Inside a Yishun HDB bedroom, the split unit runs nonstop every night yet blows flat, lukewarm air that fails to chill the bed. Routine filter rinsing barely changed airflow strength, raising worries that the R32 gas had run low.
- Setup
- LG Wall-mounted4-6 yearsHDBYishun
- Misread as
- Spending S$120 to S$200 on an unneeded R32 top-up that overcharges a tight LG refrigerant loop while leaving coil biofilm behind.
- Check first
- Showing the live R32 suction pressure needle holding steady inside normal range on the manifold before opening the indoor cover to expose biofilm
- Actual finding
- Sticky biofilm sealing the LG indoor evaporator fins and restricting airflow while the sealed R32 circuit sits squarely within factory pressure spec
- Scope saved
- Servicing or adjustment with no parts replaced

What Else Produces This
Warm bedroom air triggers frequent assumptions about low refrigerant. Checking live suction pressure first gives hard numerical proof before anyone opens a gas cylinder.
Connecting the gauge manifold to the outdoor LG service port under steady cooling shows R32 suction pressure holding squarely within normal specification.
Feeling the outdoor suction valve confirms brisk cold return back to the condenser, verifying full refrigerant circulation.
Lifting the indoor bedroom chassis cover exposes a dark, tacky coat of humid biofilm bridging the aluminum evaporator fins.
Inspecting the inner drain tray and blower channel shows grey jelly buildup slowing air movement across the lower coil rows.
Why It Happens
Years of humid Yishun nights turned fine bedroom dust and moisture into a sticky biofilm layer across the evaporator face. That organic film insulated the cold fins from room air and narrowed air gaps while the sealed R32 loop stayed completely tight.
What Resolution Involves
Disconnect the manifold gauges cleanly with zero R32 gas added. Hang a protective wash sheet under the LG fan coil, mist dedicated coil wash across the slimy aluminum fins and blower vanes, and rinse thoroughly with steam until bright metal shows through. Flush the loosened slime cleanly down the condensate drain line.
How to Tell It Worked
Power the Yishun unit back up at 23°C on mid speed and log vent cooling with a thermometer. Confirm crisp, fast-chilling airflow reaching across the room and clean, odour-free condensate flow out the drain.
Before You Approve a Quote
Verify live gas pressure before approving any R32 refill
- An R32 needle holding squarely in range proves the sealed LG gas circuit has no leak and needs zero refrigerant.
- Warm bedroom air paired with healthy operating pressure points straight to indoor evaporator fouling or airflow blockage.
- In-place chemical cleaning (S$80 single, S$60 each for 3+) strips slimy biofilm away and restores fast Singapore bedroom cooling.