LG · Wall-mounted
A gauge manifold connected at an outdoor unit's service valves, with corrosion on the fittings. Salt and moisture attack these connections over years, and a top-up does not close the gap they open.
What It Looks Like
A CH35 code with cooling that fades over several weeks, cleared by a top-up and back within the month. A second top-up buys the same few weeks. The charge will not stay put.
Commonly misread as
Simple gas loss, which turns two top-ups into an open-ended cycle.
What Separates the Causes
Two top-ups that fade point to a leak, but CH35 can still be restricted indoor airflow, a fouled indoor coil or a sensor reading low. All three are cheaper to clear than a leak hunt, so they go first. With airflow normal and the sensor reading correctly, the outdoor pipework is where to look.
A clean filter and indoor coil with normal airflow remove the first of the three causes.
A pressure sensor that reads correctly when tested on its own removes the second.
Green oxidation on the gas line and liquid line fittings at the outdoor unit is visible before any test confirms it.
A bubble test locates the escape at the fitting where the gas line meets the outdoor valve. Clean, dry joints indoors rule out the other end.
Refrigerant escapes through corroded fittings at the outdoor unit. Moisture and airborne salt attack the connection surfaces over years, faster in coastal estates near open water than sheltered inland blocks. A top-up restores pressure against an opening that is still open, so the charge falls below the CH35 threshold within weeks.
What Fixes It and How to Verify
The leaking connection is repaired and leak-tested, and only then is the circuit charged to the model specification. Fittings installed together corrode together, so the neighbours are inspected while the unit is open. With the leak traced to the outdoor connection, no indoor coil or compressor work is needed.
How to tell it worked
The repaired joint passes a leak check, and CH35 stays away past the few weeks it used to take to return. A correct reading on the day of charging proves nothing about the leak.
Before You Approve a Quote
A top-up that keeps fading is a leak, not a charge problem
- A CH35 code on its own does not confirm a leak. Ask whether indoor airflow and the pressure sensor were cleared first.
- Corrosion starts at the outdoor pipe connections, and green staining on the fittings is visible without any instrument.
- A top-up with no location named is not a repair. Ask where the leak was traced before paying for more gas.