Skip to main content
snowflakeaircon.sg

Room Temperature Stratification: The Air at Your Ankles

Air in a closed room sorts itself by density, warm above cool. A wall unit samples the top of that arrangement, and the people sit at the bottom of it. Both readings are honest, and they describe different rooms.

By Team Snowflake | Updated 16 Sept 2026

A closed room sorts itself by height

Air arranges itself by density and holds that arrangement. Warmer air carries less mass in the same volume, settling above cooler air. Left undisturbed, a room becomes a stack of bands instead of one body of air at one temperature.

Nothing inside a still room undoes that sorting. The denser air is already at the bottom, so no imbalance drives a return flow. Stirring has to arrive from outside, which in a flat means a fan, an open door, or somebody walking through.

Every warm object in the space feeds that stack. ASHRAE defines a stratified zone as one where air movement is driven entirely by buoyancy from convective heat sources. A person is such a source, so is a laptop, a router, a downlight, or a patch of floor that took the afternoon sun.

Each source launches a plume, and the plume changes as it climbs. ASHRAE's chapter on space air diffusion describes a thermal plume rising by natural convection: it draws in surrounding air as it climbs, growing in volume and slowing down. Warm air leaves the source, collects room air on the way up, and delivers the mixture to the ceiling.

The band near the ceiling therefore holds the room's own heat, carried there by a process that runs whether the aircon is on or off. Switching a unit on adds a second flow working against the first. Where the room settles is the outcome of the two, and neither is under the remote's control.

The comfort standards give this a name

Vertical layering appears in the standards as a recognised defect. ISO 7730 lists four common causes of local thermal discomfort: draught, radiant asymmetry from hot or cold surfaces, cold or warm floors, and an abnormally high vertical temperature difference between the head and the ankles.

Naming it that way is the useful part. The standard never asks what a room averages. It asks what the difference is between two heights on one seated person, and a single reading taken high on a wall has no way to answer that question.

The machine measures one plane, and the maker knows it

A wall unit reads the air arriving at its own intake, high on the wall. In a room being cooled, that is the warmest band in the space, and the opposite end of the stack from everybody in the room.

Manufacturers write this down in their own service literature. Daikin's manual for inverter wall-mounted splits defines room temperature as the temperature of the lower part of the room, and lists room thermistor temperature separately. The manual states the two differ, depending on the indoor unit type and installation condition.

What the control does about it is the interesting half. The same manual says temperature control uses a target temperature adjusted for the indoor unit together with what the thermistor detects: the board applies an assumed offset between the plane it can measure and the plane people occupy.

An assumed offset is a factory figure for that model, not a measurement of this flat. A room that layers more heavily than the assumption gets the same correction as one that layers less. So when a display reports the room has reached its target, that claim is narrower than it looks.

ASHRAE Standard 55 fixes its own planes for judging comfort. Ankle level is 0.1 m above the floor, and head level is 1.1 m for a seated occupant and 1.7 m for a standing one. The tallest still sits below the intake of a wall unit in an ordinary flat.

Two honest numbers, one unresolvable argument

Two people in the same room can disagree without either being wrong. Somebody standing has their head near the top of the range the standard covers, while somebody on a floor cushion has their whole body inside the bottom of it. They are reporting different air.

Checking the remote settles none of it. The remote reports the machine's plane, and the disagreement belongs to a different one. Resolving it takes a thermometer placed where the complaint is happening, which nobody does, because the display already gives a number that feels authoritative.

What makes the layering steep

The gradient is a balance, and both sides of it move. ASHRAE states that the amount of stratification in a room is determined primarily by the balance between total room airflow and heat load. Push more air across the room and the bands blend together. Add heat, or spread it further up the height of the room, and they separate again.

Where the heat sits matters as much as the total quantity. Researchers at Aalto University and Halton measured air temperature profiles at ten heights in a test room built at two ceiling heights. With low-level sources, most of the gradient sat inside the occupied zone regardless of room height. Room height mattered when the heat loads were high up.

That study examined displacement ventilation, a design that sets out to stratify a room on purpose, so its numbers do not transfer to a wall split. What carries over is the point about heat sources: their height decides where the layering lands, which is why two rooms with the same cooling load can feel different.

Glazing acts on both sides of the balance at once. Sun through a window warms the floor and furniture, and those surfaces behave as low-level sources feeding the occupied zone. A tall window admits that heat across more of the room's height, so the stack is fed at several levels instead of one.

Ceiling height sets the size of the reservoir. More volume above head height means more air the outlet has to turn over before the lower band improves, and that volume is fixed on the day the flat is built.

None of these five is a fault, which is what makes the conversation difficult. Each is a property the flat already had before any unit was fitted. A machine can work against them. It cannot remove them.

