40A | Check the connection. The alternating LC-24 display belongs to the master outdoor unit. |
| LC-30 - master / LC-31 - slave 1 / LC-32 - slave 2 | Outdoor inverter INV2 transmission trouble at main PCB connectors X20A, X28A, or X40A | Check the connection. The alternating LC-30 display belongs to the master outdoor unit. |
| LC-33 - master / LC-34 - slave 1 / LC-35 - slave 2 | Transmission trouble between the main PCB and sub PCB at connectors X20A, X2A, or X3A | Check the connection. The alternating LC-33 display belongs to the master outdoor unit. |
| VRV 5-S R32 - LC | Shut-off PCB transmission trouble or disconnection | Check the outdoor-unit to INV1 or FAN1 inverter transmission connection. |
| VRV 5 Heat Recovery R32 - LC / VRV 5 Heat Pump R32 - LC | Outdoor-unit to inverter transmission trouble | Check the outdoor inverter, fan, and main-to-sub PCB transmission connections. |
| ERA-AYF AHU / air curtain | Inverter or outdoor-fan transmission fault (LC-14/19/24) | Match this meaning to your model and the unit that shows the code, then use the checks below. |
- Model / series
- LC-19 - master / LC-20 - slave 1 / LC-21 - slave 2
- What it means
- Outdoor inverter FAN1 transmission trouble at main PCB connectors X20A, X28A, or X40A
- What to check first
- Check the connection. The alternating LC-19 display belongs to the master outdoor unit.
- Model / series
- LC-24 - master / LC-25 - slave 1 / LC-26 - slave 2
- What it means
- Outdoor inverter FAN2 transmission trouble at main PCB connectors X20A, X28A, or X40A
- What to check first
- Check the connection. The alternating LC-24 display belongs to the master outdoor unit.
- Model / series
- LC-30 - master / LC-31 - slave 1 / LC-32 - slave 2
- What it means
- Outdoor inverter INV2 transmission trouble at main PCB connectors X20A, X28A, or X40A
- What to check first
- Check the connection. The alternating LC-30 display belongs to the master outdoor unit.
- Model / series
- LC-33 - master / LC-34 - slave 1 / LC-35 - slave 2
- What it means
- Transmission trouble between the main PCB and sub PCB at connectors X20A, X2A, or X3A
- What to check first
- Check the connection. The alternating LC-33 display belongs to the master outdoor unit.
- Model / series
- VRV 5-S R32 - LC
- What it means
- Shut-off PCB transmission trouble or disconnection
- What to check first
- Check the outdoor-unit to INV1 or FAN1 inverter transmission connection.
- Model / series
- VRV 5 Heat Recovery R32 - LC / VRV 5 Heat Pump R32 - LC
- What it means
- Outdoor-unit to inverter transmission trouble
- What to check first
- Check the outdoor inverter, fan, and main-to-sub PCB transmission connections.
- Model / series
- ERA-AYF AHU / air curtain
- What it means
- Inverter or outdoor-fan transmission fault (LC-14/19/24)
- What to check first
- Match this meaning to your model and the unit that shows the code, then use the checks below.
What Does a Technician Check for Daikin LC?
Before quoting parts for Daikin LC, a technician should confirm LC exactly and record which controller, gateway, or unit reported it.
Match the indoor and outdoor model stickers, and the unit that shows the code, to the models the manual covers.
Follow the matching service-manual procedure and keep measured test evidence before naming a failed part.
Will Daikin LC Need a Repair or a New Unit?
Daikin LC confirms the fault label the manufacturer lists, not a failed part or repair procedure. Match the installed model to its service manual and require measured diagnostic evidence before approving parts, settings, or refrigerant work.