What aircon does a server or comms room need?
It needs a unit that keeps the equipment inside its temperature and humidity range day and night, and something that takes over when that unit fails. IBM's design criteria, drawn from ASHRAE's thermal guidelines, recommend 18 to 27°C with humidity no higher than 60%.
Office comfort is a different job, set by people rather than racks. For that side of the floor, see office aircon comfort.
| Setup | What it gives | What to ask before choosing |
|---|---|---|
| One split unit | Cooling for a small room, with nothing behind it | What happens to the room while it is down |
| A unit from a technical-room range | Ranges sold for server rooms and telecom shelters | Whether the controller offers rotation, standby and a fault alert |
| Two units on rotation | One runs, one waits and takes over on a fault | Whether each unit alone can carry the full heat load |
| A precision cabinet | Close control of temperature and humidity | Whether the equipment really needs that control |
One unit or two: what decides redundancy
Two units make sense when the equipment cannot stop while the aircon is repaired. Mitsubishi Electric's data-centre page puts it plainly: server rooms run continuously, so cooling must continue even when the climate system fails.
Daikin Europe states that duty rotation comes standard with its Sky Air remote control. The running unit hands over to the standby after set periods, takeover on a fault is automatic, and an emergency repair alert goes out. Ask whether the controller offered in Singapore does the same.
A standby aircon unit only protects the room if it can cool the whole load alone. Size each unit for the full heat of the rack, not half of it.
Humidity and nonstop running in Singapore
Singapore's air is the harder half of the job. Singapore's Meteorological Service gives a mean annual relative humidity around 82%, rising above 90% before sunrise, well over the 60% ceiling in IBM's recommended range.
Comms room cooling therefore has to dry the air as well as cool it, so keep the door shut and the room sealed from the corridor. Mitsubishi Electric describes precision cabinets as the choice when constant temperature and humidity are required.
Ask for a unit rated for continuous duty. Mitsubishi Electric Trane in the US lists one outdoor unit for 24-hour operation at 100% rated capacity, and Mitsubishi Electric uses inverter compressors for efficiency in 24/7 running; check the rating of the model quoted here.
Servicing it, and what happens when it fails
A unit that never switches off still needs its filters cleaned. Daikin Australia's general rule is every two weeks, and more often in dusty rooms. With two units on rotation, one can be serviced while the other carries the room.
With a single unit, a fault means the room warms with no backup. IBM lists 32°C as the top of the allowable range for class A1 equipment. A room temperature alert gives time to act before that point.
If the wider office is short of cooling as well, read about an office cooling shortfall first.
Common questions
What temperature should a small server room be kept at?
Do I need two aircon units for a comms room?
How often should a server room aircon be serviced?
Why does humidity matter in a Singapore server room?
Sources
Sources checked .
- IBM environmental design criteria (ASHRAE thermal guidelines)
- Mitsubishi Electric: air conditioning for data centres
- Daikin infrastructure and data centre cooling
- Mitsubishi Electric Trane: critical cooling for data centres
- Daikin: how often to clean aircon filters
- Meteorological Service Singapore: climate of Singapore