On this page
Summary
If renovation work has damaged mains wiring or the isolator, switch the unit off at the isolator and have the electrical side checked before running it again.
Likely Causes
- A cut signal cable rejoined in the wrong order stops the units communicating.
- A nicked communication wire causes an error that comes and goes.
- Fine renovation dust chokes the drain or loads the coil.

Quick Fault Summary
| Likely cause | What to check | Typical next step |
|---|---|---|
| Signal cable rejoined in the wrong order | The error appeared immediately after the works, not gradually. | A technician opens the joint made during the works, checks each conductor against its terminal, reterminates the cable correctly and tests communication. |
| Communication wire nicked but not cut through | The error comes and goes rather than showing constantly. | A technician tests continuity along the disturbed route to find where the signal weakens, then replaces that section rather than joining it, so the repair leaves no second weak point. |
| Renovation dust in the drain or on the coil | There is no error code, just leaking or weak airflow. | A technician clears the drain path and assesses how far dust has loaded the coil, then cleans it to the depth the loading warrants rather than wiping the face. |
- Likely cause
- Signal cable rejoined in the wrong order
- What to check
- The error appeared immediately after the works, not gradually.
- Typical next step
- A technician opens the joint made during the works, checks each conductor against its terminal, reterminates the cable correctly and tests communication.
- Likely cause
- Communication wire nicked but not cut through
- What to check
- The error comes and goes rather than showing constantly.
- Typical next step
- A technician tests continuity along the disturbed route to find where the signal weakens, then replaces that section rather than joining it, so the repair leaves no second weak point.
- Likely cause
- Renovation dust in the drain or on the coil
- What to check
- There is no error code, just leaking or weak airflow.
- Typical next step
- A technician clears the drain path and assesses how far dust has loaded the coil, then cleans it to the depth the loading warrants rather than wiping the face.
1. Signal Cable Rejoined in the Wrong Order
A constant communication error straight after Singapore BTO or resale HDB hacking usually means the indoor-to-ledge cable was cut and rejoined in the wrong core order.
How to Tell
An error present every time since the day of the works points to the rejoin. A nicked wire comes and goes, and dust gives no error code.
- The error appeared immediately after the works, not gradually.
- It shows every time the unit is switched on.
- The indoor unit powers up but the outdoor unit does not respond.
- Hacking or drilling happened along the trunking route.
How We Confirm It
A technician opens the joint made during the works, checks each conductor against its terminal, reterminates the cable correctly and tests communication.
A miswired rejoin gives the same error as a failed board. The joint is opened and reterminated first, then the board is tested.
Related Cases
2. Communication Wire Nicked but Not Cut Through
An error that comes and goes after renovation points to a wire grazed by a drill or blade but not cut through. The signal passes some of the time and drops when the weakened conductor shifts.
How to Tell
An error that comes and goes points to the nicked wire. A wrongly rejoined cable gives a constant error from the day of the works, and dust shows as a leak or weak airflow rather than a communication error.
- The error comes and goes rather than showing constantly.
- The unit had sometimes worked between errors.
- Recent drilling or hacking took place near the trunking.
- No damage is visible from outside the trunking.
How We Confirm It
A technician tests continuity along the disturbed route to find where the signal weakens, then replaces that section rather than joining it, so the repair leaves no second weak point.
Do not restart a unit if you suspect wiring damage. Send the error shown and where the work was done on WhatsApp.
Related Cases
3. Renovation Dust in the Drain or on the Coil
Leaking or weak cooling after condo or flat works with no error code means fine dust got past the filter. In humid air, plaster dust packs into drain sludge and blankets the coil fins.
How to Tell
No error code, with a leak or weak air after dusty works, points to dust. The electronics are fine, and the trigger is airborne dust rather than a damaged conductor.
- There is no error code, just leaking or weak airflow.
- Fine dust settled everywhere during the works.
- The unit ran while the renovation was in progress.
- Cooling dropped off around the same time.
How We Confirm It
A technician clears the drain path and assesses how far dust has loaded the coil, then cleans it to the depth the loading warrants rather than wiping the face.
Never leave the aircon running while hacking or sanding is happening. The unit pulls that dust straight onto the coil, which is what causes this in the first place.