Starmex Repeat Gas Leaks: Thick-Wall Copper Pipe Upgrade

Repeated gas loss in a Clementi HDB flat points to corroded thin-wall copper inside old trunking, not normal gas use. Upgrading to thick SWG22 copper and fresh lagging ends leaks for good.

On this page

How This Presents

A living-room split in a Clementi resale HDB flat cools well for a few weeks after each gas top-up, then turns warm again. Paying S$80 to S$150 for repeat R410A refills adds up fast, yet both indoor and outdoor units still sound normal.

Setup
Mitsubishi Electric Wall-mounted10-12 yearsHDBClementi
Misread as
Paying for another short-lived gas top-up or replacing a sound aircon system when hidden copper lines keep leaking refrigerant.
Check first
Isolating the indoor and outdoor coils under nitrogen pressure to prove the leak lived in the corroded trunking run rather than the Starmex unit
Actual finding
Pinhole pitting along aged thin-wall copper piping trapped inside damp trunking, causing recurring refrigerant loss after every top-up
Scope saved
Root cause fixed once instead of repeat call-outs
Spiral copper pipe coil laid on a workshop floor
Fresh thick-walled SWG22 copper pipe coil prepared before replacing corroded old refrigerant piping in a Clementi resale HDB flat.

What Else Produces This

Repeat gas loss needs a proper leak check before adding more gas. Testing each section on its own shows whether the leak sits inside the units or in the pipe run.

  • Pressure tests on the outdoor valves and indoor flares stay tight with no leak trace.

  • Opening the old wall trunking in the Clementi flat shows wet, brittle foam stuck to dark green corroded copper.

  • Testing the isolated pipe run with dry nitrogen shows a steady pressure drop from tiny pinholes along the damp line.

  • Checking the old pipe wall shows thin-grade copper that is too soft and pitted for safe spot brazing.

Why It Happens

Over ten years in a Clementi resale flat, cracked foam let humid Singapore air sweat onto thin-wall copper tubing. Trapped water inside the trunking ate tiny pinholes along the copper wall. Every fresh gas refill leaked right back out within weeks.

What Resolution Involves

Skip another short-term refill and keep the sound Starmex units. Pull out the corroded pipes fully, lay fresh thick-walled SWG22 copper coil inside sealed Armaflex lagging, tighten fresh flare joints cleanly, pull a deep vacuum, and recharge gas by weight.

How to Tell It Worked

Hold a steady nitrogen pressure test on the new SWG22 run before vacuuming, then test the Clementi living-room Starmex on full cool. Vent air turns sharply cold, the cold pipe stays dry under tight foam, and gas pressure holds steady.

Before You Approve a Quote

Replace thin corroded copper lines instead of buying repeat gas refills

  • Aircons run as sealed loops, so losing cold air every few months always means a real leak in the system.
  • Older Singapore resale flats often hide thin copper lines inside wet trunking where damp air pits the metal into pinholes.
  • Switching the bad run to thick SWG22 copper with tight foam sleeves stops repeat leaks and saves a sound Starmex unit.

Questions This Case Answers

Why does an older Starmex keep losing gas after repeated top-ups in Singapore HDB flats?
Aircon gas does not get used up during cooling. Repeat gas loss in older HDB flats often starts when worn foam lets wet air sit on thin copper pipes. Over years of humid use, rust and pitting open tiny pinholes that leak fresh gas out.
Why is SWG22 copper piping used when replacing leaking aircon pipe runs?
SWG22 copper has a thicker pipe wall than budget thin tubing used in older jobs. That thicker wall holds up better against tight bends, flare cracks, and damp pitting in Singapore weather. It gives a lasting fix without repeat gas top-ups.
Does replacing leaking copper piping mean replacing the Mitsubishi Electric indoor and outdoor units?
Sound Mitsubishi Electric Starmex units can stay in use after a pipe upgrade if tests show both coils hold tight. Checking the indoor coil, outdoor unit, and pipe run separately stops homeowners from scrapping good hardware too soon.