Trunking Water Drip: Cracked Drain Elbow Behind Casing

A trunking drip that flushing does not stop is rarely a blockage. In an older HDB flat, a cracked drain elbow behind the casing leaks while the tray drains cleanly.

Mitsubishi Electric · Wall-mounted

The insulated drain outlet sits tucked beneath the indoor evaporator tray where it turns into the wall trunking. A hairline crack in an aged elbow leaks condensate directly into the casing channel even when the main line is clear.

What It Looks Like

Water forms below the trunking whenever the unit runs more than an hour, and returns after a drain flush. The indoor tray is not overflowing, which does not fit a blocked line.

Commonly misread as

The indoor unit needing replacement, because clearing the drain kept not working.

What Separates the Causes

A choke and a breach make the same puddle. A choked line backs water up until the tray overflows. A breach lets the tray drain and loses water further along. A tray that is not overflowing rules out the choke, so the job turns from flushing to tracing the water mark to where it starts.

  • An indoor tray draining normally, not overflowing, rules out a blockage upstream of it.

  • A water mark beginning at a bend, rather than at the unit, locates the escape instead of the drip.

  • A cracked elbow found at that bend explains the whole pattern with nothing else needed.

  • A pipe run clear after the elbow keeps the repair to one section instead of the full route.

PVC drain fittings age under years of daily condensation in Singapore flats, and a tight bend carries the stress, so an elbow cracks first. Water leaves the tray correctly and escapes at the crack into the trunking, which channels it to a low point where it drips. The visible drip sits downhill of the fault, sometimes well downhill.

What Fixes It and How to Verify

The cracked section is replaced and the joint sealed. The run past the elbow stays, because it passes a flush and nothing is gained by replacing pipe that works. A full re-run is for a route failing along its length, not at one bend.

How to tell it worked

Run water through the tray while watching the repaired bend, the trunking exit where the drip appeared, and the outlet. All three must behave before the trunking closes; a repair checked only at the repair is checked at the wrong end.

Before You Approve a Quote

The drip is downhill of the fault, not at it

  • A tray that is not overflowing rules out a blocked line. Flushing again proves the route carries water, not that it holds it.
  • Follow the water mark to where it starts, and open that section first.
  • Inside a covered run, water travels before it drips. The visible wet patch is not the fault.