Mitsubishi Electric · Cassette
A ceiling cassette opened at the return grille exposes the central fan wheel inside its circular housing. When a blade sits slightly off-centre on a loose clip, resonance across one speed band lets the tip graze the surround.
What It Looks Like
A rattle that comes and goes with the fan setting in an office running daily through tropical heat, loudest for whoever sits underneath. Cooling is unaffected and the outdoor unit sounds normal from outside.
Commonly misread as
Failing compressor bearings, which puts the whole outdoor unit up for replacement.
What Separates the Causes
Running the fan through its speeds takes two minutes and splits the problem in half. A sound belonging to the indoor fan changes with fan speed. A sound from the outdoor side does not, because the compressor runs at its own pace. The shape of that relationship then says which indoor part.
A rattle present at medium and absent at both low and high is not a wear pattern.
A compressor running smoothly at every indoor fan setting keeps the outdoor unit out of it.
A retaining clip shifted on the motor shaft lets the blade sit fractionally off-centre.
A noise confined to one speed band is a resonance acting on a loose part, not damage, and a loose part can be re-secured.
A blade sitting slightly off-centre on a loose clip runs close to its housing. Every spinning assembly has a band of speeds where it resonates, and in that band the blade vibrates enough for the tip to catch on every turn. Below and above it, the vibration settles and the tip clears. Silence on both sides of the band is what rules out a worn bearing, which would worsen with speed and never improve.
What Fixes It and How to Verify
With the cassette isolated, the clip is re-secured and the blade set to run true, then spun by hand to confirm no play remains. Nothing is replaced. Light marks where the tip grazed the housing are cosmetic.
How to tell it worked
Quiet at every speed, tested through the full range. A blade merely nudged off the housing is quiet at the setting that was noisy and catches at another.
Before You Approve a Quote
Noise at one speed and silence either side is a clearance
- Run the fan through every speed and note where the noise starts and stops. It takes two minutes.
- Wear gets worse the harder a part works. A noise that disappears at high speed is not wear.
- A sound that changes with fan speed belongs to the indoor fan, not to the compressor.