Server Room Aircon: Cooling a Comms Room That Runs All Day

A server or comms room needs aircon that holds the equipment between 18 and 27°C around the clock, plus a plan for the hour that unit stops. The choices are the unit type, a second unit for backup, and servicing.

On this page

What aircon does a server or comms room need?

It needs a unit that keeps the equipment inside its temperature and humidity range day and night, and something that takes over when that unit fails. IBM's design criteria, drawn from ASHRAE's thermal guidelines, recommend 18 to 27°C with humidity no higher than 60%.

Office comfort is a different job, set by people rather than racks. For that side of the floor, see office aircon comfort.

What aircon does a server or comms room need? summary table
SetupWhat it givesWhat to ask before choosing
One split unitCooling for a small room, with nothing behind itWhat happens to the room while it is down
A unit from a technical-room rangeRanges sold for server rooms and telecom sheltersWhether the controller offers rotation, standby and a fault alert
Two units on rotationOne runs, one waits and takes over on a faultWhether each unit alone can carry the full heat load
A precision cabinetClose control of temperature and humidityWhether the equipment really needs that control

One unit or two: what decides redundancy

Two units make sense when the equipment cannot stop while the aircon is repaired. Mitsubishi Electric's data-centre page puts it plainly: server rooms run continuously, so cooling must continue even when the climate system fails.

Daikin Europe states that duty rotation comes standard with its Sky Air remote control. The running unit hands over to the standby after set periods, takeover on a fault is automatic, and an emergency repair alert goes out. Ask whether the controller offered in Singapore does the same.

A standby aircon unit only protects the room if it can cool the whole load alone. Size each unit for the full heat of the rack, not half of it.

Humidity and nonstop running in Singapore

Singapore's air is the harder half of the job. Singapore's Meteorological Service gives a mean annual relative humidity around 82%, rising above 90% before sunrise, well over the 60% ceiling in IBM's recommended range.

Comms room cooling therefore has to dry the air as well as cool it, so keep the door shut and the room sealed from the corridor. Mitsubishi Electric describes precision cabinets as the choice when constant temperature and humidity are required.

Ask for a unit rated for continuous duty. Mitsubishi Electric Trane in the US lists one outdoor unit for 24-hour operation at 100% rated capacity, and Mitsubishi Electric uses inverter compressors for efficiency in 24/7 running; check the rating of the model quoted here.

Servicing it, and what happens when it fails

A unit that never switches off still needs its filters cleaned. Daikin Australia's general rule is every two weeks, and more often in dusty rooms. With two units on rotation, one can be serviced while the other carries the room.

With a single unit, a fault means the room warms with no backup. IBM lists 32°C as the top of the allowable range for class A1 equipment. A room temperature alert gives time to act before that point.

If the wider office is short of cooling as well, read about an office cooling shortfall first.

Common questions

What temperature should a small server room be kept at?
A small server room is usually held between 18 and 27°C, the recommended range in IBM's design criteria, which come from ASHRAE's thermal guidelines. The same criteria keep humidity at or below 60%. Where the equipment maker publishes a stricter specification, that specification applies.
Do I need two aircon units for a comms room?
Two aircon units are worth installing when the equipment in a comms room cannot stop while one unit is repaired. Daikin Europe's Sky Air controls run a duty rotation, hand over automatically on a fault and send a repair alert. Each unit must be able to cool the full load alone.
How often should a server room aircon be serviced?
Server room aircon filters follow the rule Daikin Australia gives for any indoor unit: clean them every two weeks, and more often where the room is dusty. A unit that runs day and night has no quiet hours, so a second unit on rotation lets one be serviced while the other cools.
Why does humidity matter in a Singapore server room?
Humidity matters because Singapore's mean annual relative humidity is around 82%, while IBM's recommended range for IT equipment tops out at 60%. The aircon has to remove moisture as well as heat, so a sealed room with the door kept shut holds the range far more easily.