Is Mitsubishi Heavy Industries Aircon Good? Repair View

Mitsubishi Heavy Industries builds a capable split system, and the efficiency ratings show it. Whether it suits a given home depends on the warranty paperwork and who will service it.

On this page

Is Mitsubishi Heavy Industries aircon good?

Yes, as equipment: MHI household splits are registered with NEA at 4 and 5 ticks. The weak points are in ownership, mainly a 14-day registration window and a warranty that never pays labour.

The strengths and watch points below come from the NEA register and MHI's own Singapore terms.

Is Mitsubishi Heavy Industries aircon good? summary table
AspectWhat worksWhat to watch
EfficiencySRC single splits at 4 or 5 ticks; SCM multi-splits all at 5Compare weighted COP within the same capacity band
RangeSingle splits from 2.5 to 7.1 kW; multi-splits from 4.3 to 8.0 kWIndoor and outdoor units pair only within MHI's own combinations
Compressor cover5 years on the compressorLabour, transport and refrigerant charging excluded, even in year one
RegistrationOne rule: register with KM MarketingMiss the 14 days from purchase and the warranty is not effective
Warranty repairsOne route: KM Marketing or its appointed agentsA repair by anyone else puts the claim at risk
Second-hand unitsThe unit itself can still be serviced and repairedChange of ownership is outside MHI's warranty

Who an MHI system suits

An MHI system suits a buyer who registers it on installation day and keeps to a servicing schedule. MHI's terms do not cover damage caused by poor maintenance.

Its Singapore FAQ asks owners to have units inspected and maintained regularly by a certified service company.

  • Good fit: a new system installed and registered by an MHI dealer.
  • Good fit: replacing an MHI indoor unit on a working MHI outdoor unit.
  • Weaker fit: a second-hand MHI unit, since change of ownership is outside the warranty.

What the common MHI codes point to

MHI's indoor display shows faults as E-codes. Each code names a circuit, so the check starts there before any part is quoted.

An E35 and an E36 both stop the outdoor unit, but for different reasons. The registry lists low gas as a cause of E36, not of E35.

What the common MHI codes point to summary table
MHI codeWhat it meansCauses the registry lists
E7Room temperature sensorThe sensor or its connection
E9Drain faultThe drain pan, pipe or float
E16Indoor fan motor errorThe fan motor or its wiring
E35Cooling high pressure protectionOverload, overcharged refrigerant, a broken outdoor coil sensor wire, or a closed service valve
E36Compressor overheatLow gas, a faulty discharge pipe sensor, or a closed service valve

Before you buy or keep one

Register the unit within 14 days and keep the confirmation. Ask the installer who holds parts for the model, and file each servicing invoice alongside the purchase receipt.

The Mitsubishi Electric or Heavy Industries comparison sets the two Mitsubishi warranties side by side. For MHI against Panasonic, see the Mitsubishi Heavy vs Panasonic guide.

Common questions

Is Mitsubishi Heavy Industries a good aircon brand?
Mitsubishi Heavy Industries household aircons are capable split systems, registered with NEA at 4 and 5 ticks. The trade-offs are ownership ones. The unit must be registered within 14 days, and the warranty never covers labour, transport or refrigerant charging, even in the first year.
What warranty does a Mitsubishi Heavy Industries aircon have in Singapore?
Mitsubishi Heavy Industries' Singapore terms give 12 months on all parts and 5 years on the compressor only. Labour, transport and refrigerant charging are not covered. The unit must be registered with KM Marketing within 14 days of purchase, and repairs must go through KM Marketing or its agents.
What does E9 mean on a Mitsubishi Heavy aircon?
E9 on a Mitsubishi Heavy Industries household aircon is a drain fault. The drain pan, the drain pipe and the float switch are checked and cleared first. A part or board is quoted only once the drain path has been ruled out as the cause.
Does the MHI warranty transfer to a new owner?
No. Mitsubishi Heavy Industries' Singapore terms list change of ownership among the cases the warranty does not cover. A second-hand MHI aircon can still be serviced and repaired, but any repair is paid for by the new owner from the first day.

Sources