How This Presents
A living-room split in a Clementi resale HDB flat cools well for a few weeks after each gas top-up, then turns warm again. Paying S$80 to S$150 for repeat R410A refills adds up fast, yet both indoor and outdoor units still sound normal.
- Setup
- Mitsubishi Electric Wall-mounted10-12 yearsHDBClementi
- Misread as
- Paying for another short-lived gas top-up or replacing a sound aircon system when hidden copper lines keep leaking refrigerant.
- Check first
- Isolating the indoor and outdoor coils under nitrogen pressure to prove the leak lived in the corroded trunking run rather than the Starmex unit
- Actual finding
- Pinhole pitting along aged thin-wall copper piping trapped inside damp trunking, causing recurring refrigerant loss after every top-up
- Scope saved
- Root cause fixed once instead of repeat call-outs

What Else Produces This
Repeat gas loss needs a proper leak check before adding more gas. Testing each section on its own shows whether the leak sits inside the units or in the pipe run.
Pressure tests on the outdoor valves and indoor flares stay tight with no leak trace.
Opening the old wall trunking in the Clementi flat shows wet, brittle foam stuck to dark green corroded copper.
Testing the isolated pipe run with dry nitrogen shows a steady pressure drop from tiny pinholes along the damp line.
Checking the old pipe wall shows thin-grade copper that is too soft and pitted for safe spot brazing.
Why It Happens
Over ten years in a Clementi resale flat, cracked foam let humid Singapore air sweat onto thin-wall copper tubing. Trapped water inside the trunking ate tiny pinholes along the copper wall. Every fresh gas refill leaked right back out within weeks.
What Resolution Involves
Skip another short-term refill and keep the sound Starmex units. Pull out the corroded pipes fully, lay fresh thick-walled SWG22 copper coil inside sealed Armaflex lagging, tighten fresh flare joints cleanly, pull a deep vacuum, and recharge gas by weight.
How to Tell It Worked
Hold a steady nitrogen pressure test on the new SWG22 run before vacuuming, then test the Clementi living-room Starmex on full cool. Vent air turns sharply cold, the cold pipe stays dry under tight foam, and gas pressure holds steady.
Before You Approve a Quote
Replace thin corroded copper lines instead of buying repeat gas refills
- Aircons run as sealed loops, so losing cold air every few months always means a real leak in the system.
- Older Singapore resale flats often hide thin copper lines inside wet trunking where damp air pits the metal into pinholes.
- Switching the bad run to thick SWG22 copper with tight foam sleeves stops repeat leaks and saves a sound Starmex unit.