On this page
Quick summary
Finding where the first wet bead forms separates three common Singapore aircon leaks fast. Mist on the front louvre signals humid room air. Wall drips under the casing point to a full drain tray, while damp PVC trunking warns of torn foam insulation.
How to Run a 3-Minute Dry-Tissue Water Trace Safely
Wipe the bottom lip of the unit, the painted wall below it, and the first metre of side trunking dry with kitchen paper first. Checking already soaked surfaces hides where moisture starts.
Run normal cool mode for 10 minutes while watching from floor level with a phone torch. Staying below the casing keeps drips from running down your arm.
- Dab dry paper gently across the outer plastic louvre face. Check whether fine mist beads coat the vent evenly.
- Press a fresh dry sheet against the narrow seam behind the unit. Wet streaks here point to rear pan overflow.
- Slide a third dry tissue along the bottom seams of white wall trunking heading toward the toilet.
- Take one wide photo showing the wet zone and any ajar windows or doors nearby.
Pass or Fail Self-Check to Match Drip Spots with Real Causes
Singapore rooms often sit past 80% humidity. Cold vents and exposed pipes sweat fast whenever warm hallway air hits chilled surfaces.
| What you see | What it usually means | Safe DIY step or book S$30 check |
|---|---|---|
| Fine dew beads across the louvre blades when window or bedroom door stays ajar | Humid room air hitting cold vent surfaces below dew point | Pass if closing doors and raising set point to 25°C stops misting |
| Steady drips falling from the left or right bottom casing corner | Algae jelly blocking the front drain tray outlet or choked PVC condensate line | Turn off cool mode and book general or chemical servicing with drain vacuuming |
| Water streaking straight down the painted wall behind the indoor casing | Blocked rear secondary drain tray or loose rear pipe connection | Switch unit off; book chemical overhaul or S$30 on-site check (waived on repair) |
| Damp seams or cold beads weeping midway along horizontal PVC trunking | Cracked Armaflex foam insulation, missing tape, or uninsulated drain line | Leave trunking sealed and book S$30 on-site check to assess re-insulation |
| Sudden water gush 20 minutes after switching the aircon off | Thawing evaporator coil ice melting faster than the tray can drain | Inspect filters, dry floor, and book S$30 on-site check for airflow or gas fault |
Singapore Safety Stop-Line Around Leaking Wall Aircons
Unplug bedside chargers, power strips, and lamps beneath any leaking unit right away. Water running down plaster walls can seep into wall sockets and trip your flat's RCCB.
Observe EMA electrical rules by leaving the unit's 230V wire cover and wet trunking firmly closed. Never spray alkaline foam near indoor PCBs. Keep indoors per HDB and MOM safety limits, staying off external ledges and away from gas valves.
Next Step Once You Know Whether Pan, Louvre, or Pipe Leaks
Shutting doors and raising the remote to 25°C stops light louvre mist when filters are clean. Wall streaks or weeping trunking need clearing or fresh Class 0 foam before paint bubbles.
Match your trace result to Snowflake Aircon Services published rates:
- Basic general servicing bills S$50 (single), S$30 per fan coil (pair), or S$25 per fan coil (three+). This clears early front-pan clogs.
- Chemical wash bills S$80 (single), S$70 per fan coil (pair), or S$60 per fan coil (three+). Book this when sticky jelly coats the tray and coil.
- Chemical overhaul bills S$150 (single), S$125 per fan coil (pair), or S$115 per fan coil (three+). Choose this when water runs down the back wall.
- Request a S$30 fault inspection (offset in full upon repair) for sweating trunking joints, false ceiling stains, or thaw floods.