Daikin Aircon E4 Error Code

Confirm the listed meaning of Daikin E4, note the unit that shows the code and its model, and match the service manual before diagnosis. Match the model first; same-looking codes can point to different rows.

What does Daikin E4 mean?

Daikin E4 is listed as actuation of low pressure switch, low-pressure sensor activated, and low-pressure malfunction caused by a closed stop valve, refrigerant shortage, or an indoor-unit malfunction in fault lists for more than one model family, including VRV X RXQ-A(N)R cooling only, VRV IV+ REYQ / REMQ heat recovery, VRV 5-S RXYSA R32, VRV 5 Heat Recovery REMA / REYA R32, VRV 5 Heat Pump RYMA / RXYA R32, Sky Air FNA R32 - test-run diagnostic, and ERA-AYF AHU / air curtain. This meaning comes from the manufacturer's own diagnostic material. Do not collapse this code across model families; use the model, series, or system type to choose the right row. Confirm the exact model, series, or signal row before accepting a parts quote.

What to do now

Use these steps to record evidence and match the installed model to its service manual before diagnosis or a repair quote.

  • Record E4 and match the service manual

    Record E4 and stop there; the manufacturer gives no customer reset procedure. Arrange diagnosis with the matching service manual.

  • No manufacturer reset steps listed for E4

    Capture the complete E4 error code and model stickers first. The manufacturer lists the meaning but no customer reset procedure; do not treat a generic power-cycle as manufacturer guidance.

  • Send these to us

    E4 error code, a clear display photo, Daikin indoor and outdoor model stickers, the controller, gateway, or unit that reported the code, operating mode and affected area, and any power or setting changes made after the code appeared

Choose the listing that matches your unit

The same code has more than one listed meaning. Match the model family, the system type and the unit that shows the code before approving parts.

  • Code
    SkyAir
    What it means
    Actuation of low pressure switch
    What to check first
    Match this meaning to your installed model and the unit that shows the code, then use the checks below.
  • Code
    VRV X RXQ-A(N)R cooling only
    What it means
    Low-pressure sensor activated
    What to check first
    Match this meaning to your installed model and the unit that shows the code, then use the checks below.
  • Code
    E4-01 - master / E4-02 - slave 1 / E4-03 - slave 2
    What it means
    Low-pressure malfunction caused by a closed stop valve, refrigerant shortage, or an indoor-unit malfunction
    What to check first
    Open the stop valves, check refrigerant amount, and check the indoor-unit display or transmission wiring. The alternating E4-01 display belongs to the master outdoor unit.
  • Code
    VRV 5-S R32 - E4 / VRV 5 Heat Recovery R32 - E4 / VRV 5 Heat Pump R32 - E4
    What it means
    Outdoor low-pressure malfunction
    What to check first
    Check for a closed outdoor stop valve or insufficient refrigerant charge.
  • Code
    Sky Air FNA R32 - E4 (test-run diagnostic)
    What it means
    Stop valve is closed or an air inlet or outlet is blocked
    What to check first
    Confirm the indoor model is FNA25~60A2VEB(9), record the reporting controller, and follow the matching Daikin service procedure.
  • Code
    ERA-AYF AHU / air curtain
    What it means
    Low-pressure protection, refrigerant shortage, or closed stop valve (E4-01)
    What to check first
    Match this meaning to your installed model and the unit that shows the code, then use the checks below.

Guidance for your model

Notes that match the code to your exact model. Electrical, refrigerant, wiring, resistance and component checks are for a technician.

  • Detail
    Singapore / model note
    What it says
    Official Daikin SM-TS3 self-diagnosis row. Manual causes: Abnormal drop in low pressure; Defective low pressure sensor; Defective outdoor unit PCB.
  • Detail
    Singapore / model note
    What it says
    Official Daikin RXQ6-48A(N)R cooling-only service-manual row. Confirm the installed model and matching regional manual before diagnosis; this source is not claimed as universal across every Daikin VRV generation.
  • Detail
    Singapore / model note
    What it says
    Official Daikin 4PEN561154-1C overview row for REYQ8~20 and REMQ5U7Y1B VRV IV+ heat-recovery systems. The guide refers technicians to the service manual for the complete code list and detailed troubleshooting.

What to check before repair

The manufacturer's fault table gives the code's meaning, not a repair procedure. Capture evidence first; model-specific tests belong to the matching service manual.

  • You can check
    Photograph the complete E4 error code before taking any action.
    Technician should confirm
    Confirm E4 exactly and record which controller, gateway, or unit reported it.
  • You can check
    Capture the Daikin indoor and outdoor model stickers and identify which controller or unit reported it.
    Technician should confirm
    Match the indoor and outdoor model stickers, installed family, and reporting equipment to the source scope.
  • You can check
    The manufacturer provides no customer reset procedure. Preserve the evidence and use the matching service manual for any system action.
    Technician should confirm
    Follow the matching service-manual procedure and keep measured test evidence before naming a failed part.

Source-bounded repair decision

Daikin E4 confirms the fault label the manufacturer lists, not a failed part or repair procedure. Match the installed model to its service manual and require measured diagnostic evidence before approving parts, settings, or refrigerant work.

  • Whether the reporting controller or unit and exact installed model are confirmed.

  • What the matching service-manual procedure and measured tests show.

  • Whether the proposed repair names the evidence for the failed part or condition.

Daikin E4 questions

What does the Daikin E4 error mean?
Daikin E4 is listed as actuation of low pressure switch, low-pressure sensor activated, and low-pressure malfunction caused by a closed stop valve, refrigerant shortage, or an indoor-unit malfunction in fault lists for more than one model family, including VRV X RXQ-A(N)R cooling only, VRV IV+ REYQ / REMQ heat recovery, VRV 5-S RXYSA R32, VRV 5 Heat Recovery REMA / REYA R32, VRV 5 Heat Pump RYMA / RXYA R32, Sky Air FNA R32 - test-run diagnostic, and ERA-AYF AHU / air curtain. This meaning comes from the manufacturer's own diagnostic material. Do not collapse this code across model families; use the model, series, or system type to choose the right row. Confirm the exact model, series, or signal row before accepting a parts quote.
Can I fix a Daikin E4 error myself?
No. E4 needs a technician's measurement before parts are decided. Photograph the complete E4 error code before taking any action. Capture the Daikin indoor and outdoor model stickers and identify which controller or unit reported it.
Is it safe to keep running the aircon with an E4 error?
Record E4 and stop there; the manufacturer gives no customer reset procedure. Arrange diagnosis with the matching service manual.
What causes a Daikin E4 error?
Daikin E4 has a listed meaning that depends on the exact model and on which unit shows the code. Use the decoder on this page before assuming a specific cause.
Will a Daikin E4 error need a repair or a full replacement?
Daikin E4 confirms the fault label the manufacturer lists, not a failed part or repair procedure. Match the installed model to its service manual and require measured diagnostic evidence before approving parts, settings, or refrigerant work.
What should I send a technician about a Daikin E4 error?
Before booking, send: E4 error code, a clear display photo, Daikin indoor and outdoor model stickers, the controller, gateway, or unit that reported the code, operating mode and affected area, and any power or setting changes made after the code appeared.

Where to go next

Not the right code?

Browse the full Daikin list or check a few codes in the same fault category.

Read next

Use this quote-check guide only after the matching service manual identifies the diagnostic path.