  • What the room has
    People and equipment at seat height
    What it does to the layering
    Plumes rise through the occupied zone and warm it as they climb
    Whether mixing can undo it
    Yes, this is precisely what mixing is for
  • What the room has
    Downlights and a hot ceiling void
    What it does to the layering
    Heat enters above head height and stays above it
    Whether mixing can undo it
    Partly, and only where the supply reaches that band
  • What the room has
    A tall window taking direct sun
    What it does to the layering
    Warm surfaces feed the stack across the room's full height
    Whether mixing can undo it
    Partly, and the load returns every afternoon
  • What the room has
    Fan held on its quietest setting
    What it does to the layering
    Less air crosses the room, so the bands hold their shape
    Whether mixing can undo it
    Yes, and the setting is what created them
  • What the room has
    A ceiling well above head height
    What it does to the layering
    More air sits above the people than one outlet can turn over
    Whether mixing can undo it
    No, this one is set by the room

The consequence sits below the sensor

A room can satisfy its sensor and still fail the people inside it. That is the cost of the gradient, and it never surfaces as a fault code, a pressure reading, or anything a technician can put on an invoice.

The ISO 7730 model scores dissatisfaction from vertical temperature difference only when temperature rises with height. People are less sensitive when it falls instead. ASHRAE Standard 55 says it more bluntly. Stratification in the opposite direction is rare, perceived more favourably, and not addressed by the standard.

Cooling reliably produces the direction people mind. Cold air is denser, settling low while the warm band stays high, which leaves the head in warmer air than the ankles. Producing the reverse takes a warm floor, which is why the standards treat it as unusual.

The requirement was written for exactly this occupant. ASHRAE 55 applies its local discomfort limits to people with clothing insulation below 0.7 clo and metabolic rates below 1.3 met, a pairing it calls lightly clothed and near-sedentary. A household sitting in a flat on a warm evening fits it without trying.

No single figure defines how much layering is too much. ASHRAE 55 sets the limit as an air temperature gradient between head and ankle level, and that limit moves with whole-body thermal sensation: the same layering is judged differently depending on how warm the person feels. The limit is drawn where at most five percent of a room would be dissatisfied.

Why none of this reads as a machine fault

Nothing in the system registers a failure. The compressor reached its target, the sensor reported honestly, and airflow matched the setting it was given. A visit that only asks the machine questions finds nothing wrong, because the machine behaves correctly at the one height it can see.

That is also why the complaint survives a service. Cleaning a coil restores capacity, and capacity was never the constraint. A household that expected the wash to fix a seated-height problem gets the same room back, plus a reason to distrust the next recommendation.

Mixing is the lever, and the room can outrun it

Mixing is what removes a gradient, and a split system has only one route to it: the supply must reach the lower band and fold it into the upper. Whether it does is a property of the room and the mounting, and it turns on why cold air runs along the ceiling.

An overhead system is designed to prevent layering, not tolerate it. ASHRAE sorts room air distribution into mixed, fully stratified and partially mixed types, placing overhead distribution in the mixed group, defined as producing little or no thermal stratification within the space. A wall split in a Singapore flat belongs to that group by design.

So persistent bands in an ordinary flat say the mixing has stopped, not that layering is normal for this equipment. Usually it stopped because somebody turned it off. Quiet settings, sleep modes and draught-free modes all reduce air movement, and reduced air movement is the exact condition layers need to survive.

The standards treat moving air as changing the question. ASHRAE 55 exempts a space from its vertical gradient requirement where elevated air speed delivers comfort. Air crossing the occupants is a different route to the same result, and the gradient limit was written for still conditions.

In a tall space this stops being a servicing question and becomes a design one. ASHRAE treats stratification height, where the upper mixed zone begins, as a design quantity in stratified and partially mixed systems. A wall split gives nobody a way to place it. Given enough volume above the occupied zone, one high-level outlet cannot turn the room over, and bands form regardless of the machine.

Say that out loud before money is spent. A chemical wash does not change the height of a room. Neither does more capacity, and neither does gas. Where a quote answers a seated-height complaint with any of the three, ask what was measured at seated height beforehand. If nothing was, the quote answers a question nobody asked.

What to establish before agreeing to anything

Two thermometers and one hour settle most of this. Place one near the indoor unit and one beside where the complaint happens, run the room normally, and note both figures at the same moment. Record the fan setting and mode as well, since the figures depend on them.

Then repeat it with the fan raised and every quiet mode off. A gap that closes was a mixing problem, and mixing costs nothing to change. A gap that holds in a high-ceilinged room was built into the flat, and no service visit moves it.

Common questions

Why is the air near the ceiling warmer than at floor level?
Warm air is less dense and settles above cooler air, so a still room forms bands by height. People, equipment and sunlight keep feeding the upper band while the aircon samples it.
Why does a room feel warm when the display shows the set temperature?
The unit reads the air arriving at its own intake, high on the wall, and applies a fixed offset for the lower part of the room. Heavier layering than the factory assumption leaves the occupied level short of the target.
Will a chemical wash settle a warm spot at seated height?
Usually not, because capacity was not the constraint. Cleaning restores cooling output, while the gap between head and ankle comes from mixing and room layout, so read both heights before booking work.

Sources

  1. Grilles and Diffusers Engineering Guidelines

    Titus HVAC · Checked

    Titus gives the ankle-to-head gradient limit and floor stratification.

  2. Service Manual No. OBH515 (Indoor Unit) — MSZ-GE22VA to MSZ-GE71VA Split-Type Air Conditioners

    Mitsubishi Electric Corporation · Checked

    The wall unit's room thermistor samples air at the unit itself.

Ready to get started?

Tell us what’s going on. Symptoms, setup, photos, anything we should know. We’ll assess and come back with the right next step.

WhatsApp us