Skip to main content

Cassette Not Cooling: Stuck Gas-Flow Valve, Not Compressor

A stuck expansion valve is the suspect when a gas top-up makes no difference to a cassette's cooling. Stuck part-closed, this gas-flow control starves the coil while the charge and compressor are fine.

Daikin · Cassette

A thermometer at a cassette outlet reading 27.8. Warm supply air says the coil is not getting enough refrigerant; pressures and pipe temperatures tell a stuck valve from a low charge or a failed compressor.

What It Looks Like

Weak cooling in an industrial office even with a correct refrigerant charge, after earlier top-ups brought no relief. Airflow feels brisk and the coil is clean. Cooling runs continuously through Singapore afternoon heat without pulling room temperature down.

Commonly misread as

A leak that nobody can find, with the system needing gas again and again.

What Separates the Causes

A correct charge alongside poor cooling separates the quantity of refrigerant from the rate it moves. Both produce weak cooling; only one is a shortage. With the charge correct and airflow fine on both sides, what remains is a restriction in the circuit, and a metering valve stuck part-closed produces exactly this symptom.

  • A previous top-up giving no improvement makes another refill a poor first step.

  • A correct charge on measurement confirms the quantity in the system is not the problem.

  • Normal airflow and a clean coil remove the air side from consideration on both halves.

  • Pressures consistent with a restriction rather than a shortage place the fault at the flow control itself.

A flow-control valve meters refrigerant into the indoor coil, modulating to match tropical heat load. Internal deposit, moisture or mechanical wear can freeze it part-closed, starving the coil regardless of how full the circuit sits. Another top-up solves nothing and risks overcharging the system.

What Fixes It and How to Verify

Free or replace the valve and leave the charge as it is. Where a top-up made no difference, do not authorise a second one: it loads the system with refrigerant it never needed.

How to tell it worked

Measure output after the valve work on the charge it already holds. Correct cooling on that same charge confirms the quantity was never the issue.

Before You Approve a Quote

No improvement after a top-up is itself evidence

  • Weak cooling comes from too little refrigerant or from refrigerant moving too slowly. Only one is a top-up.
  • If a top-up does not improve cooling, ask for measured evidence before agreeing to more refrigerant.
  • A flow-control valve stuck part-closed starves the coil while the system stays completely full.