On this page
How This Presents
Damp marks appear beside the service hatch of a Novena condo living room whenever the concealed ceiling system runs through humid evenings. Peering into the ceiling space reveals a metal drip tray suspended beneath the supply plenum, slowly filling with clear water. Room temperatures stay cold and airflow across every linear grille remains strong.
- Setup
- Mitsubishi Electric Ducted7-9 yearsCondoNovena
- Misread as
- Dreading a major condo ceiling hack to replace corroded ductwork or a leaking concealed evaporator coil.
- Check first
- Opening the ceiling access hatch during humid operation to trace droplets forming along exposed plenum edges

What Else Produces This
Clear water accumulating inside a secondary catch tray splits into a cracked main drain pan or cold-surface condensation. Opening the ceiling hatch under live cooling reveals where droplets actually originate.
Primary fan coil drain pan and condensate pipe flow freely with zero standing backup or slime obstruction.
Outer foil facing along the supply plenum bottom edge has peeled back, exposing strips of bare galvanised metal.
Heavy droplets form along the cold exposed flange and drip directly into the auxiliary tray beneath the duct.
Warm humid air drafts through unsealed service-shaft gaps into the ceiling void, keeping void humidity high.
Why It Happens
Ceiling voids in Novena condos sit warm beside riser shafts and hold damp Singapore air all year. Over time, foil tape along the duct plenum peels back and leaves thin gaps along corners and seams. Cold supply air chills that bare sheet metal until steady water drops form across the base.
What Resolution Involves
Switch off the system and wipe every wet duct corner and seam dry before resealing. Strip soaked foam patches and press fresh closed-cell lagging tight onto the bare metal. Tape every joint shut with foil tape, then drain and dry the catch tray below.
How to Tell It Worked
Run the Novena living-room unit on a low setting through a humid evening and check inside the ceiling hatch. Newly sealed duct seams stay dry to the touch, no water beads along the metal edges, and the drip tray stays bone dry.
Before You Approve a Quote
Catch trays hide active duct sweating until joints are resealed
- Water gathering in a secondary tray while the main drain pipe runs clear points to external sweating rather than a blocked drain.
- Warm ceiling spaces in humid Singapore flats quickly drench any small strip of exposed cold metal.
- Drying the plenum, replacing perished foam sheets, and vapour-sealing every joint stops condensation without duct replacement.