A living-room split in a Woodlands HDB flat runs non-stop every afternoon yet never pulls the hall below stuffy room temperature. Coolness can be felt only by holding a hand inches from the louvre. Rinsing the mesh filters at home restores almost no airflow across the seating area.
- Setup
- Mitsubishi Electric Wall-mounted7-9 yearsHDBWoodlands
- Misread as
- Paying for an unnecessary R32 gas top-up or leak search because a living-room split ran continuously yet never chilled the hall.
- Check first
- Opening the outdoor panel with manifold gauges connected to prove full R32 pressure before stripping the indoor cover to inspect the blower drum
- Actual finding
- Heavily fouled indoor blower wheel and coated evaporator fins starving living-room airflow while the Starmex R32 charge holds normal operating pressure
- Scope saved
- Servicing or adjustment with no parts replaced

What Else Produces This
Continuous running with weak room cooling triggers common fears of low gas. Connecting manifold gauges outdoors first rules out a refrigerant leak before focusing on indoor airflow.
Opening the outdoor cover and fitting gauges reads steady R32 gas pressure right inside normal cool range.
Feeling the copper return pipe shows brisk cold flow back to the outdoor unit, proving strong coil cooling.
Lifting the indoor front cover and shining a torch behind the vane exposes thick grey lint packed inside the blower blades.
Checking the upper indoor coil shows sticky grey grime bridging the fins and blocking air draw across the centre.
Why It Happens
Years of humid Woodlands hall use and cooking mist bonded sticky lint onto the indoor blower blades and coil face. Although the outdoor Starmex unit held full R32 gas, the choked wheel could not push cold air out into the room. Warm hall air stayed near the sensor, keeping the unit running non-stop.
What Resolution Involves
Remove the outdoor gauges with zero gas added and leave every brass joint sealed. Fit a wash bag beneath the indoor wall unit and coat the dirty fins and blower wheel with coil cleaner. Rinse the grime clear through the drain tray at published chemical wash rates (S$80 single, S$60 each for three or more).
How to Tell It Worked
Refit the indoor casing and run the Woodlands living-room unit at 23°C on medium fan. Confirm strong, even air throw reaching across the hall, crisp cold outlet air, and normal compressor cycling once the room hits setpoint.
Before You Approve a Quote
Confirm outdoor gas levels before agreeing to a refill
- A unit running non-stop with weak cooling often comes from choked indoor airflow rather than missing gas.
- Checking the outdoor unit first proves whether the sealed gas loop is already full, preventing overcharging.
- Chemical servicing at S$80 for one unit or S$60 each for three or more clears the sticky indoor fan wheel with zero gas added.