Aircon Gas Leak at the Flare Joint or Coil: What Each Means

Where the leak is matters more than how much gas was lost. A leaking flare joint is usually a short fix at the pipe end; a leaking coil means replacing a large part, or the unit.

On this page

Flare joint or coil: what is the difference?

A flare joint is where the copper pipe is shaped and screwed onto the unit's valve. A leak there is usually repaired on the visit by cutting the flare and making a new one.

A coil leak is in the unit's heat exchanger itself. It is fixed by replacing the coil or the indoor unit, which costs more and may need a part ordered.

Flare joint leak or coil leak: repair and cost

Scroll to see more columns

Where the leak isMarket range in SingaporeOur rateHow it is repairedRisk after the repair
Flare joint at the indoor or outdoor unitFewer than three operators publish a flare repair price; access to the joint sets it.Quoted per jobFlare cut and remade, new flare nut, then vacuum and rechargeLow if the flare is remade properly
Indoor or outdoor coil$200–$1,800 per jobQuoted per jobCoil replaced, or the whole indoor unit, then vacuum and rechargeLow once replaced; patching a coil is not a lasting fix
Leak test to tell them apart$50–$180 per jobQuoted per jobPressure test and leak searchNone; it decides the repair

A flare joint is usually reached at the unit without opening walls. A coil job costs more on larger units and on models whose coil has to be ordered.

Market ranges: published rates from 4 Singapore operators. Checked 18 Nov 2026.

Our rates are from our rate card.

Signs that point one way or the other

Only the leak test settles it. A technician checks the joints first, because they are the cheapest place to find a leak.

Signs that point one way or the other summary table
SignPoints to
Oily residue at the pipe connection on the outdoor or indoor unitFlare joint
Leak started soon after an installation or relocationFlare joint
Cooling fades slowly over months, unit several years oldEither; coil more likely on an older unit
Leak test finds the joints tightCoil or a pipe section

Why a flare repair has to be done properly

Tightening a leaking flare nut is not a repair. Mitsubishi Electric's manual calls for the flare nut to be renewed and the pipe newly flared when a joint is remade.

Ask for the flare to be remade, then the circuit vacuumed and charged by weight. A joint that is only tightened may leak again.

When a coil leak means replacing the unit

If the unit is over ten years old or its coil is no longer made, a coil leak is the time to compare a new indoor unit or a whole new system. The guide on a leaking evaporator coil compares the two.

Common questions

What is a flare joint leak in an aircon?
A flare joint leak in an aircon is a gas leak where the copper pipe's flared end screws onto the unit's valve. It is one of the most common leak points and is usually repaired on the visit by cutting off the old flare, making a new one and fitting a new flare nut.
Is a coil leak worse than a flare joint leak?
Yes, in cost. A coil leak means replacing the coil or the whole indoor unit, which can need a part ordered, while a flare joint leak is usually fixed on the visit by remaking the flare. Either repair ends with the circuit vacuumed and recharged by weight.
Can a technician just tighten a leaking flare nut?
Tightening a leaking flare nut is not a lasting repair. Mitsubishi Electric's guidance is to renew the flare nut and make a new flare when a joint is remade. After that, the circuit should be vacuumed and charged by weight, so the leak and the gas loss are both dealt with.
How does a technician know if the leak is at the joint or the coil?
A technician pressurises the circuit and checks each joint first, because joints are the cheapest leak points to repair. If the joints hold, the leak is in the coil or a pipe section, and a further search along the run narrows it down before any part is replaced.