Living-room air from an older wall unit in a Clementi HDB flat turns mild roughly three months after every gas refill. Airflow across the louvres stays strong, and the indoor filter looks spotless. Along the service-yard window, outer pipe tape has weathered dark and damp.
- Setup
- Daikin Wall-mounted10-12 yearsHDBClementi
- Misread as
- Spending endlessly on short-lived gas top-ups or ripping out full living-room trunking across an older Clementi flat.
- Check first
- Pressurising the pipe circuit with dry nitrogen and soap-testing bare copper bends beside the service-yard window

What Else Produces This
Cooling that recovers briefly after top-ups and fades on a steady cycle confirms escaping refrigerant rather than a weak compressor. Isolating and pressurising the copper run separates a wall-buried leak from an accessible window bend.
Manifold gauges confirm low standing pressure while both indoor and outdoor coils show no oily trails.
Peeling away cracked tape beside the service-yard window uncovers green copper verdigris sitting under soggy foam lagging.
Pressurising the circuit with dry nitrogen and brushing leak-test soap onto the green spot raises a steady stream of fine bubbles.
Adjacent copper upstream and downstream measures clean bright wall thickness suitable for a local brazed repair.
Why It Happens
Service-yard windows in Clementi HDB flats expose pipe bundles to rain splash, detergent mist, and sun-baked UV glare. Once outer vinyl tape cracks, rainwater wicks inside foam lagging and sits trapped against the copper wall. Over ten to twelve years, damp corrosion eats a pinhole straight through the pipe.
What Resolution Involves
Recover any remaining gas safely instead of adding another blind refill. Cut away the corroded pipe span beside the window, braze in a clean copper section under nitrogen purge, and hold high-pressure dry nitrogen to confirm zero drop. Pull a deep vacuum, weigh in fresh R410A or R32 charge to factory spec, and seal new UV-resistant lagging.
How to Tell It Worked
Nitrogen gauges sit motionless across the pressure hold, and fresh soap solution shows zero bubbles around both brazed joints. Once vacuumed and charged by weight, the Clementi living-room unit delivers crisp cold discharge air with steady suction pressure and dry sealed pipework.
Before You Approve a Quote
Trace and braze exposed copper pinholes instead of repeating top-ups
- Aircon refrigerant never wears out inside a closed loop; losing chill within months always signals an active escape.
- Laundry steam and driving rain at Singapore HDB service-yard windows pit exposed or wet copper faster than indoor trunked runs.
- Cutting out the pitted section, welding fresh copper, pressure-testing the line, and recharging fresh refrigerant ends repeat refills.